Setting an indoor unit address and installation option
Setting an indoor unit installation option (suitable for the condition of each installation location)
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional
power supply in the indoor unit.
2. The panel(display) should be connected to an indoor unit to receive
option.
3. Set the installation option according to the installation condition of an air
conditioner.
- The default setting of an indoor unit installation option is “020010-
100000- 200000-300000”.
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is
more than one indoor unit.
4. Set the indoor unit option by wireless remote controller.
■
02 series installation option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
2
Evaporator Drying
Use of external
room temperature
sensor / Minimizing
fan operation when
thermostat is off
Use of central control
FAN RPM
compensation
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
Use of drain pump
Use of hot water heater
-
EEV Step when
heating stops
-
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
Use of external control
Setting the output
of external control /
External heater signal
/ Cooling operation
signal / Free Cooling
control signal
-
Buzzer control
Hours of filter
usage
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
Individual control of a
remote controller
Heating setting
compensation
Adjusted EEV step of
stopped unit during oil
return /defrost mode.
-
-
f
1WAY/2WAY/4WAY MODEL : Drain pump(SEG8) will be set to ‘USE + 3minute delay’ even if the drain pump is set to 0.
f
1WAY/2WAY/4WAY, DUCT MODEL : Number of hours using filter(SEG18) will be set to ‘1000hour’ even if the SEG18 is set
to exept for 2 or 6.
f
When setting the option other than above SEG values, the option will be set as “0”.
f
SEG5 central control option is basically set as 1(Use), so you don’t need to set the central control option additionally.
However, if the central control is not connected but it doesn’t indicate an error message, you need to set the central
control option as 0 (Disuse) to exclude the indoor unit from the central control.
f
The output of hot water heater in SEG9 is generated from the hot coil part of the terminal board in duct models.
Indoor Unit
1(L)
F2
F1
2(N)