9

<MCU-S1NEK1N>

ø 22.22 (ø 7/8)

ø 19.05 (ø 3/4)

ø 9.52 (ø 3/8)

 

ø 9.52 (ø 3/8) WELDING

ø 15.88 (ø 5/8) WELDING

Liquid pipe connected to indoor unit

Gas pipe connected to indoor unit

Space requirements

1.  Since refrigerant noise can be generated during the MCU operation, do not install the unit on the ceiling of the places 

that requires silence such as bedrooms, libraries, hospitals and offices etc.

2.  Do not install the MCU in the ceiling of the living area. Otherwise, noise generated from the MCU may disturb people in 

that area and cause inconvenience. 

<Spaces with developed ceiling>

<Ceiling of the office>

Summary of Contents for MCU Series

Page 1: ...MCU S6NEK2N MCU S4NEK3N MCU S2NEK2N MCU S1NEK1N MCU installation manual imagine the possibilities Thank you for purchasing this Samsung product ...

Page 2: ...2 Contents Safety precautions 3 Mesures de sécurité 5 Preparing the installation 7 Space requirements 9 Installing the unit 11 Refrigerant piping works 15 Wiring works 19 Commisioning 24 ...

Page 3: ... down and cause injury Check out the safety precautions below before installing or fixing the unit X Before welding the unit you must remove all the hazardous materials around the unit that may cause an explosion and a fire X When refrigerant is in the product or the pipe before welding the unit you must remove the refrigerant If you weld the unit when there is refrigerant inside the increased pre...

Page 4: ...nsulate the drain pipe so that frost does not generate X If the draining work is done incompletely property damage may occur due to a leakage Install the power cable and communication cable of MCU at least 1m away from the electric appliances and at least 2m away from the lightning rod X However you may hear a noise 1 meter away from the unit depending on the condition of the electric wave Install...

Page 5: ...t provoquer des blessures Consultez les précautions de sécurité ci dessous avant d installer et de fixer l appareil X Avant de souder l appareil vous devez retirer tous les matériaux dangereux qui se trouvent autour car ceux ci pourraient provoquer une explosion et un incendie X Si du fluide frigorigène se trouve dans l appareil ou dans les tuyaux avant le soudage vous devez retirer le réfrigérant...

Page 6: ... que les condensats s évacuent correctement par le tuyau de vidange conformément aux recommandations du présent manuel d installation et isolez le tuyau de vidange afin d éviter la formation de givre X Si l installation de la vidange est faite de façon incomplète des dommages matériels provoqués par des fuites d eau peuvent survenir Installez le câble d alimentation et le câble de communication de...

Page 7: ...er pipe must be used If an annealed type C1220T O copper pipe is used pipe may break due to its low pressure resistance and cause personal injury Outerdiameter Minimumthickness Tempergrade mm inch mm inch 6 35 1 4 0 70 0 028 Annealed 9 52 3 8 0 70 0 028 12 70 1 2 0 80 0 031 15 88 5 8 1 00 0 039 19 05 3 4 0 90 0 035 Drawn 22 22 7 8 0 90 0 035 25 40 1 1 00 0 039 28 58 1 1 8 1 10 0 043 31 75 1 1 4 1 ...

Page 8: ...U S2NEK2N MCU S1NEK1N IndoorUnit AM N MCUKit Model Description MCU S6NEK2N below 61 6 kW 216MBH MCU S4NEK3N below 61 6 kW 216MBH MCU S2NEK2N below 32 kW 108MBH MCU S1NEK1N below 16 kW 54MBH Gas pipe connected to indoor unit Liquid pipe connected to indoor unit Side view of MCU ø 28 58 ø 1 1 8 ø 28 58 ø 1 1 8 ø 9 52 ø 3 8 WELDING ø 15 88 ø 5 8 WELDING Unit mm inch ø 15 88 ø 5 8 MCU S6NEK2N MCU S4NE...

Page 9: ...e refrigerant noise can be generated during the MCU operation do not install the unit on the ceiling of the places that requires silence such as bedrooms libraries hospitals and offices etc 2 Do not install the MCU in the ceiling of the living area Otherwise noise generated from the MCU may disturb people in that area and cause inconvenience Spaces with developed ceiling Ceiling of the office ...

Page 10: ...ixed to the concrete of the ceiling 5 MCU may generate noise so don t install it too close to the ceilingTex 6 Each pipe hanger should be placed at 1 5m 4 92 interval to support its weight firmly If the pipe or the hanger isn t fixed firmly the unit may fall and cause a property damage or loss of life 7 When Low temperature cooling range expansion option is set for constant cooling operation throu...

Page 11: ...4NEK3N MCU S2NEK2N MCU S1NEK1N Example installing Each port connection Example installing MCU series connection MCU MCU Installing indoor units Under16 0kWindoorunit Don tuseY connector 16 0kW 28 0kWindoorunit UseY connectorattheGas Liquidline Ifyouwanttocontinuouscoolingoperationunder 5 C setoutdoor Expandoperationaltemperaturerangeforcooling operation HRonly anduseY connectoron5 0 16kWindoorunit...

Page 12: ...ions between the markings 2 Insert bolt anchors use existing ceiling supports or construct a suitable support as shown in figure Concrete Holeinanchor Holeinplug Suspension bolt 3 8 or M10 Insert 3 Install the suspension bolts depending on the ceiling type Ceiling support Ensure that the ceiling is strong enough to support the weight of the indoor unit Before hanging the unit test the strength of ...

Page 13: ...use the pattern sheet for installation that is provided with the product When welding the gas pipes protect the product with the flame proof sheet When connecting the MCU with outdoor units default direction is set in the MCU If installing opposite direction weld the enclosed copper cap in each high pressure low pressure and liquid pipes 6 How to connetY connector X In case of connecting one indoo...

Page 14: ...copper pipe Stop valve Taping Pressure regulator Flowmeter Insulation cover pipe Indoor unit Be sure to overlap the insulation Insulation pipe Method and cautions on refrigerant pipe insulation Make sure to check for gas leakage before completing the installation hose and pipe insulation and insulate hoses and pipes when there is no sign of leakage 1 To avoid condensation problems placeT13 0 1 2 o...

Page 15: ...after EEV kit and MCU f Install the gas side and liquid side pipes leave 10mm 3 8 of space f When contacting the gas side and liquid side pipe use 1 grade thicker insulation Gas pipe Liquid pipe Insulation Insulation Gas pipe 10mm 3 8 Liquid pipe 10mm 3 8 10mm 3 8 Install the insulation not to get wider and use the adhesives on the connection part of it to prevent moisture from entering Wind the r...

Page 16: ... communication line must be connected as shown in drawing Case 1 Case 2 220 240V 208 230V Single Phase Supply separately ELB MCCB Outdoor Unit Indoor Unit Indoor Unit ELB MCCB Outdoor Unit Indoor Unit Indoor Unit MCU Indoor Unit 220 240V 208 230V Single Phase Supply separately Case 3 ELB MCCB Outdoor Unit Indoor Unit MCU Indoor Unit Indoor Unit 220 240V 208 230V Single Phase Supply separately X Po...

Page 17: ...0 2 0 007 0 2 0 007 D Standard dimension mm inch 3 4 0 134 4 2 0 165 5 6 0 220 Allowance mm inch 0 3 0 011 0 2 0 007 0 3 0 011 0 2 0 007 0 3 0 011 0 2 0 007 d1 Standard dimension mm inch 1 7 0 066 2 3 0 090 3 4 0 133 Allowance mm inch 0 2 0 007 0 0 2 0 007 0 0 2 0 007 0 E Min mm inch 4 1 0 161 6 0 236 6 0 236 F Min mm inch 6 0 236 6 0 236 5 0 196 L Max mm inch 16 0 629 17 5 0 688 20 0 787 d2 Stand...

Page 18: ...ach port Set using each port connected to indoor unit by DIP switch Example If you want to connect indoor units at A B C F port set DIP switch 1 2 3 2 to ON DIP switch for indoor unit setting ON Use OFF Not use 1 ON 2 3 4 1 ON 2 1 ON 2 3 4 1 ON 2 DIP S W Default Using A B C F port 3 DIP switch setting for using Y connetor In case of using Y connector to connect 2 port Set DIP Switch S W option Exa...

Page 19: ...ddress setting mode 0 No Main address 0 9 100 digit 0 9 10 digit 0 9 Aunit digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE SettingRMCaddress Groupchannel 16 Groupaddress Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details 1 0 NoRMC address RMC1 0 F RMC2 0 F 1 RMC address setting mode ...

Page 20: ...setting checking MCUaddress 00 15 Portaddress A F None Setting for MWR SH10N 1 Pressthetoprightcorner hiddenbutton ofthedisplayformorethan3secondsanddropit Thenyoucanpress buttonsandselectNo 3andpress OK button 2 AssignanindoorunitMCUportaddresswithmainmenu4 submenu7 MCUaddressis assingnedtoSEG12 PortaddressisassingedtoSEG4 Ifyouwanttoknowthedetailed operationofMWR SH10N refertoinstallationmanualf...

Page 21: ... centralcontroller issettotheheatingmode En cas de réglage de l unité sur le mode refroidissement exclusif veillez à régler le SEG 9 chauffe eau de la série 02 sur 0 lors de l installation Lorsque l option de refroidissement uniquement est sélectionnée pour l unité aucun fonctionnement en mode chauffage n est possible lorsque le contrôleur de la télécommande sans fil ou central est réglé sur le mo...

Page 22: ...5 7 30min K1 Pushedtime DisplayContents Displaysegment Remarks 1 2 3 4 1 MCU address 0 Blank 0 0 MCU address 0 Blank 0 1 MCU address 1 Blank 0 2 MCU address 2 Blank 1 1 MCU address 11 Blank 1 5 MCU address 15 2 Mode switching EEV1 step 1 4 8 0 Ex 480 steps 3 Mode switching EEV2 step 2 4 8 0 Ex 480 steps 4 Mode switching EEV3 step 3 4 8 0 Ex 480 steps 5 Mode switching EEV4 step 4 4 8 0 Ex 480 steps...

Page 23: ...l Control MODE end P Communication DATA Display K2 Pushedtime DisplayContents Displaysegment Remarks 1 2 3 4 1 Indoor unit main address for matching with port A A 0 0 Indoor unit main address of port A 0 2 Indoor unit main address for matching with port B B 0 3 Indoor unit main address of port B 3 3 Indoor unit main address for matching with port C C 0 6 Indoor unit main address of port C 6 4 Indo...

Page 24: ...for R 410A has been used or not 5 Checking malfunction of the wire and the communication line 6 If the MCU frame has been installed upside down or not 7 If the wire earthing work has been done or not 8 If the space between sidewalls ceiling concrete and the ceilingTex has been secured enough or not to install the MCU frame 9 If the supporting tool of the MCU pipe has been safely placed in 1 5m int...

Page 25: ...5 ƊʪθЭ ϑ ʒ 9 Ɠ ŵ Ę ƟkçĘÑç ƊkŵǤÑƊࣛđk đkƟ 9 Ɠ ŵ Ę ǽʪϩ ʒ Ɗͱцɇʒ Ǥʪθ Uɇ θʪϑ ƊkŵÑç Ǥʪθ Ęͱ ߣߦߤߧߩߧߩ ߨߪߦ Ɵʪ ʪ ͱ Ęͱ ߢߤߦߤ ߩߤߤߢߧߦߪ ǽ9 Ęͱ ߢߩࣛ ǽ9ࣛߧߥߣ ʒθʪϑ çŁçkȐ đ øøkƊÑ 9Ƹŵđ ĘAà A UUkƊÑ ĘͱࡤߣߢߦࢩA Ɠʪ θ ĘƟ øǽ 6 ƊʪθЭ ϑ ʒ 9 ǽŵ ç køkçƟŵĮĘÑç Ɵ đÑŵ 9 çÃđ ÑȐđkƟøkŵÑ Ɗ Ę ƟÑA øƟU ƓƟÑ ǽʪϩ ʒ Ɗͱцɇʒ Ǥʪθ Uɇ θʪϑ ȐÑøkŵ Ǥʪθ Ęͱ ߣߧߧߢߧߦߦߪߨߪ Ɵʪ ʪ ͱ Ęͱ ߢߥߨߤߦߥߣߨߦߪߢ ǽ9 Ęͱ ߧߧࣛ ǽ9ࣛߤ ߤ ʒθʪϑ ߣ đ ǽÃƊ đ 9 øÑ A U ĘĮࡤߥߪ Ñøç UÃđࢩ SAMSUN Ɠʪ θ SAMS...

Page 26: ...ͱ ߥߥࣛ ǽ9ࣛ ߤߥ ʒθʪϑ ťÃĘ ŵ9 Ɠà đ øøkƊÑ Ɵ ƟDŽŵç 9ƸøǤ ŵà ĘͱࡤߨߣࢩA ࢩ đƸƟ Ɠʪ θ đkŵƊÑĘ 18 ƊʪθЭ ϑ ʒ đ ǤÑ ǽ đDŽ kĘUÑƊøÑç đ çÑĘk ÑĘƓ Ɵ køkçƟŵĮĘÑç Ɗ Ę ǽÑ Ǥk ƟÑA ŵkƟ øÑđÑƟkU ƓÑŵçkƟÑ ǽʪϩ ʒ Ɗͱцɇʒ Ǥʪθ Uɇ θʪϑ pamukkale Ǥʪθ Ęͱ ߨߣߥߢߨ ߤߤߩߧ Ɵʪ ʪ ͱ Ęͱ ߢߤߧߪߤߨߤߢߢߢ ǽ9 Ęͱ ߤߢࣛ ǽ9ࣛߣߤߤߣ ʒθʪϑ đʪθ ʪіʪ ʪ ʒ đɇ ɇ ʪϑ ߤ k 9Ї Эɇθ Ęͱࡤߥߩࢩ đɇЭ ɇц Ñϗ đʪθ ʪі đʪθ ʪіʪ ʪ ʒ ࢩUʪ і ࢩ UkĘÑȐøÑ Ɠʪ θ UkĘÑȐøÑ 19 ƊʪθЭ ϑ ʒ đk đkƟ øç ǽ ÑȐđkƟ køkçƟŵĮĘÑç Ɵk...

Page 27: ...ߣߨߦࢩ ࢩ ĮŵƟ ÑƊ ŵ Ɠʪ θ TRABZON 28 ƊʪθЭ ϑ ʒ Ƹ Ƹç Ęk9Ñ Ɵkđkø ǽʪϩ ʒ Ɗͱцɇʒ Ǥʪθ Uɇ θʪϑ kŵ ĘÑ Ǥʪθ Ęͱ ߣߩߦߪߤߪߪߥߪߧߦ Ɵʪ ʪ ͱ Ęͱ ߢߦߣߤߨߣߣߤߢߦߥ ǽ9 Ęͱ ߤߣࣛ ǽ9ࣛߥߥߥߥ ʒθʪϑ UĘ Ę đkĘUkŵkƊ đ øøkƊÑ ǽkĘÑ ø A UUkƊÑࡥ ƊĮç ç ߣࢩߣ ࢩ kŵ ĘÑ Ɠʪ θ UÑǽ ŵ9 çÃŵ 29 ƊʪθЭ ϑ ʒ DŽĘ ƊĮ ƸƟđ ࣛ çÑ DŽĘ ǽʪϩ ʒ Ɗͱцɇʒ Ǥʪθ Uɇ θʪϑ UŁŵƟǽĮø Ǥʪθ Ęͱ ߥߣߪߥߣߨߥߧߤߦߨ Ɵʪ ʪ ͱ Ęͱ ߢߥߤߨ ߩߣߤ ߥߪ ߢ ǽ9 Ęͱ ߥߣࣛ ǽ9ࣛߤߪ ʒθʪϑ ǽkƓÑø đ Ɵ ƟDŽŵç AU çkŵǤ Ę ƊĮç ĘĮࡤߦ Ɠʪ θ Ɵ ǽ 30 ƊʪθЭ ϑ ...

Page 28: ...DB68 06903A 00 ...

Reviews: