28_
appendix
OPERATION RANGES
The table below indicates the temperature and humidity ranges the air conditioner can be operated within.
Refer to the table for efficient use.
MODE
OPERATING CONDITIONS
IF OUT OF CONDITIONS
COOLING
Indoor temp: 16˚C~32˚C
- A safety device will stop continuously
the system functioning;
- Condensation may occur on the indoor
unit with risk to have either water blow
off or drops on the floor;
Indoor humidity: below 80%
Outdoor temp: -5˚C~43˚C
HEATING
Indoor temp: below 27˚C
- A safety device will stop continuously
the system functioning;
Outdoor temp: -15˚C~24˚C
DEHUMIDIFYING
Indoor temp: 16˚C~32˚C
- A safety device will stop continuously
the system functioning;
- Condensation may occur on the indoor
unit with risk to have either water blow
off or drops on the floor;
Indoor humidity: below 80%
Outdoor temp: -5˚C~43˚C
POWER SUPPLY
Single phase rated voltage
minimum and maximum limit
220-240V~, 50Hz
198V - 264V
• Any damage occurs out of condition specified cannot be covered by product warranty. If the system
works continuously outside of conditions, its performance and reliability will be compromised.
• If the outdoor temperature is as low as 0°C, the heating capacity may drop depending on the
operating condition.
Summary of Contents for MH052FJEA
Page 2: ......
Page 30: ...appendix _29 ENGLISH ...