Samsung Electronics
Part
Breakdown Inspection Method
Room Temperature Sensor
Measure resistance with a tester
Normal
At the normal temperature 37kΩ~ 8.3kΩ(-7˚C~+30˚C)
*Refer to Table 12-3-4.
Abnormal
∞, 0Ω . . . Open or Short
Room Fan Motor
Measure the resistance between terminals of the connector (CN73) with a tester.
Normal
At the normal temperature (10˚C ~ 30˚C)
Abnormal
∞, 0Ω . . . Open or Short
Stepping Motor
Measure the resistance between the red wire and each terminal wire with a tester.
Normal
About 300Ω at the normal temperature (20˚C ~ 30˚C)
Abnormal
∞, 0Ω . . . Open or Short
12-4 Main Part Inspection Method
12-21
Compare terminal
Resistance
Remark
Yellow, Red
166Ω(
✳✳
035
✳✳
), 47Ω(
✳✳
052/070
✳✳
) ± 10%
Main
White, Red
144Ω(
✳✳
035
✳✳
), 59Ω(
✳✳
052/070
✳✳
) ± 10%
Sub