Samsung Electronics
Troubleshooting
12-9
12-3-4 Communication error during the operation
No
If address is not fault
exchange the indoor unit PCB after
communication line check.
Replace PCB after checking
the outdoor unit communication line
and connector
No
Yes
Yes
Measure the 2 lines of outdoor side
by scope after removing the
communication line connecting from
outdoor unit to indoor unit.
After connecting again the communication
line connecting from outdoor unit to indoor unit,
remove the communication
connector on indoor unit PCB, and find the
indoor unit preventing communication
through connecting the communication
connectors each by each, and then replace
the indoor unit PCB after line check.
Check the display after
pressing the reset key on outdoor PCB
When tracking, is there any
indoor answer from display part?
At this time, is the voltage
between lines rectangular wave over DC±0.7V
like below figure?
+0.7V
-0.7V
Good
Bad
Multi type
After 2 minutes, check if PCB address
setting of indoor unit displayed the
communication error among indoor units are
overlapped or not.
(If the indoor unit address is overlapped, the
communication error is occurred.)
- In this case, the communication error is
occurred to over two indoor units set
wrong.
Outdoor unit display
Indoor unit display
How to determine
Reason of error
(Communication error during the operation)
(Operation)
(Timer)
(Airflow)
(Filter)
Disconnection and short of communication lines
Communication error between the indoor unit and outdoor unit.
24524(1)_1 56/10/3 7:10 PM Page 4-46
All manuals and user guides at all-guides.com