Cutting/Flaring the pipes

CAUTION

In case of welding the pipe, you must weld with nitrogen gas blowing.

Inclined

Damaged Surface

Cracked

Uneven Thickness

Oblique

Rough

Burr

1

Make sure that you have the required tools available.  
(pipe cutter, reamer, flaring tool and pipe holder).

2

If you wish to shorten the pipes, cut it with a pipe cutter, taking care to ensure 
that the cut edge remains at a 90° angle with the side of the pipe. Refer to the 
illustrations below for examples of edges cut correctly and incorrectly.

3

To prevent any gas from leaking out, remove all burrs at the cut edge of the 
pipe, using a reamer.

4

Slide a flare nut on to the pipe and modify the flare.

Outer diameter (D)

 Depth (A)

 6.35 mm (1/4”)

9.52 mm (3/8”)

12.70 mm (1/2”) 

15.88 mm (5/8”)

19.05 mm (3/4”)

1.3mm

1.8mm

2.0mm 

2.2mm

2.2mm

5

Check that the flaring is correct, referring to the illustrations below for 
examples of incorrect flaring.

6

Align the pipes and tighten the flare nuts first manually and then with 
a torque wrench, applying the following torque.

Valve

Flare nut

Valve cap

Pressure port cap

Valve needle

Pressure port

Wrench(mm)

N•m

Wrench(mm)

N•m

Wrench(mm)

N•m

Wrench(mm)

N•m

Wrench(mm)

N•m

1/4"

17

18

23

20

18

16~18 Allen(hex.) 5

9

-

0.34

3/8"

22

42

23

20

18

16~18 Allen(hex.) 5

9

-

0.34

1/2"

26

55

29

40

18

16~18 Allen(hex.) 5 13

-

0.34

5/8"

29

65

29

40

18

16~18 Allen(hex.) 5 13

-

0.34

3/4"

36

100

38

40

18

16~18 Allen(hex.) 5 13

-

0.34

FJM CONSOLE_IM_29317A_E_10.16.08.indd   12

2008-11-24   15:41:33

Summary of Contents for MH052FJEA

Page 1: ...FJM CONSOLE_IM_29317A_E_10 16 08 indd 1 2008 11 24 15 41 20 ...

Page 2: ...hat the national safety code requirements have been followed for the main supply circuit Ensure that a properly sized and connected ground wire is in place Check if the voltage and the frequency of the main power supply are those required for the unit to be installed and check the connection Make sure that properly sized disconnecting and safety switches are installed Do not attempt to repair move...

Page 3: ...he wires firmly to the terminal block connecting sections so that the pressure is not applied to the sections Inappropriate connection and fixing could cause fire Avoid the use of an extension cord and do not share the power outlet with other appliances Incomplete connection defective insulation or exceeding the permissible current may cause electric shock or fire Make sure that the refrigerant ga...

Page 4: ...s pipe water pipe lightning rod or telephone grounding Defective grounding could cause electric shock Do not install the unit in a place where it is exposed to inflammable gas leakage There is a risk of explosion Install a ground leakage breaker depending on the installation place where it is humid If not it may cause electric shock Perform the drainage piping work securely according to the instal...

Page 5: ...n 9 Purging the unit 10 Connecting the refrigerant pipe 11 Cutting Flaring the pipes 12 Performing leak test insulation 13 Drain hose installation 14 Connecting the connection cord 15 Assigning address to indoor unit 16 Troubleshooting 17 Additional accessories 20 FJM CONSOLE_IM_29317A_E_10 16 08 indd 5 2008 11 24 15 41 21 ...

Page 6: ...locations where it could come into contact with water for example rooms used for laundry In areas where curtains and furniture could affect the supply and discharge of air Without leaving the required minimum space around the unit as shown in the drawing In scarcely ventilated areas On surfaces that are unable to support the weight of the unit without deforming breaking or causing vibrations durin...

Page 7: ...ound the indoor unit Make sure that the water dripping from the drain hose runs away correctly and safely Do not install the unit where it will be exposed to direct sunlight Space requirements for indoor unit air e ng y ncy The units must be installed according to distances declared in order to permit accessibility from each side either to guarantee correct opera tion of maintenance or repairing p...

Page 8: ...rant charge see the outdoor unit installation manual No Name Description MH026 035FJEA MH052FJEA 1 Liquid pipe connection ø6 35 Φ6 35 2 Gas pipe connection ø9 52 Φ12 7 3 Drain pipe connection ID ø12 OD ø18 4 Power supply connection Dimension And Weight MH FJEA Net Dimension Indoor Unit mm 720 620 199 Net Weight Indoor Unit kg 15 2 FJM CONSOLE_IM_29317A_E_11 24 08 indd 8 2008 11 28 9 59 03 ...

Page 9: ...er overflowing 3 Please remove the items when set is installed MH026 035FJEA 6 Items MH052FJEA 7 Items 4 The body front should be opened to connect pipes Please release the 4 screws of body front and then pull it out from the bottom of the set Indoor unit installation It is recommended to install the refnet joint before installing the indoor unit Screw Hole Screw Hole Position of drain Position of...

Page 10: ...until you are ready to connect the piping Indoor unit installation Continue The designs and shape are subject to change according to the model Purging the unit 5 Making a hole on the wall 6 The pipes cable should be go through the bottom back hole 7 Hanging the indoor unit on the Bracket Hanger then fix the Indoor Unit by using 4 Screws Case 1 Installing on the floor Must fix 4 screws on the wall m...

Page 11: ... if the installed area is warm and humid 6 Do not use joints or extensions for the pipes that connect the indoor and outdoor unit The only permitted connections are those for which the units are designed CAUTION Use the bender which have a minimum bending radius when you bend the pipe Be careful so that the pipes is bended one time only Piping will be very difficult if you repeat the bending more ...

Page 12: ... a flare nut on to the pipe and modify the flare Outer diameter D Depth A 6 35 mm 1 4 9 52 mm 3 8 12 70 mm 1 2 15 88 mm 5 8 19 05 mm 3 4 1 3mm 1 8mm 2 0mm 2 2mm 2 2mm 5 Check that the flaring is correct referring to the illustrations below for examples of incorrect flaring 6 Align the pipes and tighten the flare nuts first manually and then with a torque wrench applying the following torque Valve ...

Page 13: ...eaks in the system you can insulate the piping and hose 1 To avoid condensation problems place T13 0 or thicker Acrylonitrile Butadien Rubber separately around each refrigerant pipe Note Always make the seam of pipes face upwards 2 Wind insulating tape around the pipes and drain hose avoiding to compress the insulation too much 3 Finish wrapping insulating tape around the rest of the pipes leading...

Page 14: ... drain hose under the refrigerant pipe keeping the drain hose tight 5 Pass the drain hose through the hole in the wall Check if it slants downwards as seen in the picture The hose will be fixed permanently into position after finishing the installation and the gas leak test refer to page 11 for further details Shield Drain hose Extension drain hose No default resource The hose must NOT slant upwar...

Page 15: ... the ceiling the hole on the wall 4 Reassemble the electrical component box cover carefully tightening the screw Alwaysremembertoconnecttherefrigerantpipesbeforeperformingtheelectricconnections Whendisconnectingthesystem alwaysdisconnecttheelectriccablesbeforedisconnectingtherefrigerantpipes Alwaysremembertoconnecttheairconditionertothegroundingsystembeforeperforming theelectricconnections CAUTION...

Page 16: ... remote control centralized control etc see an appropriate installation manual 5 If an optional accessory is not installed you do not have to set the RMC address However adjust K1 and K2 switches of the SW05 DIP switch to ON position in this case 6 Set the MAIN address by adjusting the rotary switch SW02 from 0 to F Each indoor unit connected to the same outdoor unit must have different address If ...

Page 17: ...minutes 2 Error on the communication received from outdoor unit 3 Outdoor unit tracking time out 3 minutes 4 Number of Installation doesn t match after tracking X X X 1 Indoor unit error Display is unrelated with operation 2 Outdoor unit error Display is unrelated with operation Simultaneous cooling heating operation error Multi mode only X X X If you turn off the air conditioner when the LED is f...

Page 18: ...ak error Inverter DC Link voltage 150V or less 410V or more Inverter Compressor rotation error Inverter Electric current error Inverter DC Link sensor error Inverter EEPROM READ WRITE error Inverter Inverter zerocrossing error Setting the outdoor unit capacity option error X X EEPROM error X X EEPROM option error MPI no feedback Error X X X X If you turn off the air conditioner when the LED is fli...

Page 19: ...Indoor Temp Sensor Open Short Error Indoor Unit Eva in Sensor Open Short Error EEPROM ERROR EEPROM Option setting error If an error occurs is displayed on the wired remote control If you would like to see an error code press theTest button Indoor unit Wired Remote Display Error Mode Option resource FJM CONSOLE_IM_29317A_E_10 16 08 indd 19 2008 11 24 15 41 42 ...

Page 20: ...manual Wired Remote Controller Accessories Wired remotecontroller 1 Cable tie 2 Cable clamp 5 M4x16 tapped screw 7 Indoorunitpower drawingcable 1 Communication cableofthewired remotecontroller 1 Wire joint 1 Owner s instructions 1 Installationmanual 1 Wireless Remote Controller Accessories Wireless remotecontroller 1 Batteriesfor remotecontroller M4x12 tapped screw Remote con trol holder User s ma...

Page 21: ... Transmitter communication cable Installation manual 1 1 1 Transmitter accessories Note If you would like to install the centralized control you must install the transmitter in the outdoor unit 7 day scheduler 1 Cable tie Cable clamp M4x16 tapped screw User s manual Installation manual 2 2 4 1 1 7 day scheduler accessories FJM CONSOLE_IM_29317A_E_10 16 08 indd 21 2008 11 24 15 41 45 ...

Page 22: ...FJM CONSOLE_IM_29317A_E_10 16 08 indd 22 2008 11 24 15 41 46 EEE Yönetmeliğine Uygundur This EEE is compliant with RoHS ...

Page 23: ... Multi Air Conditioner Cooling and Heating INSTALLATION MANUAL MH FJEA Series ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH EΛΛHNIKA DB98 29317A 5 S E F I D P G FJM CONSOLE_IM_29317A_E_10 16 08 indd 23 2008 11 24 15 41 46 ...

Reviews: