Samsung MH050FXEA2 Series Installation Manual Download Page 31

"EEE Yönetmeliğine Uygundur" 
"This EEE is compliant with RoHS"

FJM_IM_DB98-31792_E_6.10.10.indd   32

2010-6-10   9:54:23

Summary of Contents for MH050FXEA2 Series

Page 1: ...on If the refrigerant gas of the indoor unit leaks and comes into contact with the fan heater space heater or stove harmful gas will be generated Ensure that the national safety code requirements have been followed for the main supply circuit Ensure that a proper ground wire is in place Do not connect the ground to a gas pipe water pipe lightning rod or telephone grounding Defective grounding coul...

Page 2: ...rtation and do not install or use damaged equipment After completing the installation run the trial operation If no error occurs explain to the customer how to use and clean the air conditioner according to the user s manual In addition give the installation manual and the user s manual to the customer All of the manufacturing and packaging material used for your new appliance are compatible with ...

Page 3: ...unit 15 Connecting the refrigerant pipe 15 Cutting Flaring the pipes 16 Performing leak test insulation 17 Drain hose installation 18 Connecting the connection cord 20 Increasing Fan Speed 22 Assigning Address to Indoor Unit 23 Additional Functions 24 Filter Replacement 25 Drain pump Installation Optional 27 Placing the Indoor Unit in Position 29 Troubleshooting 30 FJM_IM_DB98 31792_E_6 10 10 indd...

Page 4: ...e curtains and furniture could affect the supply and discharge of air Without leaving the required minimum space around the unit as shown in the drawing In scarcely ventilated areas On surfaces that are unable to support the weight of the unit without deforming breaking or causing vibrations during the use of the air conditioner In a position that does not enable the condensate drainage pipe to be...

Page 5: ...nd the bottom of indoor unit Otherwise the noise from the vibration of indoor unit may bother the user When the ceiling is under construction the hole for check up must be made to take service clean and repair the unit It is possible to install the unit at an height of between 2 2 2 5m from the ground if the unit has a duct with a well defined lenght 300mm or more to avoid fan motor blower contact...

Page 6: ...m 30 m 15m 7 5 m Composition A B A B H h Piping length and the height Main power switch 300 mm minimum 300 mm minimum 600 mm minimum CAUTION 3 m as minimum pipe length It will reduce noise and vibration This value must be increased at 7 5 meters in case it is connected just one indoor unit System can work with one indoor unit connected but it is recommended that the TOTAL number of indoor unit sug...

Page 7: ...minimum 300 mm minimum 600 mm minimum 300 mm minimum CAUTION 3 m as minimum pipe length It will reduce noise and vibration This value must be increased at 7 5 meters in case it is connected just one indoor unit System can work with one indoor unit connected but it is recommended that the TOTAL number of indoor unit suggested by manufacturer are connected to obtain the maximum performance The appea...

Page 8: ... length and the height C D Main power switch 600 mm minimum 300 mm minimum 300 mm minimum 600 mm minimum CAUTION 3 m as minimum pipe length It will reduce noise and vibration This value must be increased at 7 5 meters in case it is connected just one indoor unit System can work with one indoor unit connected but it is recommended that the TOTAL number of indoor unit suggested by manufacturer are c...

Page 9: ...exible hose Drain pipe holder Insulation D Insulation cover band E Putty Cable Tie Wired remote controller box Wired remote control accessories Wired remote control Cable tie Cable clamp M4x16 tapped screw Indoor unit power drawing cable Communication cable of the wired remote control Wire joint User s manual Installation manual Installation manual User s manual FJM_IM_DB98 31792_E_6 10 10 indd 10...

Page 10: ...900 1000 500 MH026FEEA MH035FEEA NJ026LHXEA NJ035LHXEA No Name Description 1 Liquid pipe connection ø6 35 2 Gas pipe connection ø9 52 3 Hose connection 4 Hose connection 5 Power supply Communicaion connection 6 Power supply connection 7 Air discharge grille flange 8 Air inlet grille flange M8 M10 Air outlet duct flange Suspension position Suspension position hole Air around Unit mm Discharge side ...

Page 11: ...1 5 4 4 1 12 9 1 7 0 0 1 0 1 3 322 966 Air outlet duct flange Suspension position Suspension position hole Air around Unit mm No Name Description 1 Liquid pipe connection ø6 35 2 Gas pipe connection ø12 7 3 Drain pipe connection 4 Drain pipe connection 5 Power supply connection 6 Air discharge flange 7 Air filter 8 Hook M8 M10 Discharge side Suction side FJM_IM_DB98 31792_E_6 10 10 indd 12 2010 6 ...

Page 12: ...e Suspension position No Name Description 1 Liquid pipe connection ø6 35 2 Gas pipe connection ø12 7 3 Drain pipe connection OD32 ID26 without drain pump 4 Drain pipe connection Using drain pump Optional 5 Power supply connection 6 Air discharge flange 7 Air filter 8 Hook M8 M10 Unit mm MH052FUEA Discharge side Suction side FJM_IM_DB98 31792_E_6 10 10 indd 13 2010 6 10 9 53 38 ...

Page 13: ...una operación en el techo falso para poder usarlo y efectuar las operaciones requeridas en la unidad interna 4 Screw eight nuts to the suspension bolts making space for hanging the indoor unit CAUTION You must install all the suspension rods 5 Hang the indoor unit to the suspension bolts between two nuts Note Piping must be laid and connected inside the ceiling when suspending the unit If the ceil...

Page 14: ...s A smaller one for the liquid refrigerant A larger one for the gas refrigerant The inside of copper tube must be clean has no dust The connection procedure for the refrigerant pipes varies according to the exit position of the pipes from the indoor unit as seen when facing the indoor in the A side Liquid refrigerant port Gas refrigerant port Drain hose connection port 1 Remove the pinch pipe on t...

Page 15: ...flaring 6 Align the pipes and tighten the flare nuts first manually and then with a torque wrench applying the following torque Cutting Flaring the pipes CAUTION In case of welding the pipe you must weld with nitrogen gas blowing Inclined Damaged Surface Cracked UnevenThickness Oblique Rough Burr Valve Flare nut Valve cap Pressure port cap Valve needle Pressure port Wrench mm N m Wrench mm N m Wre...

Page 16: ...pipes leading to the outdoor unit 4 The pipes and electrical cables connecting the indoor unit with the outdoor unit must be fixed to the wall with suitable ducts All refrigerant connection must be accessible in order to permit either unit maintenance or removing it completely CAUTION LEAKTESTWITHNITROGEN beforeopeningvalves Inordertodetectbasicrefrigerantleaks beforerecreatingthevacuumand recircu...

Page 17: ...ote Fix the flexible hose to the indoor unit with the supplied cable clamp securely Use the screwdriver to fix the flexible hose securely 3 Install the drain hose so that its length can be as short as possible Internal diameter of the drain hose should be the same or slightly bigger than the external diameter of the drain hose port Inner diameter of the drain hose Note Give a slightly slant to the...

Page 18: ... allowed to hang loose from its connection to the unit Fasten the hose to a wall frame or other support as close to the unit as possible Upward gradient Ceiling Support pieces Ceiling When not installing the drain pump Do not give the hose upward gradient after the connection port This will cause water to flow backwards when the unit is stopped resulting in water leaks Water supply intake MH FEEA ...

Page 19: ... unit through the ceiling the hole on the wall 3 Reassemble the electrical component box cover carefully tightening the screw 4 Between Indoor and Outdoor Connection Cord Specifications 220 240V 50Hz 10 1 0mm2 or more H07RN F 3 wires Ø 1 6mm 2 wires 0 75 1 25mm2 H07RN F 2 wires 0 75 1 25mm2 2 wires Power Supply Single Phase Power Supply Max Min V ConnectionWire Earth Cable Communication Cable Home...

Page 20: ...e may be cross connected however it is recommended that they are connected to the corresponding F3 and F4 terminal over nect he 2 o 1 L 2 N 1 L 2 N Vc Vc Vw Vw F1 F2 V1 V2 F3 F4 V2 V1 Receiver Display Unit Optional Float Switch Drain Pump Optional COM2 F3 F4 Wired Remote Controlle MAIN PCB Indoor Unit Between Indoor and Outdoor Communication Terminal Indoor Power Terminal Outdoor Unit CN51 BLK CN3...

Page 21: ... the OFF position 2 Re install the cover plate and join the removed screw 3 Function Normal speed High speed External Static Pressure mmAq MH026FEEA NJ026LHXEA MH035FEEA NJ035LHXEA MH052FEEA 1 0 015201 1400FB 015201 16025D 011223 194108 015201 14020C 015201 16026E 011223 194119 015201 140360 015201 1603C4 011223 1941AC 015201 1403A2 015203 160108 011223 19431D 2 0 3 0 4 0 K1 K2 K3 K4 SW05 Mark is ...

Page 22: ...r properly 3 It is required to set the RMC address if you install the wired remote control ler and or the centralized controller 4 If you install optional accessories such as the wired remote controller central ized controller etc see an appropriate installation manual 5 If an optional accessory is not installed you do not have to set the RMC address However adjust K1 and K2 switches of the SW05 D...

Page 23: ... use Use No Function ON OFF SW06 K5 IndoorTemperature Compensation for Heating Mode 2 C 5 C K6 Filter Time 1 000 hours 2 000 hours K7 Hot Water Coil Not Use Use K8 No Function ON OFF SW07 K9 K10 K11 External control Not Use Use K12 External Control Output Thermal ON Operation ON K1 OFF Heating mode Setting temperature compensation value 0 C Thermo OFF Fan OFF FJM_IM_DB98 31792_E_6 10 10 indd 24 20...

Page 24: ...ccording to the following instruction Accessories Appearance Installation Diagram When air enters back side When air enters bottom side When air enters back side Suction Grille TEX Diffuser When air enters bottom side TEX Diffuser Suction Grille Bracket filter 2 Filter 2 Cap filter 1 FJM_IM_DB98 31792_E_6 10 10 indd 25 2010 6 10 9 54 17 ...

Page 25: ...her pad between the indoor unit and the support 4 When air enters back side Fix the indoor unit support to the top of the air inlet with screws 1 Put pads on the support 2 Put the indoor unit on the support 3 Installation Method When air enters bottom side Fix the cover to the back of the product with screws FJM_IM_DB98 31792_E_6 10 10 indd 26 2010 6 10 9 54 18 ...

Page 26: ... a clamp Change a clamp under the drain pump Note Fix it with 3 screws Note Accessories Connect the flexible hose to the flexible hose pump 3 Check a rubber ring is installed to the drain pump Stop the drain hole of the drain cushion with a drain cap Insulate the flexible hose Note Flexible hose pump 1 Drain pump Float switch 1 Drain cap 1 Flexible hose 1 Cable tie 4 Screw 3 Must fit tightly again...

Page 27: ...ube outlet on the right and left side of the indoor unit with an insulating materials Note Using Drain Pump X O CAUTION The drain pump must be installed by an installation specialist Before installing the optional kits ensure that you have turned off the main power You should use the original drain pump made in Samsung If you assemble the drain pump you are responsible for every claim caused from ...

Page 28: ...insulating tape around the pipes assembly cable and drain hose 3 Place the resulting bundle carefully in the lower part of the indoor unit making sure that it does not jut out from the rear of the indoor unit 4 Hook the indoor unit on to the installation plate and move the unit to the right and left until you are sure that it is securely in place 5 Finish wrapping vinyl tape around the rest of the...

Page 29: ...it Displayed on the indoor unit regardless of operation 2 Error of outdoor unit Displayed on the indoor unit which is operating Power reset Error of temperature sensor in indoor unit OPEN SHORT Error of heat exchanger sensor in indoor unit Error of heat exchanger OUT sensor in indoor unit Error of outlet temperature sensor in indoor unit OPEN SHORT For heat pump models only Error of mixed operatio...

Page 30: ...t not detected 1 Error of electronic expansion valve close 2 Error of electronic expansion valve open 3 Breakaway of EVA OUT sensor 4 Breakaway of EVA IN sensor 5 Breakaway of COND MID sensor 6 2nd detection of refrigerant completely leak 7 2nd detection of high temperature COND 8 2nd detection of high temperature DISCHARGE 9 COMP DOWN due to 2nd detection of low pressure switch 10 Error of revers...

Page 31: ... EEE Yönetmeliğine Uygundur This EEE is compliant with RoHS FJM_IM_DB98 31792_E_6 10 10 indd 32 2010 6 10 9 54 23 ...

Page 32: ...onditioner Cooling and Heating INSTALLATION MANUAL MH FEEA Series MH FUEA Series NJ LHXEA Series ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH EΛΛHNIKA DB98 31792A 2 S E F I D P G FJM_IM_DB98 31792_E_6 10 10 indd 33 2010 6 10 9 54 24 ...