22
Field specification setting mode of wired remote controller
Classification
Function
Detail
Code
Basic
Min.
Max.
Step
Unit
DHW
Booster heater
Operation
3031
1 (Yes)
0 (No)
1
-
-
Delayed time
3032
20
20
95
5
min
Overshoot
3033
0
0
4
1
°C
Compensation temperature
3034
10
0
20
1
°C
Disinfection
Operation
3041
1 (Yes)
0 (No)
1
-
-
Operation interval
3042
Fri
Mon
Sun
1 (All)
day
Start time
3043
23
0
23
1
hour
Target temp.
3044
70
40
70
5
°C
Holding time
3045
10
5
60
5
min
Solar heat panel
H/P interlocking
3061
0 (No)
0
1 (Yes)
-
-
3-way/DHW valve
Basic valve direction
3071
0
(Room/
Normal
Close)
0
1 (Tank/
Normal
Open)
-
-
Heating
Heat pump
Heating/hot water priority
4011
0 (Hot
water)
0
1
(Heating)
-
-
Heating priority
4012
0
-15
20
1
°C
Heating Off
4013
35
14
35
1
°C
Overshoot
4014
2
1
4
1
°C
Others
Outing mode
Temperature of cooling water
oulet
5011
25
5
25
1
°C
Room Temperature of cooling
Mode
5012
30
18
30
1
°C
Temperature of heating
discharge water
5013
15
15
55
1
°C
Indoor heating temperature
5014
16
16
30
1
°C
Temperature of auto heating
WL1 water
5017
15
15
55
1
°C
Temperature of auto heating
WL2 water
5018
15
15
55
1
°C
Temperature of hot water Tank
5019
30
30
70
1
°C
Saving hot water
Temperature of hot water Tank
5021
5
0
40
1
°C
Benefit kWh (Power
Peak control)
Operation
5041
0 (No)
0
1 (Yes)
-
-
Heat source for operation limit
5042
0 (All)
0
2
1
-
Contact Logic
5043 1 (High) 0 (Low)
1
-
-
•
The menu not supported by the product will not be displayed.