E-
32
Drain pump installation (Optional) (Continued)
5
Insert the flexible hose into the drain socket until it clicks.
Note
Check if water does not drain.
Insulate the drain hose so that frost does not form.
6
Connect the cable to the electrical component box as shown at the figure.
Note
Connect the drain pump cable to yellow terminal(CN74) and
the float switch to black terminal(CN51).
7
Adjust K4 DIP switch(SW05) to the “OFF” position.
Note
Wrap the drain tube outlet on the right and left side of the
indoor unit with an insulating materials.
Switch No.
Switch Position Using Drain Pump
K4
ON
X
OFF
O
SW05
Must fit tightly against body without any gap.
Cable-tie
Drain hose
Insulation
Indoor unit
Float switch
Drain pump
Technical Specification & Product feature
Maximum installation height: up to 3.6m
Condensate discharge pump(built-in): Max. 750mm
Length of pipes and difference in height: see the outdoor unit installation manual
Vacuum and refrigerant charge: see the outdoor unit installation manual
Model
EH035EAV1 EH052EAV1 EH070EAV1 DH052EAS DH070EAS DH090EAS DH105EAS DH052EAV1 DH070EAV1 DH090EAV DH105EAV DH140EAV
Capacity(Cooling
and Heating)
3.5/4.0kW 5.0/6.0kW 7.1/8.0kW 5.0/6.0kW 7.1/8.0kW 9.0/9.5kW 10.5/11.2kW 5.0/6.0kW 7.1/8.0kW 9.0/9.5kW 10.5/11.2kW14.0/16.0kW
Power Input
0.07kW
0.12kW
0.13kW
0.13kW
0.17kW
0.243kW
0.15kW
0.15kW
0.17kW
0.13kW
0.13kW
0.22kW
Running Current
0.36A
0.51A
0.56A
1.01A
1.14A
1.22A
0.7A
1.05A
1.10A
0.7A
0.7A
1.4A
Refrigerant
950g
1450g
1900g
1350g
1350g
2400g
2600g
1450g
1900g
2600g
2800g
2800g