Samsung Generation 6 Installation Manual Download Page 1

 Heat Pump Installation Guide

1

Generation 6

Samsung Heat Pump 

Installation Manual

REGISTER THIS PRODUCT 

ONLINE WITHIN 28 DAYS OF 

COMMISSIONING

IRELAND

www.joule.ie/register-a-product

NORTHERN IRELAND

www.jouleuk.co.uk/register-a-product

JL-SAMHPG6-DS-24-010-2019

Summary of Contents for Generation 6

Page 1: ...Generation 6 Samsung Heat Pump Installation Manual REGISTER THIS PRODUCT ONLINE WITHIN 28 DAYS OF COMMISSIONING IRELAND www joule ie register a product NORTHERN IRELAND www jouleuk co uk register a pr...

Page 2: ...from solar controller Solar PV Ser No from String Micro Inverter Air Source Heat Pump Located on external heat pump badge Integrated Heat Pump and Cylinder Located on cylinder badge Underfloor Heating...

Page 3: ...ater System Flushed Water System Filled And Purged Flow Switch fitted Flow And Return Lines Insulated Glycol level around 20 check with glycol manufacture for details Refrigerant Piping For Split Syst...

Page 4: ...emp for weather comp 10 2012 High Ambient temp for weather comp 15 2021 Flow temperature at low ambient point 2011 Zone 1 40 2022 Flow temperature at high ambient point 2012 Zone 1 25 2031 Flow temper...

Page 5: ...Max cylinder heating time from heat pump before turning back to heating zones 30 3032 Max cylinder heating time from heat pump before turning on immersion to support it 20 3041 Anti Legionella functi...

Page 6: ...and return pipe work connected the right way around Is Primary flow and return pipework insulated Heat Pump Plumbing Outdoor Is the flow switch installed on the primary pipework and fitted in the corr...

Page 7: ...or heat pump Are all cable protrusions avoiding condensate tray Is the correct communication cable installed and wired into correct terminals Heat Pump Wiring Is the correct size breaker used for cont...

Page 8: ...Contact Tel Contact Email Installer s Signature Print Name Date Heat Pump must be commissioned within 30 days of installation in order to avail of warrenty regis tration If it is found that your syst...

Page 9: ...High Gain Indirect 2 Heating 1 DHW 40 Mechanical Electrical Diagram 42 Field Setting Parameters 44 Air Source Heat Pump High Gain Indirect 2 Heating 1 DHW 44 Mechanical Electrical Diagram 46 Field Se...

Page 10: ...reement Heat pump Maintenance Package Joule s heat pump maintenance package entitles you to an annual maintenance visit during which our engineer will ensure that your Samsung heat pump supplied by Jo...

Page 11: ...omeris welcomed contacted A samsung accredited installerto Registration with Samsung must occurwithin 28 days of Commissioning date Contact 03307262677 or uk corporate samsung com for Commissioning an...

Page 12: ...te the additional warranty 3 This offer applies to models purchased after 00 01hrs GMT on 1st May 2016 4 Upon registration the claimant will be sent an email confirmation with notification of registra...

Page 13: ...xtent Of Warranty During the extended warranty period Samsung continues to warrant that the Samsung Product shall be free from defects in materials and workmanship If the relevant product does not fun...

Page 14: ...uninter rupted or error free During the Extended Warranty Period Samsung will only provide the Warranty in the UK and ROI Samsung is not responsible for paying any travel or delivery costs where the p...

Page 15: ...ion 1 These terms and conditions are governed by English law and come under the English courts shall have exclusive jurisdiction to settle and resolve any dispute which may arise in connection with th...

Page 16: ...used for the storage of potable water It has not been subjected to frost damage The unit has been serviced annually The Service Log Book has been completed after each annual service The warranty card...

Page 17: ...tions shall be performed by qualified personnel only The unit contains moving parts and electrical parts which should always be kept out of the reach of children Do not attempt to repair move alter or...

Page 18: ...E03CN 5kW 4 0mm 20Amp Power supply to the MIM units must connect to the RCD fitted inside of the MIM unit Cable Size No of Cores Location 0 75mm 2 Core Screened From indoor unit to outdoor unit F1 F2...

Page 19: ...to be installed after pump on flow but before any zone valves All underfloor heating circuits to be controlled from the run signal from the third party underfloor wiring centre All radiator zones to b...

Page 20: ...r unit and the air outlet is towards the wall The upper part of the outdoor unit and the air outlet is opposite the wall When front and rear side of the outdoor unit is towards the wall 300mm or more...

Page 21: ...r unit and the air outlet is opposite the wall 1500mm or more 600mm or more 3000mm or more 3000mm or more 300mm or more 300mm or more 300mm or more 300mm or more 300mm or more The units must be instal...

Page 22: ...t must be 20mm or higher from the base The anchor bolt must be 20mm or higher from the base surface When tightening the anchor bolt tighten the rubber washer to prevent outdoor unit bolt connection pa...

Page 23: ...sure to fol low the instructions described below To prevent exposure to wind install the unit with its suction side facing the wall Never install the unit at a site where the suction side may be expo...

Page 24: ...it or soak hole beneath the Heat Pump to prevent water or ice from forming on the ground around the Heat Pump which may be a safety hazard If installing the Heat Pump on a wall the supplied drain plug...

Page 25: ...ion should be a maximum of 150mm 3 If you install the unit on a frame please install a water proof plate within 150mm of the under side of the unit in order to prevent the invasion of water from the l...

Page 26: ...can be extended it is a 4 core cable if you do extend ensure that the cores are not crossed The switch must be located indoors as it is only splash proof Ideally the Flow Switch will be mounted horizo...

Page 27: ...tting it into the system and a solar filling station is ideal for filling the system use the connections on the fill flush and flow meter to add the glycol 5 Do not put Neat Glycol into the system fai...

Page 28: ...ighted use right hand arrow to enter Using the arrows enter phone number once done push OK You will now return to service timer Use down arrow to highlight installation date then right arrow to enter...

Page 29: ...arrows to highlight Energy Push the ok button to enter this menu Energy usage should be highlighted push right arrow to enter From here you have four options Instantaneous usage Weekly energy usage M...

Page 30: ...lve Heating Zone 1 9b 22mm 2 Port Zone Valve Heating Zone 2 10 DHW Heat Pump Stat Pocket 11 Solar Probe Stat Pocket Where Applicable 12 DHW Immersion 13 Buffer Tank Immersion Where Applicable 14 Buffe...

Page 31: ...Heat Pump Installation Guide 31 Please see Figure 1 1 on page 93 for Unplumbed Wiring Diagram Electrical Diagram...

Page 32: ...ired Example for weather comp and heating flow high light 20 water law Push g arrow to enter sub menu You will see the individual settings within this menu Use h and i to set FSV Example 2011 Low set...

Page 33: ...from Zone 1 Not Use Recommended Use Signal only ON OFF Use Signal ON OFF or WL Interlink OFF Water Pump1 Use Signal ON OFF or WL Interlink OFF Water Pump2 Use Signal ON OFF or WL Interlink OFF Water P...

Page 34: ...2mm 2 Port Zone Valve Heating Zone 2 9b 22mm 2 Port Zone Valve Heating Zone 2 10 DHW Heat Pump Stat Pocket 11 Solar Probe Stat Pocket Where Applicable 12 DHW Immersion 13 Buffer Tank Immersion Where A...

Page 35: ...Heat Pump Installation Guide 35 CNS057 Please see Figure 1 2 on page 94 for Unplumbed Wiring Diagram Electrical Diagram...

Page 36: ...menu required Example for weather comp and heating flow high light 20 water law Push g arrow to enter sub menu You will see the individual settings within this menu Use h and i to set FSV Example 2011...

Page 37: ...2 This should be set to 35 C 20 91 1 External Run input for Zone 1 Room stat Not Use Recommended Use Signal only ON OFF Use Signal ON OFF or WL Interlink OFF Water Pump1 Use Signal ON OFF or WL Interl...

Page 38: ...m 2 Port Zone Valve Heating Zone 2 9c 22mm 2 Port Zone Valve Heating Zone 3 10 DHW Heat Pump Stat Pocket 11 Solar Probe Stat Pocket Where Applicable 12 DHW Immersion 13 Buffer Tank Immersion Where App...

Page 39: ...Heat Pump Installation Guide 39 CNS057 Please see Figure 1 3 on page 95 for Unplumbed Wiring Diagram Electrical Diagram...

Page 40: ...menu required Example for weather comp and heating flow high light 20 water law Push g arrow to enter sub menu You will see the individual settings within this menu Use h and i to set FSV Example 2011...

Page 41: ...stat Not Use Recommended Use Signal only ON OFF Use Signal ON OFF or WL Interlink OFF Water Pump1 Use Signal ON OFF or WL Interlink OFF Water Pump2 Use Signal ON OFF or WL Interlink OFF Water Pump3 30...

Page 42: ...Valve 8 28mm DHW 2 Port Zone Valve 9a 22mm 2 Port Zone Valve Heating Zone 1 9b 22mm 2 Port Zone Valve Heating Zone 2 9c 22mm 2 Port Zone Valve Heating Zone 3 10 DHW Heat Pump Stat Pocket 11 Solar Prob...

Page 43: ...Heat Pump Installation Guide 43 Please see Figure 1 4 on page 57 for Unplumbed Wiring Diagram CNS057 Please see Figure 1 4 on page 96 for Unplumbed Wiring Diagram Electrical Diagram...

Page 44: ...menu required Example for weather comp and heating flow high light 20 water law Push g arrow to enter sub menu You will see the individual settings within this menu Use h and i to set FSV Example 2011...

Page 45: ...2 This should be set to 35 C 20 91 1 External Run input for Zone 1 Room stat Not Use Recommended Use Signal only ON OFF Use Signal ON OFF or WL Interlink OFF Water Pump1 Use Signal ON OFF or WL Interl...

Page 46: ...ve 9a 22mm 2 Port Zone Valve Heating Zone 1 9b 22mm 2 Port Zone Valve Heating Zone 2 9c 22mm 2 Port Zone Valve Heating Zone 3 10 DHW Heat Pump Stat Pocket 11 Solar Probe Stat Pocket Where Applicable 1...

Page 47: ...Heat Pump Installation Guide 47 CNS057 CNS057 Please see Figure 1 5 on page 97 for Unplumbed Wiring Diagram Electrical Diagram...

Page 48: ...must push the Set key otherwise the change is not saved Push the Set to save and a swirling line will appear this indicated that the unit is saving the change 6 Push the f arrow so that 20 11 flashes...

Page 49: ...2 This should be set to 35 C 20 91 1 External Run input for Zone 1 Room stat Not Use Recommended Use Signal only ON OFF Use Signal ON OFF or WL Interlink OFF Water Pump1 Use Signal ON OFF or WL Interl...

Page 50: ...Zone Valve 8 28mm DHW 2 Port Zone Valve 9a 22mm 2 Port Zone Valve Heating Zone 1 9b 22mm 2 Port Zone Valve Heating Zone 2 9c 22mm 2 Port Zone Valve Heating Zone 3 10 DHW Heat Pump Stat Pocket 11 Solar...

Page 51: ...Heat Pump Installation Guide 51 Electrical Diagram...

Page 52: ...menu required Example for weather comp and heating flow high light 20 water law Push g arrow to enter sub menu You will see the individual settings within this menu Use h and i to set FSV Example 2011...

Page 53: ...flow temperature for heating circuit 2 at set value of 20 12 This should be set to 35 C 20 91 1 External Run input for Zone 1 Room stat Not Use Recommended Use Signal only ON OFF Use Signal ON OFF or...

Page 54: ...matic 3 Zone Smart Plumb Compact Installation Pre plumbed Components Pipework to be intalled by Installer Legend 1 Joule SmartPlumb Compact Cylinder 2 Samsung Monobloc Heat Pump 3 28mm Y Strainer 4 Fl...

Page 55: ...Heat Pump Installation Guide 55 Electrical Schematic 3 Zone Smart Plumb Compact Installation 2 Heating 1 Domestic Hot Water Wiring inside broken line is prewired...

Page 56: ...Monobloc Heat Pump 3 28mm Y Strainer 4 Flow regulator Flush Fill Unit 5 Automatic Air Vents 6 UFH Circulation Pump 7 Automatic Bypass Valve 8 Heating Expansion Vessel 9 Primary Circulating Pump 10 He...

Page 57: ...Heat Pump Installation Guide 57 Electrical Schematic 4 Zone Smart Plumb Compact Installation 3 Heating 1 Domestic Hot Water Wiring inside broken line is prewired...

Page 58: ...required load bearing capability Installation ser vicing maintenance and repair must be carried out by a competent person The Smart Plumb Compact unit is delivered fully packaged and fixed to a wooden...

Page 59: ...on Guide 59 Measurements 84mm 625mm 595mm 64mm 595mm 1900mm 100mm 470mm 470mm Right Side View Front View Left Side View 625mm Top View 64mm 75mm 75mm 75mm 64mm 64mm Smart Plumb Compact Installation Tr...

Page 60: ...al for servicing if required When using the adjustable feet ensure that the floor is strong enough Install the cylinder unit where it is not exposed to water excessive moisture Particular attention is...

Page 61: ...g ensure all connections are completely watertight Pipe Connections Smart Plumb Compact Installation A lack of safety devices can lead to potentially fatal injuries all necessary safety devices must b...

Page 62: ...nts on the Smart Plumb Compact casing to exit the relief pipework To access and connect the pipe work follow guidelines listed below Remove the Casing Front Panel 1 Remove the two lower screws 2 Slide...

Page 63: ...3 sizes larger and so on Bends must be taken into account in calculating the flow resistance Refer to diagram 1 Table 1 and the worked example An alternative approach for sizing discharge pipes would...

Page 64: ...uk www joule ie 64 Examples of Discharge Arrangements Left Side Pipe Exit Right Side Pipe Exit Front View Side View Front View Side View Temperature Pressure Relief Valve 7 System Smart Plumb Compact...

Page 65: ...Heat Pump Installation Guide 65 Piping Diagram Waterway Schematic Smart Plumb Compact Installation...

Page 66: ...stalled in the system to prevent the risk of scalding Heat Pump Primary Connections Connect the primary connections as shown below The direction of flow arrow should be towards the primary flow connec...

Page 67: ...pre installed along with the heating system expansion vessel The circulating pump for the heating system is also pre fitted within the casing All heating zone returns should be joined at the cylinder...

Page 68: ...receives the increased water volume when expansion takes place as the system heats up and it maintains a positive pressure in the system The expansion vessel contains a flexible diaphragm which is in...

Page 69: ...back pressurise the unit and result in discharge Secondary Circulation On larger installations long pipe runs to draw off points can cause significant volumes of water to be drawn off before an accept...

Page 70: ...hot tap furthest away from the cylinder to expel air Open the cold main isola tion valve and allow the unit to fill Once the cylinder has been fully commissioned it should be heated to its normal oper...

Page 71: ...or 5 seconds Release and make sure it resets correctly Repeat with the pressure temperature relief valve In both cases check that the discharge pipe work is carrying the water away adequately If not c...

Page 72: ...select sub menu required Example for weather comp and heating flow high light 20 water law Push g arrow to enter sub menu You will see the individual settings within this menu Use h and i to set FSV...

Page 73: ...ircuit 2 at set value of 20 12 This should be set to 35 C 20 91 1 External Run input for Zone 1 Room stat Not Use Recommended Use Signal only ON OFF Use Signal ON OFF or WL Interlink OFF Water Pump1 U...

Page 74: ...www jouleuk co uk www joule ie 74 Controller Symbols Button Functions Controller Power Key Menu Key Return Key Enter Key Navigation Keys...

Page 75: ...Heat Pump Installation Guide 75...

Page 76: ...a in sensor disconnection Check the disconnection of indoor unit pipe sensor Operation off Indoor sensor error 153 Indoor floating switch secondary detection Check indoor unit float sensor Check indoo...

Page 77: ...stacles around the indoor and outdoor units Check whether the outdoor unit service valve is open Check whether the indoor outdoor installation pipe wiring are correct Operation off Outdoor unit protec...

Page 78: ...tection control error 601 Communication error be tween the indoor unit and wired remote controller Check the connection wire between the indoor unit and the wired remote controller Operation off Wired...

Page 79: ...rts E468 Current sensor error Exchange INVERTER PBA E471 Outdoor EEPROM error EEPROM date is wrong Exchange EEPROM or MAIN PBA This error doesn t occur in EMF 150 AM E474 IPM IGBT Module or PFCM tempe...

Page 80: ...l output to Heating Zone Valve Blue Cable B17 230V AC Live Output Live Output to DHW Zone Valve Brown Cable B18 230V AC Live Input Live Output to Buffer Heating Zone Valve Brown Cable B19 230V AC Neut...

Page 81: ...Heat Pump Installation Guide 81 Figure 1 1 Air Source Heat Pump Unplumbed Smartplumb 1 Heating 1 DHW CNS057...

Page 82: ...www jouleuk co uk www joule ie 82 Figure 1 2 Air Source Heat Pump Unplumbed Smartplumb 2 Heating 1 DHW CNS057...

Page 83: ...Heat Pump Installation Guide 83 Figure 1 3 Air Source Heat Pump Unplumbed High Gain Indirect 1 Heating 1 DHW CNS057...

Page 84: ...www jouleuk co uk www joule ie 84 Figure 1 4 Air Source Heat Pump Unplumbed High Gain Indirect 2 Heating 1 DHW CNS057...

Page 85: ...Heat Pump Installation Guide 85 Figure 1 5 Air Source Heat Pump Pre Plumbed Smartplumb 1 Heating 1 Cooling CNS057...

Page 86: ...Company Name Telephone No Comments Signature Service 1 Date Engineer Name Company Name Telephone No Comments Signature Service 1 Date Engineer Name Company Name Telephone No Comments Signature Servic...

Page 87: ...Heat Pump Installation Guide 87...

Page 88: ...Power Road Plantation Bus Pk Bromborough Wirral CH62 3RN 44 0 1513 551 094 44 0 1513 568 336 info jouleuk co uk www jouleuk co uk 23 200 Kra nik ul Towarowa 34 48 0 128811171 48 0 814709046 biuro jou...

Reviews: