background image

E-

17

Installing and Connecting the Drain Hose of the Indoor Unit

When installing the drain hose for the indoor unit, check if condensation draining is adequate.   
When passing the drain hose through the 65-mm hole drilled in the wall, check the following:

Drain hose installation:

1

If necessary, connect the 2-meter extension drain hose to the drain hose. 

2

If you use the extension drain hose, insulate the inside of the extension drain 

hose with a shield.

3

Fit the drain hose into 1 of 2 drain hose holes, then fix the end of the drain 

hose tightly with a clamp. 

  If you don’t use the other drain hose hole, block it with a rubber stopper. 

4

Pass the drain hose under the refrigerant pipe, keeping the drain hose tight.

5

Pass the drain hose through the hole in the wall. Check if it slants downwards 

as seen in the picture. 

   

The hose will be fixed permanently into position after finishing  
the installation and the gas leak test; refer to page 15 for further details. 

Shield

Drain hose

Extension drain hose

The hose must  

 NOT slant upwards. 

The end of the drain 

hose must NOT be 

placed under water. 

Do NOT bend the hose 

in different directions.

 

Keep a clearance of at 

least 5cm between the 

end of the hose and 

the ground.

 

Do NOT place the end 

of the drain hose in a 

hollow.

5cm

less

Ditch

Rubber cap

Drain pan outlet

Drain hose

Screws hole

Screw

Changing Direction of the Drain Hose

You can select the direction of the drain hose, depending on where you want to 
install the indoor unit.

1

Detach the rubber cap with the flyer.

2

Detach the drain hose by pulling it and turning to the left.

3

Insert the drain hose by fixing it into the groove of the drain hose and the 

outlet of the drain pan.

4

Attach the rubber cap with a screwdriver by turning it to the right until it fixes 

to the end of the groove.

One of the diagrams has an illustration with the words “Screws hole” that 
should be changed to “Screw hole.” 

AVXWV@@_IM_E_29819-1_4.14.09.indd   17

2009-4-14   10:15:42

Summary of Contents for AVXWVH022EE

Page 1: ...AVXWV _IM_E_29819 1_4 14 09 indd 1 2009 4 14 10 15 27...

Page 2: ...necting the Refrigerant Pipe 13 Cutting Flaring the Pipes 14 Performing Leak Test Insulation 15 Installing and Connecting the Drain hose of the Indoor Unit 17 Changing Direction of the Drain Hose 17 W...

Page 3: ...type air conditioner keep all electrical cables such as the power cable and the connection cord in pipe ducts cable channels e t c to protect them against liquids outside impacts and so on This applia...

Page 4: ...e agent or similarly quali ed persons according to national wiring regulations and use only rated cable If the capacity of the power cable is insufficient or electric work is not properly completed el...

Page 5: ...and the accessories may drop or water may leak The capacity of the heat exchanger may reduce or the air conditioner may be out of order The place where corrosive gas such as sulfurous acid gas generat...

Page 6: ...supplied with the indoor unit The type and quantity may differ depending on the specifications Installation Plate Remote Control Batteries for Remote Control User s Manual Installation Manual AVXWV _I...

Page 7: ...e installed should be strong enough to support the weight of the unit Rigid wall without vibration Where it is not exposed to direct sunshine Where the air filter can be removed and cleaned easily Spa...

Page 8: ...bolts the anchor bolts must not project more than 20mm 4 Determine the positions of the wooden uprights to be attached to the window frame 5 Attach the wooden uprights to the window frame giving atte...

Page 9: ...pension bolt 3 8 or M10 field supply Hole in anchor Hole in plug Insert 450mm X 200mm or more Maintenance Hole Maintenance hole must be located on the ceiling Indoor unit pipe connection Outdoor uint...

Page 10: ...sion bolt 2 Connect the IN refrigerant pipe to the outdoor unit 3 Connect the OUT refrigerant pipe to each indoor unit A B and C The liquid and gas pipes should not be crossed when piping connection 4...

Page 11: ...en connect the cable to another EEV kit 2 Connect the AC power cable and communication cable to each indoor unit A B and C 3 EEV kit address should be set same with connected indoor units main address...

Page 12: ...the ADDRESS of indoor unit is set to 1 3 and 7 The numbers which are displayed on right indicate the ADDRESS of SW01 SW02 SW03 SW04 and SW05 SW06 in sequential If it indicates 0 1 and 2 that means th...

Page 13: ...hten the nuts first with your hands and then with a torque wrench applying the following torque Outer Diameter Torque kgf cm 6 35 mm 1 4 145 175 9 52 mm 3 8 333 407 12 70 mm 1 2 505 615 15 88 mm 5 8 6...

Page 14: ...ter mm A mm Flaretoolfor R410Aclutchtype Conventional flare tool Clutch type Wing nut type 6 35 0 0 5 1 0 1 5 1 5 2 0 9 52 0 0 5 1 0 1 5 1 5 2 0 12 70 0 0 5 1 0 1 5 1 5 2 0 15 88 0 0 5 1 0 1 5 1 5 2 0...

Page 15: ...t doesn t project from the rear of the indoor unit 5 Hook the indoor unit to the installation plate and move the unit to the right and left until it is securely in place 6 Wrap the rest of the pipe wi...

Page 16: ...side and liquid side pipes but the pipes should not be pressed When contacting the gas side and gas side pipe use 1 grade thicker insulator Refrigerant pipe after EEV kit andMCU Install the gas side...

Page 17: ...ishing the installation and the gas leak test refer to page 15 for further details Shield Drain hose Extension drain hose The hose must NOT slant upwards The end of the drain hose must NOT be placed u...

Page 18: ...and communication cable F1 F2 each 5 Connect V1 V2 for DC12V and F3 F4 for communication when installing the wired remote control Power and communication cable connection Norminal dimensions for cabl...

Page 19: ...Distance among each indoor unit m Ak Power cable specification mm2 ik Running current of each unit A Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 Example of Installation Total power cable lengt...

Page 20: ...le disconnection from the power supply must be incorporated in the fixed wiring 3mm You must keep the cable in a protection tube Keep distances of 50mm or more between power cable and communication ca...

Page 21: ...and SW02 The MAIN address from 00 to 99 should differ from each other Check the indoor unit address on the plan that you are to install and set the address according to the plan You may not need to s...

Page 22: ...5 Heating CurrentTemperature Compensation 2 C 5 C K6 Filter Time 1 000 hours 2 000 hours K7 K8 No Function ON OFF SW07 K9 Indoor Expansion Valve For Heating Stop Fix 80 step 0 or 80 step K10 Wired Rem...

Page 23: ...e following The appropriate indicator lights up and the air conditioner operates according to the selected mode or function 4 Press the button and check the following The airflow blades work properly...

Page 24: ...PEN SHORT For heat pump models only X X X Displayed on appropriate indoor unit which is operating Error of indoor fan motor Below 450RPM for 15 minutes X X X X Displayed on appropriate indoor unit whi...

Page 25: ...operating Displayed on outdoor unit 5 Breakaway of COND MID sensor 6 2nd detection of refrigerant completely leak 7 2nd detection of high temperature COND 8 2nd detection of high temperature DISCHARG...

Page 26: ...EEE Y netmeli ine Uygundur This EEE is compliant with RoHS AVXC1 _IM_E_29824 1_5 05 09 indd 30 2009 5 12 8 46 05...

Page 27: ...E INSTALLATION MANUAL Wall mountedTypeSeries VivaceType AVXWV DB98 29819A 1 Air Conditioner AVXWV _IM_E_29819 1_5 08 09 indd 27 2009 5 8 16 58 36...

Reviews: