installing your air conditioner
_33
ENGLISH
Wiring Work
Silver solder
1.
Before wiring work, you must turn off all power source.
2.
Indoor unit power should be supplied through the
breaker(MCCB, ELB) separated by the outdoor power.
3.
The power cable should be used only copper wires.
4.
Connect the power cable{1(L), 2(N)} among the units within
maximum length and communication cable(F1, F2) each.
5.
Connect V1, V2(for DC12V) and F3, F4(for communication)
when installing the wired remote Control.
Power and communication cable connection
N
L
N
L
N
L
N
L
Indoor Unit 1
Outdoor
Unit
Wired Remote
Control
220-240V~
ELB : Essential Installation
Ceiling, wall-mounted indoor unit.
Indoor Unit 2
Indoor Unit 3
Indoor Unit 4 Indoor Unit 5 Indoor Unit 6
EEV kit
Selecting compressed ring terminal
Norminal
dimensions
for cable
(mm
2
)
Norminal
dimensions
for screw
(mm)
B
D
d1
E F
L
d2
t
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm) Min. Min. Max.
Standard
dimension
(mm)
Allowance
(mm) Min.
1.5
4
6.6
±0.2
3.4
+0.3
-0.2
1.7
±0.2 4.1 6 16
4.3
+0.2
0
0.7
4
8
2.5
4
6.6
±0.2
4.2
+0.3
-0.2
2.3
±0.2
6 6 17.5
4.3
+0.2
0
0.8
4
8.5
4
4
9.5
±0.2
5.6
+0.3
-0.2
3.4
±0.2
6 5 20
4.3
+0.2
0
0.9
Specification of electronic wire
Power supply
MCCB
ELB
Power
cable
Earth
cable
Communication
cable
Max : 242V
Min : 198V
X
A
X
A, 30mmA
0.1 sec
2.5mm
2
2.5mm
2
0.75~1.5mm
2
Decide the capacity of ELB and MCCB by below formula.
The capacity of ELB, MCCB
X
[A] = 1.25 X 1.1 X ∑Ai
X
: The capacity of ELB, MCCB
∑Ai : Sum of Rating currents of each indoor unit.
Refer to each installation manual about the rating current of indoor unit.
Decide the power cable specification and maximum length
within 10% power drop among indoor units.
Coef: 1.55
L
k
: Distance among each indoor unit[m],
A
k
: Power cable specification[mm
2
], i
k
: Running current of each unit[A]
∑ (
Coef×35.6×L
k
×i
k
) < 10% of input
voltage[V]
1000×A
k
n
k=1
1.
If necessary, connect the 2 meter extension drain hose to
the drain hose.
2.
If you use the extension drain hose, insulate the inside of
the extension drain hose with a shield.
3.
Fit the drain hose into 1 of 2 drain hose holes, then fix the
end of the drain hose tightly with a clamp.
If you don’t use the other drain hose hole, block it with a
rubber stopper.
4.
Pass the drain hose under the refrigerant pipe, keeping the
drain hose tight.
5.
Pass the drain hose through the hole in the wall.
Check if it slants downwards as seen in the picture.
The hose will be fixed permanently into position
after finishing the installation and the gas leak test.
Shield
Drain hose
Extension drain hose
(No default resource)
Drain hose installation
6-Ways to connect Drain Hose and Pipe
Knock out
�
WARNING
Power off before connecting any wires;
Indoor PBA will be damaged while V1,V2,F3,F4
short each other.