background image

10

Indoor unit installation

It is recommended to install the refnet joint before installing the indoor unit.

1.  Place the pattern sheet on the ceiling at the spot where you want to install 

the indoor unit.

Since the diagram is made of paper, it may shrink or stretch slightly due 
to temperature or humidity. For this reason, before drilling the holes 
maintain the correct dimensions between the markings; refer to pages 
8~9.

2.  Insert bolt anchors, use existing ceiling supports or construct a suitable 

support as shown in figure.

3.  Install the suspension bolts depending on the ceiling type.

•   Ensure that the ceiling is strong enough to support the weight of the 

indoor unit.  Before hanging the unit, test the strength of each attached 
suspension bolt.

•  If the length of suspension bolt is more than 1.5m(59.06 inch), it is 

required to prevent vibration.

•  If this is not possible, create an opening on the false ceiling in order to 

be able to use it to perform the required operations on the indoor unit.

4.  Screw eight nuts to the suspension bolts making space for hanging the 

indoor unit.

You must install more than four suspension bolt when installing the 

indoor unit.

5.  Check the level of the indoor unit by using a leveler or a vinyl tube filled with 

water.

 - A tilt of the indoor unit may cause malfunction of a built-in float switch and 

water leaks.

6.  Adjust the height of the indoor unit by using the gauge of dimensions.

 - You should adjust the gauge of dimensions and the pattern sheet to fit the 

cutting dimensions of ceiling.

 - Make sure that the indoor unit is installed at a level if the indoor unit slants 

too much, there can be water leaks.

Ceiling

Gauge of Dimensions

Air 

inlet

Air 

outlet

15

m

m

(0

.5

9"

)

15

m

m

(0

.5

9"

)

MH

✴✴✴

FSBA

 

Ceiling

Gauge of 

Dimensions

17mm(0.67")

20mm(0.79")

Indoor unit

MH

✴✴✴

FSBA

7.  Tighten the upper part nuts.
8.  Remove the gauge of dimensions after installing the indoor unit.

Ceiling support

Concrete

Suspension bolt(3/8" or M10)

Hole in anchor
Hole in plug

Insert

Not supplied

Washer 

(supplied)

Rubber

Fasten the nut

Vinyl tube

Level

NOTE

CAUTION

CAUTION

FJM IDU-PH_Cassette type_IM_31595A-04_EN.indd   10

2015-11-16   오후 4:52:21

Summary of Contents for MH FMBA Series

Page 1: ...FJM IDU PH_Cassette type_IM_31595A 04_EN indd 26 2015 11 16 오후 4 52 24 ...

Page 2: ...N ES PT Cassette Type Series MH FSBA MH FMBA Air Conditioner installation manual imagine the possibilities ThankyouforpurchasingthisSamsungproduct FJM IDU PH_Cassette type_IM_31595A 04_EN indd 27 2015 11 16 오후 4 52 25 ...

Page 3: ...9 336 EEC and the Directive on pressurized equipment 97 23 EEC f f The manufacturer shall not be responsible for damage originating from unauthorized changes or the improper connection of electric and requirements set forth in the Operating limits table included in the manual shall immediately invalidate the warranty f f The air conditioner should be used only for the applications for which it has...

Page 4: ...ctions on how to operate the air conditioner to the user f f Do not use the air conditioner in environments with hazardous substances or close to equipment that release free flames to avoid the occurrence of fires explosions or injuries f f Our units should be installed in compliance with the spaces shown in the installation manual to ensure accessibility from both sides and allow repairs or maint...

Page 5: ... earth wire to the gas pipe water pipe lighting rod or telephone wire If earthing is not complete electric shock or fire may occur Install the circuit breaker If the circuit breaker is not installed electric shock or fire may occur Make sure that the condensed water dripping from the drain hose runs out properly and safely Install the power cable and communication cable of the indoor and outdoor u...

Page 6: ...mum space around the unit as shown in the drawing f f In scarcely ventilated areas f f On surfaces that are unable to support the weight of the unit without deforming breaking or causing vibrations during the use of the air conditioner f f In a position that does not enable the condensate drainage pipe to be correctly installed at the end of the installation It is always essential to check the eff...

Page 7: ... 295 27 inch to be respected f f Leave enough clearance beneath the indoor unit to enable the filters to be removed without hindrance f f Maintain sufficient clearance around the indoor unit f f Make sure that the water dripping from the drain hose runs away correctly and safely f f The indoor unit must be installed in this way that they are out of public access Not touchable by the users You have...

Page 8: ...06 ormore 1500mm 59 06 ormore The units must be installed according to distances declared in order to permit accessibility from each side either to guarantee correct operation of maintenance or repairing products The unit s parts must be reachable and removable completely under safety condition for people or things CAUTION FJM IDU PH_Cassette type_IM_31595A 04_EN indd 7 2015 11 16 오후 4 52 20 ...

Page 9: ...scription Liquid pipe connection ø6 35 1 4 Gas pipe connection ø9 52 3 8 Drain pipe connection OD 29 1 14 ID 25 0 98 Power supply connection Air discharge grille Air suction grille Dimension and weight Net dimension Indoor unit mm inch 970 38 19 x 135 5 31 x 410 16 14 Panel size 1180 46 46 x 25 0 98 x 460 18 11 Net weight Indoor unit Panel kg 13 FJM IDU PH_Cassette type_IM_31595A 04_EN indd 8 2015...

Page 10: ...uspension position 321 12 64 288 11 34 Suspension bolt 4 M8 M10 Freshairintakehole Unit mm inch No Name Description 030 035 052 Liquid pipe connection ø6 35 1 4 ø6 35 1 4 Gas pipe connection ø9 52 3 8 ø12 70 1 2 Drain pipe connection OD 29 1 14 ID 25 0 98 Power supply connection Air discharge grille Air suction grille Dimension and weight Net dimension Indoor unit mm inch 575 22 64 x 260 10 24 x 5...

Page 11: ...operations on the indoor unit 4 Screw eight nuts to the suspension bolts making space for hanging the indoor unit You must install more than four suspension bolt when installing the indoor unit 5 Check the level of the indoor unit by using a leveler or a vinyl tube filled with water A tilt of the indoor unit may cause malfunction of a built in float switch and water leaks 6 Adjust the height of th...

Page 12: ...ftover nitrogen could cause internal leakage Unscrew the pinch pipe at the end of each refrigerant pipe RESULT All inert gas escapes from the indoor unit To prevent dirt or foreign objects from getting into the pipes during installation do NOT remove the pinch pipe completely until you are ready to connect the piping Gas refrigerant port Liquid refrigerant port The designs and shape are subject to...

Page 13: ...nsulator which is thick enough to cover the refrigerant pipe to protect the condensate water on the outside of pipe falling onto the floor and the efficiency of the unit will be better 3 Cut off any excess foam insulation 4 Be sure that there must be no crack or wave on the bended area 5 It would be necessary to double the insulation thickness 10mm 0 39 or more to prevent condensation even on the ...

Page 14: ...19 7 mm 0 7598 0 7756 5 Check that the flaring is correct referring to the illustrations below for examples of incorrect flaring Flare nut Connectingpipe Indoor outlet pipe Inclined Damaged surface Cracked Uneven thickness 6 Align the pipes and tighten the flare nuts first manually and then with a torque wrench applying the following torque Valve Flare nut Valve cap Pressure port cap Valve needle ...

Page 15: ...r separately around each refrigerant pipe Always make the seam of pipes face upwards The insulation has to be produced in full compliance of European regulation reg EEC EU 2037 2000 that requires the use of sheaths insulation form without using CFC and HCFC gases for health and the environment 2 Wind insulating tape around the pipes and drain hose avoiding to compress the insulation too much 3 Fin...

Page 16: ...20 C 248 F 12 70 1 2 19 05 3 4 T13mm 0 51 T13mm 0 51 Gas pipe 6 35 1 4 T13mm 0 51 T19mm 0 75 9 52 3 8 T19mm 0 75 T25mm 0 98 12 70 1 2 15 88 5 8 19 05 3 4 When installing insulation in places and conditions below use the same insulation that is used for high humidity conditions Geological condition High humidity places such as shoreline hot spring near lake or river and ridge when the part of the b...

Page 17: ... supplied Insulation cover drain Insulation drain pipe Insulation cover band Band Adhesives Drainpipe Indoor Unit Check that the indoor unit is level with the ceiling by using the leveler Install air ventilation to drain condensate water smoothly Air ventilation Ceiling If it is necessary to increase the height of the drainpipe install the drainpipe straightly within 300mm 11 81 from the drain hos...

Page 18: ...se Testing the drainage You should test drainage after completing the installation Prepare a little water about 1 0 liter 1 0 quart 1 Open the cover water supply intake 2 Pour water into the water supply intake 3 Operate the unit in the Cool mode and check a drain pump pumping 4 Check drain water drops at the end of the drainpipe Drainpipe Drain water drops 5 Make sure there is no water leak at th...

Page 19: ...crew on the electrical component box and remove the cover plate 2 Route the connection cord through the side of the indoor unit and connect the cable to terminals refer to the figure below 3 Route the other end of the cable to the outdoor unit through the ceiling the hole on the wall 4 Reassemble the electrical component box cover carefully tightening the screw Wiring diagram Indoor Unit Outdoor U...

Page 20: ...hey are connected to the corresponding F3 and F4 terminal MH FSBA Indoor Unit PCB F1 F2 V1 V2 1 L 2 L F1 F3 F2 F4 V1 V2 Indoor unit rerminal block Accessory in the remote control CN32 CN33 WHT BLU Wired remote control optional MH FMBA Indoor Unit PCB 1 L 2 N Vc Vc V1 V2 F3 F4 F1 F2 F1 F3 F2 F4 V1 V2 Indoor unit rerminal block CN32 CN33 WHT BLU Wired remote control optional Dashed lines cables are ...

Page 21: ...or unit and the outdoor unit Therefore you must set it to operate the air conditioner properly 4 It is required to set the RMC address if you install the wired remote control and or the centralized control 5 If you install optional accessories such as the wired remote control centralized control etc see an appropriate installation manual 6 If an optional accessory is not installed you do not have ...

Page 22: ...6 K7 K8 SW06 SW06 K5 Indoor temperature compensation for heating mode 2 C 3 6 F 5 C 9 F K6 Filter time 1000 HR 2000 HR K7 K8 MH FMBA No Function ON OFF SW06 K5 Indoor temperature compensation for heating mode 5 C 9 F 2 C 3 6 F K6 Filter time 1000 HR 2000 HR K7 K8 No Function ON OFF K9 K10 K11 K12 SW07 SW07 K9 K10 K11 External control Not use Use K12 External control output Thermo on Operation on F...

Page 23: ...ety net 2 Fix the safety net to the electric component cover box with four screws as indicated The electric component box cover The safety net Air blocking kits 1 When installing the unit depending on the situation you can fill up the air outlet s with one or two max air blocking kits not supplied Then install the insulation to block air completely If the humidity goes over 65 do not block more th...

Page 24: ...mixed operation X X X Error of indoor fan motor Below 450RPM for 15 minutes X X X X Error of outdoor temperature sensor Error of COND sensor Error of DISCHARGE sensor X X X 1 No communication for 2 minutes between indoor unit and outdoor unit communication error for more than 2 minutes 2 Indoor unit receiving the communication error from outdoor unit 3 Outdoor unit tracking 3 minutes error 4 When ...

Page 25: ...E 4 Compressor down due to 6th detection of freezing X X Displayed on appropriate indoor unit which is operating Displayed on outdoor unit Error of float switch X X X Error of setting option switches for optional accessories X X X EEPROM error X X EEPROM option error On Flickering X Off f f If you turn off the air conditioner when the LED is flickering the LED is also turned off FJM IDU PH_Cassett...

Page 26: ...25 ENGLISH Memo FJM IDU PH_Cassette type_IM_31595A 04_EN indd 25 2015 11 16 오후 4 52 24 ...

Reviews: