Troubleshooting
Samsung Electronics
5-16
5-3-3 Detailed Procedure
No.
1
2
3
Malfunction
Pull out the power plug from
the AC terminal and confirm
the fuse on the PCB assembly
Turn the power on.
Set the TURBO mode
Checking point (symptoms)
1. Is the broken(open)?
Voltage check
1. AC voltage at BD71(~,~)?
: rating voltage ± 10% range
2. DC voltage at BD71(+,-)?
: about 325[v] ± 10%
3. DC voltage at IC02
: IN-GND
➔
DC12[v]
: OUT-GND
➔
DC5[v]
4. Voltage waveform at Q201
: collector-GND
➔
squarewave
Voltage check
1. check voltage of IC06
(pin#10,pin#8)
: relay on
➔
0.7[v]
: relay off
➔
12[v]
2. Voltage at terminal block
((N1) -1)
➔
rating voltage
Causes
Voltage over
Indoor unit fan
motor short-circuit
SMPS circuit is faulty
SMPS circuit is faulty
PC02, R202-R205
SMPS circuit is faulty
IC06 is faulty
RY71 is faulty
∆
∆
∆
∆
∆
∆
DB98_11868A(1)_1 3/3/03 11:17 AM Page 5-6
Summary of Contents for MC26AC2-07
Page 3: ...MEMO Samsung Electronics 1 2 ...
Page 21: ...MEMO Samsung Electronics 3 14 ...
Page 25: ...MEMO Samsung Electronics 4 4 ...
Page 46: ...MEMO 5 21 Samsung Electronics ...
Page 53: ...MEMO Samsung Electronics 6 7 ...
Page 55: ...Samsung Electronics 8 1 8 PCB Diagrams 8 1 ASS Y MAIN PCB DB93 01018A TOP PATTERN ...
Page 57: ...Samsung Electronics 8 3 BOTTOM PATTERN PCB Diagrams ...
Page 58: ...8 4 Samsung Electronics 8 2 PCB OUTDOOR UNIT PE M3000 02 ...
Page 61: ...MEMO Samsung Electronics 8 7 ...
Page 62: ...9 1 Samsung Electronics 9 Wiring Diagrams 9 1 Indoor Unit ...
Page 63: ...Samsung Electronics 9 2 9 2 Outdoor Unit ...
Page 64: ...10 1 Samsung Electronics 10 Schematic Diagrams 10 1 Indoor Unit ...
Page 66: ...ELECTRONICS Samsung Electronics Co Ltd Mar 2003 Printed in Korea Code No DB98 11868A 1 ...