1. Unit selection (based on cooling load)
2
. Outdoor unit
ΙΛ
ΙΛ
1-1. Indoor unit selection
Select the indoor unit based upon cooling load and unit capacity. (The indoor unit capacity should larger than the load.)
1-2. Outdoor unit selection
Allowable combinations are described on the indoor unit combination total capacity index table.
For a standard indoor unit and outdoor unit combination, select the nearest value of the total
indoor unit capacity index that is less than a 100% outdoor unit combination capacity index.
◆
Indoor units can be of different capacities, however total capacity
must be checked against the outdoor unit capacity table.
■
Indoor unit combination total capacity index
outdoor unit
indoor unit combination rate
100%
16.0
28.0
28.0(ISO)
110%
17.6
30.8
30.8
120%
19.2
33.6
33.6
130%
20.8
36.4
36.4
90%
14.4
25.2
25.2
80%
12.8
22.4
22.4
70%
11.2
19.6
19.6
60%
9.6
16.8
16.8
50%
8.0
14.0
14.0
RVMH060GBM0
RVMH100GAM0
RVMH100FAM0
■
Indoor unit capacity index
- 50Hz
Unit size
capacity index
020
2.0
026
2.6
035
3.5
052
5.2
060
6.0
070
7.0
082
8.2
105
10.5
128
12.8
- 60Hz
Unit size
capacity index
020
2.0
032
3.2
040
4.0
052
5.2
060
6.0
072
7.2
083
8.3
105
10.5
128
12.8
◆
The system enables the connection of indoor units with a total capacity of between 50 to 130% of that of the
corresponding outdoor unit but where this capacity ratio exceeds 100% then the actual capacity of each indoor
unit will fall a little short of its individual rated capacity when all the units are operated simultaneously. (Except
Middle East models)