Troubleshooting

Samsung Electronics

4-126

4-4-33  

 : OLP protection control caused comp. down

Yes

Yes

No

Check the EEV.

No

Open the sub valve.

No

Connect S-net to vacuum. (forceful)

No

All the sub valves open?

The outdoor/indoor EEV operates normally?

Check the amount of coolant.

1.   How to check

Test operation

Yes

Replace the OLP sensor.

Check the pipeline.

No

Clogging in the pipeline?

(ex-filter)v

OLP sensor is resistance is normal?

(Refer to E320.)

Outdoor unit display

 

Indoor unit display

 ×(Operation)    

(Timer)    

(Fan)    

(Filter)    

(Defrost)

Criteria 

 • OLP SENSOR temp above Trip_Dis.

Cause of problem 

 • See if the sub valve is open.
 • Check the amount of coolant.
 • Check the OLP sensor.

Summary of Contents for AVXC4H052/072/100/110/145CE

Page 1: ...NIT AVXCSH023 032 040CE AVXC4H052 072 100 110 145CE AVXCMH032 040 052 060CE AVXDSH020 032 040 052 072 100 110 145CE AVXDUH100 110 145CE AVXWVH020 032 040 052 060CE AVXWNH020 032 040 052 060CE ND023 032 0401HXCA ND052 072 100 1454HXCA ND032 040 052 060MHXCA ND020 032 040 052 072 100 110 145LHXCA ND100 110 145SHXCA ND220 280HHXCE CA ND020 032 040 052 060VHXCA ND020 032 040 052 060NHXCA ND052 072CHXC...

Page 2: ...installation option 4 11 4 1 3 Option Items 4 17 4 2 What to check before diagnosis 4 19 4 2 1 Lamp combination expression method display cassette type indoor unit 4 19 4 2 2 Numeric type display outdoor unit Wired remote controller wall mount type etc 4 29 4 3 How to take measures for each symptom Model RVXVHT075 100 125FE RD075 100 125VHXFA 4 31 4 3 1 Outdoor unit operation flow 4 36 4 3 2 Indoo...

Page 3: ...r a fixed scroll Compressor Open Short 4 65 4 3 27 Compressor s Discharge Temperature Sensor dislocation error 4 66 4 3 28 Dislocation error of Compressor SUMPTemperature oil temperature Sensor 4 67 4 3 29 Dislocation error of Suction Temperature Sensor 4 68 4 3 30 SUMP Temperature Sensor error Open Short 4 69 4 3 31 High Pressure Temperature Sensor error Open Short 4 70 4 3 32 Low Ppressure Tempe...

Page 4: ...hanger s EVA IN OUT sensor dislocation error Open Short 4 102 4 4 7 Breakdown of EEV 2nd 4 103 4 4 8 Problem with EEV closure 2nd 4 104 4 4 9 Detection of Floating Switch of Indoor Unit s Drain Pump 4 105 4 4 10 The operational error of Indoor Unit s Fan Motor 4 106 4 4 11 Mixed operation Error 4 107 4 4 12 EEPROM error 4 108 4 4 13 Option error of the Remote Controller for an Indoor Unit 4 109 4 ...

Page 5: ... 1 Indoor Unit 5 1 5 1 1 Slim 1 way cassette type 5 1 5 1 2 Mini 4 way cassette type 5 7 5 1 3 4 way cassette type 5 11 5 1 4 Globel 4 way cassette type 5 17 5 1 5 Duct type Slim I 5 23 5 1 6 Duct type Slim II 5 25 5 1 7 Duct type Slim III 5 27 5 1 8 Duct type MSP 5 29 5 1 9 Duct type BIG 5 33 5 1 10 Wall mounted type Vivace 5 35 5 1 11 Wall mounted type Neo Forte without EEV 5 39 5 1 12 Wall moun...

Page 6: ... 7 1 5 Duct type Slim III 7 5 7 1 6 Duct type MSP 7 6 7 1 7 Duct type BIG 7 7 7 1 8 Wall Mounted type Vivace 7 8 7 1 9 Wall Mounted type Neo Forte with EEV 7 9 7 1 10 Wall Mounted type Neo Forte without EEV 7 10 7 1 11 Distributor kit 7 11 7 1 12 Ceiling type 7 12 7 2 Outdoor Unit 7 13 8 Schematic Diagram 8 1 8 1 Indoor Unit 8 1 8 1 1 Slim 1 way cassette type 8 1 8 1 2 4 way cassette type 8 2 8 1 ...

Page 7: ...Contents 9 Reference Sheet 9 1 9 1 Index for Model Name 9 1 9 1 1 Indoor Unit 9 1 9 1 2 Outdoor Unit 9 3 9 2 Refrigerant Circuit Diagram 9 5 9 2 1 Cycle Operation Mode 9 5 ...

Page 8: ...down It protects the danger of fire such as tracking and short O Tighten tightly the service valve of outdoor unit and the cap of charging valve with a monkey spanner O Check the assembly status of parts after repairing the break down It should be same as the status before repairing 1 2 Precautions for the Static Electricity and PL O As the PCB power terminal has a weakness for the static electric...

Page 9: ... work is not properly completed electric shock or fire may occur O Use only rated parts and tools If you don t use the rated parts and tools it can cause trouble with the air conditioner and bring about injury O If any gas or impurities except R410A refrigerant come into the refrigerant pipe serious problem may occur and it may cause injury O Leak test must be done using only Nitrogen NO2 gas O R4...

Page 10: ...ty and COP in low temperature condition 14 F 10 C Possible to connect up to 49 indoor units Digital unit module 2 New technology of DVM PLUS III Q Digital hybrid system DHS Digital Hybrid System is a brand new concept system composed of DVI Digital Vapor Injection compressor vapor injection technology and turbo intercooler These 3 factors together provide highly efficient performance 1 DVI compres...

Page 11: ...or unit increases heating capacity 1st Expansion Enthalpy kJ kg 2nd Expansion Vapor injection reduces the liquid enthalpy in flash tank facilitating heat exchanger to absorb heat more Vapor injection Injection point Mo Mi Mo Mi Evaporator ID Condenser OD DVI compressor Vapor injection Flash tank Solenoid Valve 2nd EEV 1st EEV Subcooling liquid refrigerant Low temperature gas refrigerant Low temp l...

Page 12: ... 8 n Pressure resistance same Q New G fin Highly efficient new G fin increased heat transfer performance reinforced corrosion resistance and increased operating duration in frost condition Heat transfer performance improved by 13 compared to the conventional fin even with the equivalent pressure loss Epoxy acrylic coating reinforced corrosion resistance 1 4 times longer heating operation in frost ...

Page 13: ...duce noise and vibration BLDC motor which is 2 7 more efficient than the competitors has been applied High static pressure propeller fan and the optimum Bell mouth figuration for high external static pressure 8mmAq RPM Efficiency 100 90 80 70 60 50 40 30 200 300 400 500 600 700 800 900 1000 DVM PLUS III Company A Conventional model ...

Page 14: ... is provided to support various needs and applications such as individual or central control and automated building management Internet 2 Enhanced remote analysis System managers installers or service engineers can monitor the whole air conditioning system through the internet analyzing the operation and providing service promptly ...

Page 15: ...afety and robustness Normal Faulty Window synchronization Emergent control Operation state Schedule control Key holder synchronization Z DirectON OFFindoorunitcontrol Z Automaticrecoveryforincorrect communicationwiring F1 F2 Outdoor unit L N F1 F2 Indoor unit 1 L N F1 F2 Indoor unit 1 Non Polarility Wrong wiring F1 F2 Outdoor unit L N F1 F2 Indoor unit 1 L N F1 F2 Indoor unit 1 Protection F1 F2 Ou...

Page 16: ... technology increased refrigerant flow rate and evaporation enthalpy difference Wide Ø0 32 Grooved tube and new G fin increased heat exchange efficiency The best BLDC motor in the industry and optimum fan guard design increased efficiency RPSDQ RPSDQ RQYHQWLRQDO RQYHQWLRQDO 17 5HP 7 5HP RQYHQWLRQDO RQYHQWLRQDO RPSDQ RPSDQ Q Improved heating performance Vapor injection technology has improved heati...

Page 17: ... units in module 8HP Any priority is OK 7 5HP Digital unit 12 5HP Digital unit 10HP Digital unit Conventional model A digital outdoor unit with the largest capacity should come last 7 5HP Fixed unit 10HP Fixed unit 12 5HP Digital unit Company A An outdoor unit with the largest capacity should come first 14HP 10HP DVM PLUS III Q Small size and light weight To facilitate the convenience and mobility...

Page 18: ...f OTS One Touch Solution valve that makes it easy to connect pipes and to open or shut valves DVM PLUS Ⅱ Ô Y Header Outdoor joints allow easy piping expansion and reduction with insulations to facilitate the installation Y joint Outdoor joint Header joint 260mm 10 24inch 423mm 16 65inch 120mm 4 72inch 50mm 1 97inch Q Free piping wiring directions DVM PLUS III is easy to install as its piping can b...

Page 19: ...ongest piping length 721 8ft Equivalent Total piping length 3280 8ft From the first branch joint to the farthest indoor unit 295 3ft Upsize all pipes between branch joints liquid gas Level difference between indoor units 49 2ft The longest pipe length 721 8ft Equivalent The first branch joint to the farthest indoor unit 147 6ft 1 size up 295 3ft Level differences between indoor outdoor unit 164ft ...

Page 20: ...Q Refrigerant pump down and pump out DVM PLUS III provides several functions to facilitate the replacements of product additional installation and maintenance without much effort Z Refrigerant pump down function In case of moving outdoor units maintenance of pipes between indoor units between outdoor units and indoor units it is possible that recover refrigerant into outdoor units Z Refrigerant pu...

Page 21: ...g seal Upper scroll Fixed Lower scroll Orbiting Z Radialcompliance Z Axialcompliance 2 Dual compliances Through rigorous tests such as High load and liquid flood back DVI compressor is evaluated as reliable as it can operate under any conditions C F C F 170 Evaporating temperature Condensing temperature As DVI compressor is mechanically simple in structure it has strong durability and flexibility ...

Page 22: ...portant operation in module system air conditioner s reliability DVM PLUS III Achieves continuous cooling or heating during oil recovery operation Allows level difference between outdoor unit module Company A Oil recovery during cooling operation Cooling operation Cooling operation Oil recovery during heating operation Heating operation Cooling operation Q Acceleration life cycle test All parts fi...

Page 23: ... PLUS III improves the problem of noise not only at the low sound level but also at the actual sound quality level by Developing a sound insulation material for compressor Improving fan guard air flow Adopting Ø0 32 heat exchanger Ô In particular it enhances sound quality as it improves compressor noise by 4dB A by employing new material with better acoustic absorptivity 1 200 1 000 0 800 0 600 0 ...

Page 24: ...igerant leakage in operation Also changing service valves from flange type to brazed type further prevents refrigerant leakage Q RoHS compliance RoHS restriction only applies to small or large household appliances IT equipment lightings power train toys leisure or sports equipment and vending machines Samsung expands the RoHS restriction into its entire range of products based on its own environme...

Page 25: ...ch as hotels nursing homes conference rooms etc For seasonal air conditioning which may need a simultaneous cooling and heating operation In case of medium or large office DVM PLUS III HR satisfies cooling and heating operation simultaneously for the requirements of interior and perimeter zone Z Simultaneouslycoolingandheatingforeachzone Perimeter Zone Heating Interior Zone Cooling DVM PLUS III HR...

Page 26: ...S III HR can carry out a simultaneous cooling and heating operation within a wide range of temperatures 4 New MCU The MCU for DVM PLUS III HR has a double tube heat exchanger for securing high subcooling effect by the MCU itself thus improving the reliability of the long piping and cooling and heating performance P h h3 Q1 Q2 Q3 h2 h1 30 C Indoor temp Outdoor temp Cooling 18 C 16 C 20 C 10 C 24 C ...

Page 27: ...ghing 1000 times its own weight It strengthens the rotary moment of the compressor to maximize the entire efficiency of the compressor BLDC electricity Permanent magnet strong magnetic rotor Double rotor compression cylinder Nd Fe B Neodium Iron Boron magnet SAMSUNG s double rotor compressor has the upper and lower rotors designed symmetrically The double rotor in symmetry can remove vibrations ca...

Page 28: ...ot spread any toxic materials indoors Strong heater SUPER FJM adopts Samsung s high performance double rotor compressor Compared to other products its heating effect at 10 C is about 20 higher Heating performance kW Heating performance improved 20 SUPER FJM measurement Other product measurement Other product measurement External temperature C Outside temperature rises about 7 C Inside temperature ...

Page 29: ...meters The max drop height between the indoor and the outdoor machines is 30 meters If the outdoor machine is located below the indoor machine it is 25 meters The max pipe length after installation of the first branch pipe is 40 meters Max outdoor indoor drop heights 30m Max actual pipe length 70m Max drop heights between the indoor machines 15m Caution The max pipe length for the 3HP model is 45 ...

Page 30: ...puter monitoring and network monitoring Ethernet Connection SPEEDYTROUBLESHOOTING SUPER FJM is designed to perform perfect smart self diagnosis functions that support speedy troubleshooting Self diagnosis of malfunctions The SUPER FJM indoor outdoor machines has an LED monitor where you can quickly diagnose the operational variables and repair them LED display of the control panel of the outdoor m...

Page 31: ...ecures reliable operation of installation with long piping 200m Heat Exchanger New G Fin Highly efficient new G Fin increased heat transfer performance reinforced corrosion resistance and increased operating duration in frost condition Fan Guard Fan Guard has been optimized to improve air volume and reduce noise and vibration Service Valve Ball type service valve applied o easy to operate MAIN PCB...

Page 32: ... Fan Guard Fan P D t M D Changed New Mold Improved trouble caused by rust development and reduced noise by increasing air volume Motor Bracket Secured larger opening for improved air flow Compressor Digital Scroll t Twin BLDC Inverter Control Felt Double layerd felt reduces noice from compressor Q RD040 050MHXCA ...

Page 33: ...ard Min Max mmH2O Standard Min Max WG Refrigerant Type R410a R410a R410a Control Method EEV EEV EEV Temperature Control Micom Thermistors Micom Thermistors Micom Thermistors Safety Devices Fuse Fuse Fuse Option Code AVXCSH666CE 078605 1260C8 200001 300000 078605 1460F8 200001 300000 075605 16625D 200001 300000 ND6661HXCA 078605 1260C8 200000 300000 078605 1460F8 200000 300000 075605 16625D 200000 ...

Page 34: ... BH01U MR BH01U MR BH01U ND6661HXCA MR BH01 MR BH01 MR BH01 Wired Remote Controller Simplified MWR SH00 MWR SH00 MWR SH00 Multi Function MWR WE00 MWR WE00 MWR WE00 Premium MWR WS01 MWR WS01 MWR WS01 External Contact Interface Module MIM B14 MIM B14 MIM B14 Indoor Unit cont Slim 1 way cassette type cont 1 Mode HP Heat Pump 2 Norminal cooling capacities are based on Indoor temperature 81 F 27 C DB 6...

Page 35: ...rant Type R410a R410a R410a R410a Control Method EEV EEV EEV EEV Temperature Control Micom Thermistors Micom Thermistors Micom Thermistors Micom Thermistors Safety Devices Fuse Fuse Fuse Fuse Option Code AVXCMH666CE 045224 1540B3 200000 300000 045224 1840B3 200001 300000 045224 1B40B3 200001 300000 045224 1C40F1 200001 300000 ND666MHXCA Piping Connections Liquid Flare Ø mm 6 35 6 35 6 35 6 35 Ø in...

Page 36: ...H666CE MR BH01U MR BH01U MR BH01U MR BH01U ND666MHXCA MR BH01 MR BH01 MR BH01 MR BH01 Wired Remote Controller Simplified MWR SH00 MWR SH00 MWR SH00 MWR SH00 Multi Function MWR WE00 MWR WE00 MWR WE00 MWR WE00 Premium MWR WS01 MWR WS01 MWR WS01 MWR WS01 External Contact Interface Module MIM B14 MIM B14 MIM B14 MIM B14 1 Mode HP Heat Pump 2 Norminal cooling capacities are based on Indoor temperature ...

Page 37: ...s Micom Thermistors Micom Thermistors Safety Devices Fuse Fuse Fuse Fuse Fuse Option Code AVXC4H666CE 043217 1B00C8 200001 300000 043217 1D00F9 200001 300000 045A17 10020B 200001 300000 045A17 12022E 200001 300000 047A17 130340 200001 300000 ND6664HXCA 043217 1B00C8 200000 300000 043217 1D00F9 200000 300000 045A17 10020B 200000 300000 045A17 12022E 200000 300000 047A17 130340 200000 300000 Piping ...

Page 38: ...less Remote Controller AVXC4H666CE MR BH01U MR BH01U MR BH01U MR BH01U MR BH01U ND6664HXCA MR BH01 MR BH01 MR BH01 MR BH01 MR BH01 Wired Remote Controller Simplified MWR SH00 MWR SH00 MWR SH00 MWR SH00 MWR SH00 Multi Function MWR WE00 MWR WE00 MWR WE00 MWR WE00 MWR WE00 Premium MWR WS01 MWR WS01 MWR WS01 MWR WS01 MWR WS01 External Contact Interface Module MIM B14 MIM B14 MIM B14 MIM B14 MIM B14 4 ...

Page 39: ...0010 100000 200000 300000 030000 100000 200000 300000 01407F 1560C7 234848 300008 020010 100000 200000 300000 030000 100000 200000 300000 01407F 156219 236464 300008 020010 100000 200000 300000 030000 100000 200000 300000 01407F 15621B 236E6E 300028 020010 100000 200000 300000 030000 100000 200000 300000 01407F 15624F 239191 300048 020010 100000 200000 300000 030000 100000 200000 300000 Piping Con...

Page 40: ...6CE MR BH01U MR BH01U MR BH01U MR BH01U MR BH01U ND6664HXCA MR BH01 MR BH01 MR BH01 MR BH01 MR BH01 Wired Remote Controller Simplified MWR SH00 MWR SH00 MWR SH00 MWR SH00 MWR SH00 Multi Function MWR WE00 MWR WE00 MWR WE00 MWR WE00 MWR WE00 Premium MWR WS01 MWR WS01 MWR WS01 MWR WS01 MWR WS01 External Contact Interface Module MIM B14 MIM B14 MIM B14 MIM B14 MIM B14 Global 4 way cassette cont 1 Mode...

Page 41: ...59 583 External Static Pressure Standard Min Max mmH2O 2 0 4 2 0 4 2 0 4 2 0 4 Standard Min Max WG 0 08 0 0 16 0 08 0 0 16 0 08 0 0 16 0 08 0 0 16 Refrigerant Type R410a R410a R410a R410a Control Method EEV EEV EEV EEV Temperature Control Micom Thermistors Micom Thermistors Micom Thermistors Micom Thermistors Safety Devices Fuse Fuse Fuse Fuse Option Code AVXDSH666CE 015221 1103D1 200001 300000 01...

Page 42: ...roller Simplified MWR SH00 MWR SH00 MWR SH00 MWR SH00 Multi Function MWR WE00 MWR WE00 MWR WE00 MWR WE00 Premium MWR WS01 MWR WS01 MWR WS01 MWR WS01 External Contact Interface Module MIM B14 MIM B14 MIM B14 MIM B14 Drain Pump MDP E075SEE MDP E075SEE MDP E075SEE MDP E075SEE Remote Controller Receiver Kit Duct MRK A00 MRK A00 MRK A00 MRK A00 Remote Controller ReceiverWire Duct MRW 10A MRW 10A MRW 10...

Page 43: ...6 External Static Pressure Standard Min Max mmH2O 2 0 4 3 0 6 3 0 6 3 0 6 Standard Min Max WG 0 08 0 0 16 0 12 0 0 24 0 12 0 0 24 0 12 0 0 24 Refrigerant Type R410a R410a R410a R410a Control Method EEV EEV EEV EEV Temperature Control Micom Thermistors Micom Thermistors Micom Thermistors Micom Thermistors Safety Devices Fuse Fuse Fuse Fuse Option Code AVXDSH666CE 015224 1C0250 200001 300000 015213 ...

Page 44: ...ller Simplified MWR SH00 MWR SH00 MWR SH00 MWR SH00 Multi Function MWR WE00 MWR WE00 MWR WE00 MWR WE00 Premium MWR WS01 MWR WS01 MWR WS01 MWR WS01 External Contact Interface Module MIM B14 MIM B14 MIM B14 MIM B14 Drain Pump MDP E075SEE1 MDP E075SEE1 MDP E075SEE1 MDP E075SEE1 Remote Controller Receiver Kit Duct MRK A00 MRK A00 MRK A00 MRK A00 Remote Controller ReceiverWire Duct MRW 10A MRW 10A MRW ...

Page 45: ...883 953 1236 Heating High 883 953 1236 External Static Pressure Standard Min Max mmH2O 8 6 10 8 6 10 8 6 10 Standard Min Max WG 0 31 0 24 0 39 0 31 0 24 0 39 0 31 0 24 0 39 Refrigerant Type R410a R410a R410a Control Method EEV EEV EEV Temperature Control Micom Thermistors Micom Thermistors Micom Thermistors Safety Devices Fuse Fuse Fuse Option Code AVXDUH666CE 015224 1F0202 200001 300000 015A24 10...

Page 46: ... MR BH01 Wired Remote Controller Simplified MWR SH00 MWR SH00 MWR SH00 Multi Function MWR WE00 MWR WE00 MWR WE00 Premium MWR WS01 MWR WS01 MWR WS01 External Contact Interface Module MIM B14 MIM B14 MIM B14 Drain Pump MDP M075SGU1 MDP M075SGU1 MDP M075SGU2 Remote Controller Receiver Kit Duct MRK A00 MRK A00 MRK A00 Remote Controller ReceiverWire Duct MRW 10A MRW 10A MRW 10A 1 Mode HP Heat Pump 2 No...

Page 47: ...42 Heating High 2 048 2 542 External Static Pressure Standard Min Max mmH2O 15 5 25 15 5 28 Standard Min Max WG 0 59 0 20 0 98 0 59 0 20 1 10 Refrigerant Type R410A R410A Control Method EEV EEV Temperature Control Micom Thermistors Micom Thermistors Safety Devices Fuse Fuse Option Code ND666CE 015A171600E8 200001300000 015A1717025B 200001300000 ND666CA 015A171600E8 200000300000 015A1717025B 200000...

Page 48: ...ote Controller Simplified MWR WH02 MWR WH02 Multi Function MWR WE10 MWR WE10 Premium External Contact Interface Module MIM B14 MIM B14 Drain Pump MDP N047SNC1 MDP N047SNC1 Remote Controller Receiver Kit Duct MRK A00 MRK A00 Remote Controller ReceiverWire Duct MRW 10A MRW 10A 1 Mode HP Heat Pump 2 Norminal cooling capacities are based on Indoor temperature 81 F 27 C DB 66 F 19 CWB Outdoor temperatu...

Page 49: ...R410a R410a R410a R410a R410a Control Method EEV optional EEV optional EEV optional EEV optional EEV optional Temperature Control Micom Thermistors Micom Thermistors Micom Thermistors Micom Thermistors Micom Thermistors Safety Devices Fuse Fuse Fuse Fuse Fuse Option Code AVXWVH666CE 004602 1120E7 200001 300000 004602 1320E7 200001 300000 007602 15221A 200001 300000 005606 1A225E 200001 300000 0056...

Page 50: ... MWR WE00 MWR WE00 MWR WE00 MWR WE00 MWR WE00 Premium MWR WS01 MWR WS01 MWR WS01 MWR WS01 MWR WS01 External Contact Interface Module MIM B14 MIM B14 MIM B14 MIM B14 MIM B14 1 Mode HP Heat Pump 2 Norminal cooling capacities are based on Indoor temperature 81 F 27 C DB 66 F 19 CWB Outdoor temperature 95 F 35 C DB 75 F 24 CWB 3 Norminal heating capacities are based on Indoor temperature 70 F 20 C DB ...

Page 51: ...n 7 8 7 8 9 3 12 0 14 0 Heating High 8 2 8 2 9 5 13 0 15 0 Cooling High CFM 275 275 328 424 494 Heating High 290 290 335 459 530 External Static Pressure Standard Min Max mmH2O Standard Min Max WG Refrigerant Type R410a R410a R410a R410a R410a Control Method EEV optional EEV optional EEV optional EEV optional EEV optional Temperature Control Micom Thermistors Micom Thermistors Micom Thermistors Mi...

Page 52: ...ntroller AVXWNH666CE MR BH01U MR BH01U MR BH01U MR BH01U MR BH01U ND666NHXCA MR BH01 MR BH01 MR BH01 MR BH01 MR BH01 Wired Remote Controller Simplified MWR SH00 MWR SH00 MWR SH00 MWR SH00 MWR SH00 Multi Function MWR WE00 MWR WE00 MWR WE00 MWR WE00 MWR WE00 Premium MWR WS01 MWR WS01 MWR WS01 MWR WS01 MWR WS01 External Contact Interface Module MIM B14 MIM B14 MIM B14 MIM B14 MIM B14 1 Mode HP Heat P...

Page 53: ...1 018 930 1 280 1 158 1 035 1 315 1 193 1 070 1 315 1 193 1 070 Airflow Rate Cooling High m min 7 8 7 8 9 3 12 0 12 0 Heating High 8 2 8 2 9 5 13 0 13 0 Cooling High CFM 275 275 328 424 424 Heating High 290 290 335 459 530 External Static Pressure Standard Min Max mmH2O Standard Min Max WG Refrigerant Type R410a R410a R410a R410a R410a Control Method EEV EEV EEV EEV EEV Temperature Control Micom T...

Page 54: ...R BH01U MR BH01U MR BH01U MR BH01U ND666NHXCA MR BH01 MR BH01 MR BH01 MR BH01 MR BH01 Wired Remote Controller Simplified MWR SH00 MWR SH00 MWR SH00 MWR SH00 MWR SH00 Multi Function MWR WE00 MWR WE00 MWR WE00 MWR WE00 MWR WE00 Premium MWR WS01 MWR WS01 MWR WS01 MWR WS01 MWR WS01 External Contact Interface Module MIM B14 MIM B14 MIM B14 MIM B14 MIM B14 1 Mode HP Heat Pump 2 Norminal cooling capaciti...

Page 55: ...nd Level Sound Pressure High Low 4 dB A 36 32 36 32 Fan Type Sirocco Fan Sirocco Fan Motor Model YSK140 60 4B YSK140 60 4B Type Non Feedback SSR Non Feedback SSR Output W 5 5 Airflow Rate Cooling High m3 min 16 5 16 5 Heating High m3 min 20 0 20 0 Refrigerant Type R410A R410A Control Method EEV EEV Temperature Control Micom Thermistors Micom Thermistors Safety Devices Fuse Fuse Piping Connections ...

Page 56: ...80 CFM 6 004 6 004 6 357 External Static Pressure Max mmAq 8 8 8 Pa 78 5 78 5 78 5 Safety Devices Mechanical Type High Pressure Switch High Pressure Switch High Pressure Switch Crank Case Heater Crank Case Heater Crank Case Heater Fuse for PCB Fuse for PCB Fuse for PCB Electronic Type Over Voltage Protection Over Voltage Protection Over Voltage Protection Current Transformer Current Transformer Cu...

Page 57: ...g Drain Plug Drain Plug 1 Mode HP Heat Pump 2 Norminal cooling capacities are based on Indoor temperature 81 F 27 C DB 66 F 19 CWB Outdoor temperature 95 F 35 C DB 75 F 24 CWB 3 Norminal heating capacities are based on Indoor temperature 70 F 20 C DB 60 F 15 CWB Outdoor temperature 47 F 7 C DB 43 F 6 CWB 4 Sound pressure was acquired in a dead room Thus actual noise level may be different dependin...

Page 58: ...8 82 8 82 Refrigerant charging 3 8 Charge according to liquid piping g m 50 50 oz ft 0 54 0 54 1 4 Charge according to liquid piping g m 20 20 oz ft 0 215 0 215 Set Size NetWeight kg 108 108 lbs 238 1 238 1 ShippingWeight kg 116 116 lbs 255 7 255 7 Net Dimensions WxHxD mm 1 128x932x375 1 128x932x375 inch 44 13 32x36 11 16x14 3 4 44 13 32x36 11 16x14 3 4 Shipping Dimensions WxHxD mm 1 286x1 091x472...

Page 59: ...66 AVXCSH666 Series 4 way cassette panel P4SMA ND66646666 AVXC4H666 Series mini 4 way cassette panel PMSMAA ND666M6666 AVXCMH666 Series Global 4 way cassette pane PC4NUSKA ND6664H666 Drain Pump MDP E075SEE ND020 072L6666 AVXDSH020 072C6 Series MDP E075SEE1 ND100 145L6666 AVXDSH100 145C6 Series MDP M075SGU1 ND100 100S6666 AVXDUH100 110C6 Series MDP M075SGU2 ND145S6666 AVXDUH145C6 Series MDP N047SNC...

Page 60: ...oms EEV included Below 4 5MBH MCU X4WEF1 For 4 rooms EEV included Over 5 6MBH Single EEV Kit MEV A13SA Below 12MBH MEV A16SA Over 18 24MBH 2 Room EEV Kit MXD A13K116A Below 12MBH 1 unit 18MBH 24MBH 1 unit MXD A13K200A Below 12MBH 2 units MXD A16K200A 18MBH 24MBH 2 units MXD A22K200A Over 24MBH 2 units 3 Room EEV Kit MXD A13K216A Below 12MBH 2 units 18MBH 24MBH 1 units MXD A13K300A Below 12MBH 3 un...

Page 61: ...te Controller MWR WS01 Option MWR SH00 Option 485 Interface Module MIM B13A Option Ket Tag Interface Module MIM B02 Option External Contact Interface Module MIM B14 Option SIM Interface Module MIM B12 Option Centralized Controller MCM A202A Option Operation Selection Switch MCM C200 Option DMS MIM D00 Option S NET 3 MST P3P Option S NET mini MST S3W Option ...

Page 62: ...Samsung Electronics 3 1 Q Necessary Tools 3 Disassembly and Reassembly Item Remark Screw Driver Monkey Spanner Screw Driver Nipper Electric Motion Driver L Wrench ...

Page 63: ...2 Push up the green knob in the Open direction and detach the white link from the panel Detach the safety clip 3 Remove the 2 fixed screws to remove the Control Box Cover Use Screw Driver 4 Remove the Remocon Receiver and Blade Connector Wire from the PBA 3EA 5 Push the 4 panel corners and cover downwards to remove it 3 1 Indoor Unit Q Global 4way Cassette type ...

Page 64: ... Hangers at both sides of the panel inwards and rotate them 90 degrees to remove it from the indoor unit s Hock Remove the panel from the indoor unit 2 Control Box 1 Disconnect the Connector Wire that is connected to the indoor unit s PBA from the PBA 2 Unscrew the 2 fixed screws on both sides of the Control Box and disassemble the Control Box from the indoor unit Use Screw Driver ...

Page 65: ... Unscrew the screw fixed on the Bell Mouth Use Screw Driver 2 Push the Bell Mouth in the direction opposite to where it s installed on the Control Box to remove it 4 Drain Pan 1 Unscrew the screws on the 4 corners of the indoor unit Use Screw Driver 2 Remove the Drain Pan from the indoor unit ...

Page 66: ...drainage hose from the Drain Pump Use Screw Driver 2 Remove the 2 screws and take the Drain Hose out from the indoor unit to disassemble the transparent Drain Hose fixed on the side of the indoor unit Use Screw Driver 6 Evap Temperature Sensor 1 Use your hand to remove the temperature sensor attached to the Evap Pipe along with the fixing clip ...

Page 67: ...e hexangular nuts on the Motor counterclockwise to remove the nuts Take the Motor Wires attached to these three locations out with your hands prior to removing the Motor 7 Evap Temperature Sensor 1 Remove the screws of the 2 Steel Holder Evaps that are used to fix the Heat Exchanger and then remove it Use Screw Driver 2 Remove the 2 fixing screws of the Partition Evap at the Heat Exchanger s In Ou...

Page 68: ...bly Samsung Electronics 3 7 No Parts Procedure Remark 3 Remove the screw of the Cover Pipe that is used to fix the In Out Pipe Remove the In Out Pipe Use Screw Driver 4 Remove the Heat Exchanger from the indoor unit s cabinet ...

Page 69: ...k 1 MOTOR BLOWER 1 Detach the motor connectors from the PCB 2 Unscew 16 screws and detach Cabinet Base Blower Use Screw Driver 3 Unscrew 8 screws and detach Case Blower Use Screw Driver 4 Unscrew 4 bolts and separate Motor blower from Bracket Motor Use Screw Driver Q BIG DUCT ...

Page 70: ...lt and Separate Blower from the motor Use Screw Driver 2 EVAPORATOR DRAIN PAN 1 Detach EEV and Sensor connectors from the PCB Use Screw Driver 2 Unscrew 8 screws and Detach Cover Pipe Use Screw Driver 3 Unscrew 31 screws and detach Cabinet Base Blower andCabinet Base Drain Use Screw Driver ...

Page 71: ...Disassembly and Reassembly 3 10 Samsung Electronics No Parts Procedure Remark 4 Unscrew 10 screws and detach Drain Pan from the indoor unit Use Screw Driver 5 Separate Evaporator from the indoor unit ...

Page 72: ...nics 3 11 No Parts Procedure Remark 1 Common In 1 Remove fixing screw from the Cabinet Use Screw Driver 2 Separate the Cabinet from the Outdoor Unit 3 2 Outdoor Unit Q RVXVHT075 100FE RD075 100VHXFA RD075 100 120VRXFA ...

Page 73: ... the Electrical Component Box from the Outdoor Unit 2 Motor Fan 1 Remove fixing screw from the Bell Mouth Use Screw Driver 2 Separate the Bell Mouth 3 Remove fixing bolt from the Fan 4 Separate the Fan from the Outdoor Unit 5 Remove fixing screw and after removing screws separate the Motor ...

Page 74: ...and Reassembly Samsung Electronics 3 13 Q RVXVHT125FE RD125VHXFA RD125VRXFA No Parts Procedure Remark 1 Common In 1 Remove fixing screw from the Cabinet Use Screw Driver 2 Separate the Cabinet from the Outdoor Unit ...

Page 75: ...Disassembly and Reassembly 3 14 Samsung Electronics No Parts Procedure Remark 2 Separate the Electrical Component Box from the Outdoor Unit ...

Page 76: ...rts Procedure Remark 2 Motor Fan 1 Remove fixing screw from the Bell Mouth Use Screw Driver 2 Separate the Bell Mouth 3 Remove fixing bolt from the Fan 4 Separate the Fan from the Outdoor Unit 5 Remove fixing screw and after removing screws separate the Motor ...

Page 77: ...wer cable 2 Unfasten the two fixing bolts and remove the right front board 3 Unfasten the eight fixing bolts and remove the upper cover Use Screw Driver 4 Unfasten the three bolts fixing the electrical control box to the right rear plate Use Screw Driver 5 Unfasten the twelve bolts and remove the right rear plate Use Screw Driver Q RD040 050MHXCA ...

Page 78: ...even bolts and disassemble the front board Use Screw Driver 2 Fan and electricity 1 Unfasten the flange nut to remove the fan Refer to the right figure Use Monkey Spanner 2 Unfasten the four fixing bolts and remove the electrical machinery Use Monkey Spanner 3 Disassemble the electrical cable The white plug is for the upper part The blue plug is for the lower part ...

Page 79: ...lectricity support Use Screw Driver 3 Disassemble the electrical control box 1 Disassemble the parts for the electrical control panel 2 Push the buckle to loosen the three black cable ties 3 Cut the white cable tie 4 Unfasten the two fixing bolts between the electrical control box and the central separation plate Use Screw Driver ...

Page 80: ... push it outward 4 Disassemble the electrical control box Inverter board 1 Disassemble the left front board 2 Unfasten the one fixing bolt on the fixing board below the electrical control box and the left rear board 3 Unfasten the one fixing bolt on the fixing board below the electrical control box and the central separation plate Use Screw Driver ...

Page 81: ...board below the inverter control box and the electrical control box Use Screw Driver 5 Use a wrench to cut the cable tie 6 Unplug the power cable for the compressor 7 Disassemble the fixing plate below the electrical control box 8 Unfasten the fixing bolt for the inverter control box and the right rear board Use Screw Driver ...

Page 82: ...trol box 10 Use a knife to cut off the cable tie Unfasten the two bolts fixing the harness 11 Unfasten the two bolts in the lower area of the metering device and disassemble the harness Use Screw Driver 12 Disassemble the plug for the reactor connection cable 13 Unfasten the one bolt fixing the inverter control box and the central separation board Use Screw Driver ...

Page 83: ...er control box Use Screw Driver 15 Pull out the inverter control box to separate it 16 Finish disassembling the control box 5 Heat exchanger and compressor 1 Discharge all the coolants 2 Unfasten the fixing bolts of the blocking valve Use Screw Driver 3 Using a welding machine disassemble the inlet and outlet pipes 4 Disassemble the heat exchanger ...

Page 84: ...e in the external layer 6 Remove the noise protection sponge in the internal layer 7 Unfasten the bolts fixing the electrical box for the compressor Use Monkey Spanner 8 Disassemble the power cable for the compressor 9 Unfasten the three bolts on the compressor leg Use Monkey Spanner 10 Disassemble the compressor ...

Page 85: ...ess the Mode button one time to change it into 0 and then go to step 3 Step 3 Method Input the second digit of option code by pressing the temperature adjustment button up example 021E31142285 Result If 2 is displayed go to the step 4 whenever pressing the button 1 9 A B C D E F are lit in order 4 Troubleshooting 4 1 Setting Option Setup Method 4 1 1 PCB option code input method 4 1 1 1 example 02...

Page 86: ...nt button down example 021E31142285 Result If 1 is displayed go to the step 5 Step 5 Method Input the fourth digit of option code by pressing the fan speed adjustment button example 021E31142285 Result If E displays go to step 6 Step 6 Method Input the fifth digit of option code by pressing the On timer button example 021E31142285 Result If 3 displays go to step 7 SEG 5 4 2 ...

Page 87: ... step 8 Step 8 Method After completion up to step 7 pressing mode button 1 7 steps are saved internally If the first number is 1 at the time it is correct So go to step 9 If wanting to see the screen of 2 7 steps press the mode button to make the first digit 0 Step 9 Method Input the eighth digit by pressing the temperature adjustment button up example 021E31142285 Result If 4 displays go to step ...

Page 88: ...erature adjustment button down example 021E31142285 Result If 2 displays go to step 11 Step 11 Method Input the tenth digit by pressing fan speed adjustment button example 021E31142285 Result If 2 displays go to step 12 Step 12 Method Input the 11st digit by pressing the On timer button example 021E31142285 Result If 8 displays go to step 13 4 4 ...

Page 89: ...mote controller Operation mode SET TEMP fan speed displays Error If the On Off Timer and Fan indicator is flickering the wrong option code is input Put off the power of indoor unit and turn it on again and then input the option code again If the same error occurs it is the EEPROM is defective or not inserted Replace the PCB If all of On Off Timer Fan and Filter Sign indicator are flickering along ...

Page 90: ...has a default Push the button to set the display panel to Every time you push the button the display panel reads repeatedly 3 Push the button to set the display panel to Every time you push the button the display panel reads repeatedly 4 5 6 Push the button to set the display panel to Every time you push the button the display panel reads repeatedly Push the button to set the display panel to Ever...

Page 91: ...n key to set the display part to and check the display part The display part shows Press the Mode Selection key to set the display part to and check the display part The display part shows Step 4 Pressing the ON OFF button When pressing the operation ON OFF key with the direction of remote control for unit the sound Ding or Diriring is heard and the OPERATION ICON lamp of the display is flickering...

Page 92: ...ton 3 Setting Option SEG1 Push the button to set the display panel to Every time you push the button the display panel reads repeatedly Setting Option SEG3 Push the button to set the display panel to Every time you push the button the display panel reads repeatedly 5 Setting Option SEG4 Push the button to set the display panel to Every time you push the button the display panel reads repeatedly Se...

Page 93: ... panel to Every time you push the button the display panel reads repeatedly Change it into the set display of Option SEG7 and SEG8 with the button 10 9 Setting Option SEG8 Push the button to set the display panel to Every time you push the button the display panel reads repeatedly 11 Change it into the set display of Option SEG9 and SEG10 with the button Setting Option SEG9 Push the button to set ...

Page 94: ...put of option is completed If the ding sound isn t heard try again pressing the ON OFF button Step 5 Unit operation test run First Remove the battery from the remote controller Second Re insert the battery into the remote controller Third Press ON OFF key with the direction of remote controller for set Error Mode 1st If all lamps of indoor unit are flickering Plug out plug in power plug again and ...

Page 95: ...from SEG1 to SEG 24 SEG1 SEG7 SEG13 SEG19 are not set as page option Set the SEG2 SEG6 SEG8 SEG12 as ON status and SEG14 18 SEG20 24 as OFF status SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 0 X X X X X 1 X X X X X SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 2 X X X X X 3 X X X X X Set the indoor unit address and installation option with remote contro...

Page 96: ...me you press the button will be selected in rotation 6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Press Low Fan button to enter SEG9 value Press High Fan button to enter SEG10 value Each time you press the button will be selected in rotation 8 Setting Heat mode Press Mode button to be changed to HEAT mode in the ON status 9 Setting SEG...

Page 97: ...r SEG21 value Press High Fan button to enter SEG22 value Each time you press the button will be selected in rotation 18 Setting Heat mode Press Mode button to be change to HEAT mode in the OFF status 19 Setting SEG23 SEG24 mode Press Low Fan button to enter SEG23 value Press High Fan button to enter SEG24 value Each time you press the button will be selected in rotation SEG16 SEG18 SEG21 SEG23 SEG...

Page 98: ...it of an indoor unit Remote Controller Display Indication and Details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 9 100 digit 0 9 10 digit 0 9 A unit digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE Setting RMC address Group channel 16 Group address Remote Control...

Page 99: ...r 1WAY 2WAY 4WAY MODEL Drain pump SEG8 will be set to USE 3minute delay even if the drain pump is set to 0 1WAY 2WAY 4WAY DUCT MODEL Number of hours using filter SEG18 will be set to 1000hour even if the SEG18 is set to exept for 2 or 6 If you input a number other than 0 4 of the individual control of the indoor unit SEG20 the indoor is set as indoor 1 Indoor Unit 1 L F2 F1 2 N 4 1 2 3 Setting an ...

Page 100: ...s Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 3 0 or 1 channel1 0 Disuse 0 150step 8 Disuse 2 channel2 1 0 step 9 Use 1 2 C 3 channel3 2 5 C 4 channel4 You can change each digit of set option Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation PAGE MODE Theoptionmodeyou wanttochange Thetens digitofan optionSEGyouwill change Theunit...

Page 101: ...F 1 5 6 0 9 7 2 3 3 4 3 4 3 0 0 0 0 8 0 2 0 0 1 0 1 0 0 0 0 0 2 0 0 0 0 0 3 0 0 0 0 0 0 3 0 0 0 0 1 0 0 0 0 0 2 0 0 0 0 0 3 0 0 0 0 0 ND0724HXCB 0 1 4 0 7 F 1 5 6 0 c 7 2 3 4 8 4 8 3 0 0 0 0 8 0 2 0 0 1 0 1 0 0 0 0 0 2 0 0 0 0 0 3 0 0 0 0 0 0 3 0 0 0 0 1 0 0 0 0 0 2 0 0 0 0 0 3 0 0 0 0 0 ND1004HXCB 0 1 4 0 7 F 1 5 6 2 1 9 2 3 6 4 6 4 3 0 0 0 0 8 0 2 0 0 1 0 1 0 0 0 0 0 2 0 0 0 0 0 3 0 0 0 0 0 0 3 ...

Page 102: ...0 1 5 A 1 7 1 7 0 2 2 9 2 0 0 0 0 0 3 0 0 0 0 0 10 0 1 5 A 1 7 1 7 0 2 5 b 2 0 0 0 0 0 3 0 0 0 0 0 15 0 1 5 A 1 7 1 7 0 2 9 E 2 0 0 0 0 0 3 0 0 0 0 0 20 0 1 5 A 1 7 1 7 0 3 d 1 2 0 0 0 0 0 3 0 0 0 0 0 25 0 1 5 A 1 7 1 7 0 3 F 3 2 0 0 0 0 0 3 0 0 0 0 0 28 Vivace ND020VHXCA AVXWVH020CE 0 0 4 6 0 2 1 1 2 0 E 7 2 0 0 0 0 0 3 0 0 0 0 0 ND032VHXCA AVXWVH032CE 0 0 4 6 0 2 1 3 2 0 E 7 2 0 0 0 0 0 3 0 0 0 ...

Page 103: ...munication between the indoor unit and outdoor unit for 2 minutes When communication error is for over 2 minutes 2 The indoor unit receives the communication error signal from the out door unit 3 The outdoor unit tracking 3 minutes error 4 When the outdoor unit transmits a communication error which is caused by difference between the number of the installation unit and the number of com munication...

Page 104: ...ow pressure switch 2nd detection COMP DOWN 10 Reverse phase detection error 11 Freezing 6th detection compressor stop 12 Compression sensor self diagnosis G8 G9 13 Compressor down error by compression ratio control Flot switch detection Peripheral control device option setting error EEPROM error EEPROM option error SPI error Outdoor Unit or self diag nosis error Outdoor unit operation error Overfl...

Page 105: ...unit and outdoor unit for 2 minutes When communication error is for over 2 minutes 2 The indoor unit receives the communication error signal from the outdoor unit 3 The outdoor unit tracking 3 minutes error 4 When the outdoor unit transmits a communication error which is caused by difference between the number of the installation unit and the number of communication unit after completion of tracki...

Page 106: ...d detection 18 DISCHARGE high temperature 2nd detection 19 Low pressure switch 2nd detection COMP DOWN 10 Reverse phase detection error 11 Freezing 6th detection compressor stop 12 Compression sensor self diagnosis G8 G9 13 Compressor down error by compression ratio control Flot switch detection Peripheral control device option setting error EEPROM error EEPROM option error SPi error Outdoor Unit ...

Page 107: ... When communication error is for over 2 minutes 2 The indoor unit receives the communication error signal from the outdoor unit 3 The outdoor unit tracking 3 minutes error 4 When the outdoor unit transmits a communication error which is caused by difference between the number of the installation unit and the number of communication unit after completion of tracking When communication error is for ...

Page 108: ...igh temperature 2nd detection 18 DISCHARGE high temperature 2nd detection 19 Low pressure switch 2nd detection COMP DOWN 10 Reverse phase detection error 11 Freezing 6th detection compressor stop 12 Compression sensor self diagnosis G8 G9 13 Compressor down error by compression ratio control Plot switch detection Peripheral control device option setting error EEPROM error EEPROM option error Outdo...

Page 109: ...nit LED lamp display at error detecting 4 2 1 4 Wall mounted type Neo Forte without EEV with EEV Abnormal conditions LED lamp display Remark OPERATION TIMER TURBO Indoor unit room temperature sensor error open or short Indoor unit heat exchanger temperature sensor error open or short Indoor fan motor malfunction EEPROM error Option Setting Option error option wasn t set up or option data error Opt...

Page 110: ...r PCB Indoor unit heat exchanger in temperature sensor detached Heat exchanger in sensor Indoor unit heat exchanger out temperature sensor detached Heat exchanger out sensor Indoor unit heat exchanger in out temperature sensor detached Heat exchanger in out sensor Indoor unit fan motor malfunction Fan motor and cable More than 2 indoor units cool and heat simultaneously Another indoor unit operati...

Page 111: ...communication error for more than 2 minutes 2 Indoor unit receiving the communication error from outdoor unit 3 Outdoor unit tracking 3 minute error 4 When sending the communication error from outdoor unit due to the mismatching of the communication numbers and installed numbers after completion of tracking communication error for more than 2 minutes Self diagnostic error including the indoor unit...

Page 112: ... reverse phase 11 Compressor down due to 6th detection of freezing 12 Self diagnosis of condensation sensor G8 G9 13 Compressor down due to condensation ratio control Error of float switch Error of setting option switches for optional accessories EEPROM error EEPROM option error Displayed on appropriate indoor unit which is operating Displayed on outdoor unit On Flickering Off If you turn off the ...

Page 113: ...rs ex A000 error occurs in the indoor unit with the address 0 ex A047 error occurs in the indoor unit with the address 47 4 2 2 Numeric type display outdoor unit Wired remote controller wall mount type etc Meanings of the first Alphabet numbers in Error Numbers Error display order Error display method for ones occurred in indoor unit Error no indoor unit address error no repeated E471 A002 E417 A0...

Page 114: ...0 02 Samsung Electronics 4 30 ...

Page 115: ...in out sensor of IU s heat exchanger is dislocated Check if the holder of in out sensor of IU s heat exchanger is attached 1 Normal operation Operation off Normal operation page 4 45 135 Indoor clean fan rotational frequency feedback error Check the feedback connection line Check the rotational output of the clean fan motor Check if the motor operates well 1 Normal operation Normal in other Functi...

Page 116: ...ge 4 58 203 Comm Error between main sub outdoor units Comm Error between main sub Micoms Check the comm lines between outdoor units Check the Main Sub unit setting switch outdoor units Check for the disconnected line cold solder short circuit between Main Sub MICOM 1 Operation off Operation off Operation off page 4 59 221 Outdoor unit Temp SENSOR ERROR Open Short Error level over 4 9V 50 below 0 4...

Page 117: ... the right position 1 Operation off Operation off Operation off page 4 67 269 SUCTION sensor dislocation Check if SUCTION sensor location is mounted in the right position 1 Operation off Operation off Operation off page 4 68 271 SUMP_Temp Digital SENSOR ERROR Open Short Error detection condition outdoor temp over 10 error level over 4 95V 30 below 0 5V 151 Check the connection part of SUMP_Temp Di...

Page 118: ...f there are any problems with high pressure sensor Check if indoor outdoor EEV operates Check if there is any clog in the piping such as filters Check the amount of refrigerants shortage 1 Operation off Operation off Operation off page 4 78 413 Protection Control by Sump sensor Check if SUMP sensor is mounted in the right position and any problem with sensor connector Protective control operation ...

Page 119: ... is lower then 50 Check the feedback connection line Check the fan motor s rotational output Check if the motor operates well 1 Operation off Operation off Operation off page 4 87 456 Outdoor fan over voltage error Motor connection line Check if the motor operates well 1 Operation off Operation off Operation off page 4 88 457 Outdoor fan counter rotation error Check feedback connection line Check ...

Page 120: ...3 1 Outdoor unit operation flow E425 error reverse phase phase fail Yes Yes Power input 3 phase power check normal Yes No Ch display Yes Crank case heater is pre heating complete No E201 error Tracking error Tracking complete No Normal Operation ...

Page 121: ...1 CN32 CN32 4 CN41 4 CN42 8 CN44 6 CN47 4 CN48 4 CN49 4 CN51 R337 R01 5 CN901 R02 R03 6 CN62 6 CN63 5 CN64 5 CN65 3 CN70 VA74 3 CN71 7 CN72 3 CN73 3 CN74 X501 3 CN75 X502 7 CN76 7 CN77 2 CN80 C905 2 CN81 2 CN82 C907 5 CN83 2 CN84 F902_1 3 CN85 3 CN86 10 CN91 13 CN99 C923 10 CN92_SUB 3 OPT1 IC901 IC902 IC903 R001 R002 R003 R004 R005 R006 R007 R008 R009 R010 IC18 C20 D940 R401 D941 R402 C22 D942 R40...

Page 122: ... RY77 RY78 DIS1 RY79 DIS2 RY80 RY81 RY82 RY83 RY84 RY85 RY86 F901 SS71 PC501 PC502 PC503 PC504 7 CN10 2 CN12 CN13 K1 K2 K3 K4 R501 R502 R503 4 CN100 R504 R505 R506 CN31 CN32 CN32 4 CN41 4 CN42 8 CN44 6 CN47 4 CN48 4 CN49 4 CN51 R337 R01 5 CN901 R02 R03 6 CN62 6 CN63 5 CN64 5 CN65 3 CN70 VA74 3 CN71 7 CN72 3 CN73 3 CN74 X501 3 CN75 X502 7 CN76 7 CN77 2 CN80 C905 2 CN81 2 CN82 C907 5 CN83 2 CN84 F90...

Page 123: ...units subject to the outdoor unit s communication attempt while the right one shows the address of the indoor units that have responded to the communication 3 When it is not suitable to immediately operate the compressor the display part flickers CH and heats the compressor with CCH Crank Case Heater for 2 hours and 30 minutes 4 Whether or not it is at a suitable temperature to operate is determin...

Page 124: ...Is indoor room temperature sensor connector dislocated At that time is the resistance value significantly deviated from the temp table After separating indoor room temperature sensor connector from PCB measure the resistance values between both terminals Re start after replacing PCB Re start after connecting the connector to the PCB As it is due to an indoor oom temperature sensor defect replace i...

Page 125: ...oor EVAP IN sensor connector separated from the PCB At that time is the resistance value significantly deviated from the temp table After separating indoor EVAP IN sensor connector from the PCB measure the resistance values between both terminals Re start after connecting the connector to the PCB As it is due to an indoor EVAP IN sensor defect replace it Yes No No Ex Room temp 79 F 26 C Resistance...

Page 126: ...door EVAP OUT sensor connector separated from the PCB At that time is the resistance value significantly deviated from the temp table After separating indoor EVAP OUT sensor connector from the PCB measure the resistance values between both terminals Re start after replacing PCB Re start after connecting the connector to the PCB As it is due to an indoor EVAP OUT sensor defect replace it Yes Yes Ye...

Page 127: ... 3 C OK Tair in Teva out 39 F 4 C NO Tair in Teva out 39 F 4 C OK Compressor in operation Indoor unit operation Thermo On OK Error details Indoor heat exchanger s EVAP IN sensor dislocation error 2 During heating operation Average high pressure 2 45MPa OK Average low pressure 0 83MPa OK Tcond out Tair out 37 F 3 C OK Tair in Teva out 35 6 F 2 C NO Tcond out Tair out 28 4 F 2 C OK Compressor in ope...

Page 128: ...t 37 F 3 C OK Tair in Teva out 39 F 4 C NO Tair in Teva out 39 F 4 C OK Compressor in operation Indoor unit operation Thermo On OK Error details Indoor heat exchanger s EVA IN sensor dislocation error 2 During Heating operation Average high pressure 2 45MPa OK Average low pressure 0 83MPa OK Tcond out Tair out 37 F 3 C NO Tair in Teva out 35 6 F 2 C NO Tcond out Tair out 28 4 F 2 C OK Compressor i...

Page 129: ...tails Simultaneous indoor heat exchanger s EVA IN OUT sensor dislocation error 2 During Heating operation Average high pressure 2 45MPa OK Average low pressure 0 83MPa OK Tcond out Tair out 37 F 3 C NO Tair in Teva out 35 6 F 2 C NO Tcond out Tair out 28 4 F 2 C OK Compressor in operation Indoor unit operation Thermo On OK Error details Simultaneous Indoor heat exchanger s EVA IN OUT sensor disloc...

Page 130: ...roblem Outdoor unit display 1 How to diagnose Occurs when RPM values are not sent as feedback to MICOM at a PID control type fan motor 2 How to check 1 Check the HALL IC connector that carries out RPM value feedback 2 If the operational capacitor is a PCB separation type check the connection terminal 3 Check the operation status of fan motor 4 If there is no problem with the above checkup items re...

Page 131: ...k if there is any rust on the surface of the electronic expansion valve with naked eyes then check the resistance between each terminal to find any wire breaking or short circuit 4 Press the RESET KEY K3 of the outdoor unit then see if the same error occurs 4 In case of closure problem operate the indoor unit in which the error has occurred 4 In case of opening problem please do not operate the in...

Page 132: ...if there is any rust on the surface of the electronic expansion valve with naked eye then check the resistance between each terminal to find any wire breaking or short circuit 4 Press the RESET KEY K3 of the outdoor unit then see if the same error occurs 4 In case of closure problem operate the indoor unit in which the error has occurred 4 In case of opening problem please do not operate the indoo...

Page 133: ...nit then check if drain pump operates vibrates during operation Normal operation Indoor unit s power reset after replacement Reassembly Floating Sensor CONNECTOR and reset Outdoor Unit power Indoor unit power reset required Normal operation Diagnosed as a defective Floating sensor Indoor unit s power reset after replacement Replace Drain pump Replace Drain pump Replace Indoor Unit PCB Error occurs...

Page 134: ...termine below Indoor unit display Criteria Cause of problem Outdoor unit display 1 How to diagnose 1 Occurs when RPM valve fails to feedback to MICOM at a PID control type fan motor 2 How to check 1 Check HALL IC connector that carries out feedback of RPM value 2 If a fan motor operation capacitor is a PCB separating type check the connection terminal 3 Check the operational status of the fan moto...

Page 135: ...of problem Communication failure between EEPROM and MICOM Outdoor unit display Yes Are there any problems such as short or dewetting between EEPROM PIN If you restart after reentering model options and power reset does the error occur again Replace PCB Yes No Normal operation No 1 How to check Check the location of EEPORM by referring to the schematic diagram Replace PCB ...

Page 136: ...oor unit display Operation Timer Fan Filter Defrost Missed or erroneous input of remote controller options Criteria Cause of problem Display number type of indoor unit E163 occurs Lamp type all lamps flash Outdoor unit display Check relevant remote controller options for each model then enter correct options ...

Page 137: ...ns Criteria Cause of problem Display number type of indoor unit E170 occurs Lamp type all lamps flash Occurs in an indoor unit with Celsius setting Outdoor unit display Check relevant remote controller options for each model then enter correct options As this happens only in a Celsius setting model it is necessary to reenter option codes for error free models in a region where Celsius is used ...

Page 138: ...tion Cable Connection Indoor unit display Apply power 220V to the terminal of the indoor unit communication block F1 F2 Criteria Cause of problem Check for Power input 220V for the Terminal block F1 F2 Outdoor unit display Check for disconnected line after turning off the Main power wall mount type ...

Page 139: ...fect Criteria Cause of problem Check if the output of SPi Feedback is 12V Outdoor unit display 1 How to check 예 Is the SPi connector of an indoor unit separated from PCB Connect the connector to PCB and reoperate Yes No Replace Main PCB Can you measure 12V from 1 4 power with SPi connector being connected Replace SPi No Yes 1 4 ...

Page 140: ...rom the outdoor unit to indoor units and if there is no problem find an indoor unit that hampers communication by making a connection to each unit and replace the indoor unit PCB after checking out lines At that time is the power between the 2 lines a square wave with DC 0 7 Is the number of actual indoor units installed and the number of setting values of setup switch for the number of indoor uni...

Page 141: ...ellow connector of each unit communication IC for communication among outdoor units Other outdoor units the upper part of the communication connector communication IC for communication between indoor and outdoor units 2 Measure the resistance of communication IC How to measure measure resistance between no 5 no 6 Pin How to measure measure resistance between no 5 no 7 Pin 3 Diagnosis of communicat...

Page 142: ... to indoor units then measure 2 lines on the outdoor unit with SCOPE Reconnect the communication line from the outdoor unit to indoor units then remove all communication connectors on the indoor unit PCB then find an indoor unit that hampers communication by making a connection to each unit and replace indoor unit PCB after checking out lines After 2 minutes find an indoor unit than shows a commun...

Page 143: ...door unit display Criteria Cause of problem Outdoor unit display Error reset Key 3 Confirm an error outdoor unit U200 U201 U202 U203 Is power input normal 15V 5V Check if there is a wire break in the external communication line Check the setup optionfor the outdoor unit K13 K14 Replace PCB Check power Change the wire break or connection Setup change Yes Yes Yes No No No 1 How to check If communica...

Page 144: ...om the PCB Does the resistance value greatly deviate from the temperature table After separating the outdoor temperature sensor connector from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB As it is due to a problem with the outdoor temperature sensor replace it Yes No No Yes Yes Part to measure resistan...

Page 145: ...e to the next After separating the outdoor temperature sensor connector from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB As it is due to a problem with the outdoor temperature sensor replace it Yes No No Yes Yes Temperature Resistance KΩ F C 158 140 122 104 86 70 50 32 14 70 60 50 40 30 21 10 0 10 2 2...

Page 146: ...ector dislocated from the PCB Does the resistance value greatly deviate from the temperature table After separating the outdoor COND OUT temperature sensor connector from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB At it is due to a problem with the outdoor COND OUT replace it Yes No No Part to measur...

Page 147: ...the sensor holder Yes 1 How to diagnose 1 During Cooling operation there will be no detection 2 During Heating operation Each of the below conditions have to be met for at least 20 minutes No Defective sensor replace sensor No Clogged sensor path Replace a heat exchange ASS Y No Average high pressure 2 45MPa OK Average low pressure 0 83MPa OK Tcond out Tair out 37 F 3 C OK Tair in Teva out 35 6 F ...

Page 148: ...r connector for a digital compressor dislocated from the PCB Does the resistance value greatly deviate from the temperature table After separating the discharge temperature sensor connector from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB As it is due to a problem with the discharge temperature sensor...

Page 149: ... scroll compressor dislocated from the PCB Does the resistance valve greatly deviate from the temperature table After separating the discharge temperature sensor connector of the fixed outdoor scroll compressor from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB As it is due to a problem with the dischar...

Page 150: ...r securely attached Is the resistance value for the sensor appropriate Does the compressor operate well and is the temperature of discharge piping for compressor kept at certain temperature level Restart then check again Reinsert the sensor Re attach the sensor holder Yes No Analyze the cause of the compressor s failure to operate No Defective sensor Replace the sensor No ...

Page 151: ...ht before the start of compressor Tsump ini current compressor s SUMP temp Tsump real When the difference between Tsump ini and Tsump real is an absolute value so that it cannot be more than 35 6 F 2 C In other words the condition of Tsump real Tsump ini 35 6 F 2 C has been satisfied for 60 minutes since a compressor started it is diagnosed as an error After 60 minutes of compressor operation ther...

Page 152: ...ni current temperature of compressor Tsuc real if the condition of Tsuc real Tsuc ini 35 6 F kept for 30 minutes it is diagnosed as error Suction temperature sensor dislocation error Outdoor unit display 1 How to check Complete Are a Suction sensor and a sensor holder securely attached Is the resistance value for Suction sensor appropriate refer to E231 Defective sensor replace sensor No Reinsert ...

Page 153: ...cated from the PCB Does the resistance value greatly deviate from the temperature table After separating the outdoor SUMP sensor connector from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB As it is due to a problem with the outdoor SUMP sensor replace it No No Yes Yes Yes Part to measure resistance val...

Page 154: ...t error detection only if it is under 0 4V 5 During refrigerant refill retrieval omit low pressure sensor error detection 4 3 32 Low Ppressure Temperature Sensor error Open Short Operation Timer Fan Filter Defrost Wire breaking or failure of the relevant sensor Refer to how to determine below Indoor unit display Criteria Cause of problem Outdoor unit display How to detect OPEN SHORT error in Low H...

Page 155: ...located from the PCB Does the resistance value greatly deviate from the temperature table After separating the outdoor Oil Balance Valve sensor connector from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB At it is due to a problem with the outdoor Oil Balance Valve sensor No No Yes Yes Yes Part to measu...

Page 156: ...cated from the PCB Does the resistance value greatly deviate from the temperature table After separating the outdoor SUCTION sensor connector from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB As it is due to a problem with the outdoor SUCTION sensor replace it No No Yes Yes Yes Part to measure resistan...

Page 157: ...from the PCB Does the resistance value greatly deviate from the temperature table After separating the liquid temperature sensor connector from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB As it is due to a problem with the liquid temperature sensor replace it No No Yes Yes Yes Part to measure resistan...

Page 158: ... Is connector correctly connected to PCB Can you hear the valve operating sound when power on Is the connector of sol valve coil correctly connected Replace sol valve body Check and restart the connector No Yes No Yes No Yes Check and reassemble the coil Restart the set and check if there is error ...

Page 159: ...ocated from the PCB Time does the resistance value greatly deviate from the temperature table After separating the EVI IN sensor connector from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB As it is due to a problem with the outdoor EVI IN sensor replace it No No Yes Yes Yes Part to measure resistance v...

Page 160: ...ocated from the PCB Time does the resistance value greatly deviate from the temperature table After separating the EVI OUT sensor connector from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB As it is due to a problem with the outdoor EVI OUT sensor replace it No No Yes Yes Yes Part to measure resistance...

Page 161: ...citor or wire breaking Locked service valve excessive refrigerant Criteria Detect when the value of high pressure sensor is over 4 0MPa Outdoor unit display Do the values of S net and Manifold gauge correspond Does indoor outdoor EEV operate well Is there any clogged place in the piping ex filter Check the amount of refrigerant Test operation Open the service valve Replace a high pressure sensor C...

Page 162: ... cooling operation below 23 F 5 C this error may occur Criteria Detect when the value of low pressure sensor is below 0 25MPa during cooling operation 0 14MPa during heating operation Outdoor unit display Do the values of S net and Manifold gauge correspond Does indoor outdoor EEV oper ate well Is there any clogged place in the piping ex filter Check the amount of refrigerant Is there any leakage ...

Page 163: ...cted to PCB Does the sensor indicate the temperature correctly Is the sensor correctly connected to the bottom of the compressor sensor Liquid compressor protection error See problem solution E477 Check and restart the connector No Yes Yes Yes No No Check and reattach the sensor Check other temperature sensor error Check problem solution ...

Page 164: ...in discharge check valve of the compressor in the stop side outdoor unit Criteria Detect when the value of compressor s discharge temperature sensor is over 275 F 135 C Outdoor unit display Is the discharge sensor resistance of the compressor normal refer to E251 Test operation Are all service valves open Does indoor outdoor EEV operate well Is there any clogged part in the piping ex Filter Check ...

Page 165: ...der or a failure to have one or all of phase power When phase power is back to normal E425 is automatically released Indoor unit display Criteria Cause of problem Outdoor unit display Check the power for key parts Is the power for red white white black red black wires of CN82 about AC 380V Turn off the power breaker then exchange 2 of the three lines of 3 phase power fuse then check again Does err...

Page 166: ...ressure 1 low pressure 1 is over 8 5 for more than 10 minutes Outdoor unit display 1 How to check No Do the values of S net and Manifold gauge correspond Does indoor outdoor EEV operate well Is there any clogged place in the piping ex filter Check the amount of refrigerant Test operation Open the service valve Replace a low pressure sensor Check the relevant EEV Check the piping Yes Yes Yes Are se...

Page 167: ... before entering a balance keeping operation the error is displayed 4 At the stage of releasing oils during balance keeping operation if there is less than 44 6 F 7 C temperature change after opening an oil valve balance keeping valve and opening the hot gas bypass the error is displayed Outdoor unit display 1 How to check Replace the coil Is the resistance valve of coil appropriate Is oil valve 1...

Page 168: ...y connected to PCB Check Liquid Bypass Valve open failure error Is EEV coil correctly connected Replace following EEV Check and restart the connector No Yes Normal Yes No Failure Check and reassemble the coil Solve the following valve problem If the problem continually occurs check the leakage of intercooler ...

Page 169: ...ts the operation in outdoor temperature over 59 F 15 C Outdoor unit display 1 How to check The above error code is not caused by a product s problem but a function to protect the product by limiting the available tempera ture range so please refer to the usable temperature range in the product manual If the error code is displayed despite a condition that does not belong to any of the above diagno...

Page 170: ...rage before Cooling Unable to Restart Is high pressure sensor correctly connected to PCB Replace the high pressure sensor Is there leakage of refrigerant in the system or charging inferior Check by Manifold gage Check and restart the connector No No Yes Yes Refill or recharge the refrigerant ...

Page 171: ...ower the rotational frequency of the motor to cool it down there would be no problem as long as the motor operates 2 Check if outdoor fan motor rotates or is locked 3 If it is locked it is possible to operate by removing the cause of the lock 4 3 51 RPM Error of an Outdoor Fan Motor Outdoor fan motor lock or defect When an operating outdoor fan motor s rotational frequency is more than 100rpm diff...

Page 172: ...down 3 Need to check if there is a problem with fan load status 4 3 53 Counter Rotation Error of an Outdoor Fan Motor Due to wind that can run the fan counter wise When the rotational direction of an outdoor fan motor is counter clockwise before operating Indoor unit display Criteria Cause of problem Outdoor unit display 1 How to diagnose 1 Check if the start instruction of outdoor unit s fan is c...

Page 173: ...iteria Cause of problem Outdoor unit display 1 How to check Is the resistance of CT sensor connector normal Are the CT values during the stop of compressor all 0 Are CT values during operation more than 20A Are the values from an independent ammeter and that of CT sensor identical Test operation Check and complete Replace the CT sensor Replace the CT sensor Replace the CT sensor Compressor breakdo...

Page 174: ...ompressor works fine during operation it does not have any problem If not the compressor is broken Is the resistance of CT sensor connector normal Are the CT values during the stop of compressor all 0 Does the compressor stop operating even with the contact of a magnetic contactor Are the values from an independent ammeter and that of CT sensor identical Test operation Replace the CT sensor Replac...

Page 175: ...rge sensor correctly connected Check Main EEV EVI EEV normal operation Is the sensor correctly connected to the bottom of the compressor sensor Check and replace the leakage of Discharge Check Valve Check the sensor connection No Normal Yes Failure Failure Solve the following EEV problem Solve the following valve problem ...

Page 176: ...is any rust on the surface of the coil of an electronic expansion valve with the naked eye and then check the resistance between each terminal to find any wire breaking or short circuit 4 Press the RESET KEY K3 of the outdoor unit then see if the same error occurs 4 In case of closure problem operate the indoor unit in which the error has occurred 4 In case of opening problem please do not operate...

Page 177: ...k if there is any rust on the surface of the coil of an electronic expansion valve with the naked eye and then check the resistance between each terminal to find any wire breaking or short circuit 4 Press the RESET KEY K3 of the outdoor unit then see if the same error occurs 2 In case of closure problem operate the indoor unit in which the error has occurred 2 In case of opening problem please do ...

Page 178: ...ached 1 Normal operation Operation off Normal operation page 4 102 151 The 2 nd opening error of indoor electrically operated valve Check the PCB connection of electrically operated valve wire Check the sealing condition of electrically operated valve Check if there is any external rust internal breakage short circuit on the coil After resetting OU K3 re check if error occurs again Replace electri...

Page 179: ...door temp sensor circuit and any problem in the sensor Check the wire breaking of the outdoor temp sensor circuit and the connection status of the connector PCB 1 Operation off Operation off Operation off page 4 113 231 COND_OUT Main Temp SENSOR ERROR Open Short Error level over 4 9V 50 below 0 4V 93 Check the connection part of the COND OUT temp sensor circuit and any problem in the sensor Check ...

Page 180: ...ny clog in the piping such as filters 1 Operation off Operation off Operation off page 4 124 440 Prohibit heating for outdoor temperature over 30 Check if there is any dislocation pbm with outdoor temp sensor If outdoor temp measured normal normal operation by protective control 1 Operation off Operation off Operation off page 4 125 442 Prohibit filling mode for outdoor temperature over 15 Check i...

Page 181: ...of problem Yes Yes Is indoor room temperature sensor connector dislocated At that time is the resistance value significantly deviated from the temp table After separating indoor room temperature sensor connector from PCB measure the resistance values between both terminals Re start after replacing PCB Re start after connecting the connector to the PCB As it is due to an indoor oom temperature sens...

Page 182: ...How to check Is indoor EVAP IN sensor connector separated from the PCB At that time is the resistance value significantly deviated from the temp table After separating indoor EVAP IN sensor connector from the PCB measure the resistance values between both terminals Re start after connecting the connector to the PCB As it is due to an indoor EVAP IN sensor defect replace it Yes No No Ex Room temp 2...

Page 183: ...ow to check Is indoor EVAP OUT sensor connector separated from the PCB At that time is the resistance value significantly deviated from the temp table After separating indoor EVAP OUT sensor connector from the PCB measure the resistance values between both terminals Re start after replacing PCB Re start after connecting the connector to the PCB As it is due to an indoor EVAP OUT sensor defect repl...

Page 184: ...door unit Tcond out Tair out 3 C OK Tair in Teva out 4 C NO Tair in Teva out 4 C OK Compressor in operation Indoor unit operation Thermo On OK Error details Indoor heat exchanger s EVAP IN sensor dislocation error 2 During heating operation Average low pressure 8 5kg cm2 OK Tcond out Tair out 3 C OK Tair in Teva out 2 C NO Tcond out Tair out 2 C OK Compressor in operation Indoor unit operation The...

Page 185: ...oling Operation Tcond out Tair out 3 C OK Tair in Teva out 4 C NO Tair in Teva out 4 C OK Compressor in operation Indoor unit operation Thermo On OK Error details Indoor heat exchanger s EVA IN sensor dislocation error 2 During Heating operation Average high pressure 25kg cm2 OK Tcond out Tair out 3 C OK Tair in Teva out 2 C NO Tcond out Tair out 2 C OK Compressor in operation Indoor unit operatio...

Page 186: ...ermo On OK Error details Simultaneous indoor heat exchanger s EVA IN OUT sensor dislocation error 2 During Heating operation Average high pressure 25kg cm2 OK Teva out Tair out 3 C OK Tair in Teva out 2 C NO Tcond out Tair out 2 C OK Compressor in operation Indoor unit operation Thermo On OK Error details Simultaneous Indoor heat exchanger s EVA IN OUT sensor dislocation error 2 How to check Check...

Page 187: ...if there is any rust on the surface of the electronic expansion valve with naked eyes then check the resistance between each terminal to find any wire breaking or short circuit 4 Press the RESET KEY K3 of the outdoor unit then see if the same error occurs 4 In case of closure problem operate the indoor unit in which the error has occurred 4 In case of opening problem please do not operate the indo...

Page 188: ...ck if there is any rust on the surface of the electronic expansion valve with naked eye then check the resistance between each terminal to find any wire breaking or short circuit 4 Press the RESET KEY K3 of the outdoor unit then see if the same error occurs 4 In case of closure problem operate the indoor unit in which the error has occurred 4 In case of opening problem please do not operate the in...

Page 189: ...in Pan get lower Reset the power of the indoor unit then check if drain pump operates vibrates during operation Normal operation Indoor unit s power reset after replacement Reassembly Floating Sensor CONNECTOR and reset Outdoor Unit power Indoor unit power reset required Normal operation Diagnosed as a defective Floating sensor Indoor unit s power reset after replacement Replace Drain pump Replace...

Page 190: ...termine below Indoor unit display Criteria Cause of problem Outdoor unit display 1 How to diagnose 1 Occurs when RPM valve fails to feedback to MICOM at a PID control type fan motor 2 How to check 1 Check HALL IC connector that carries out feedback of RPM value 2 If a fan motor operation capacitor is a PCB separating type check the connection terminal 3 Check the operational status of the fan moto...

Page 191: ... in an indoor unit is different from current operational status other indoor unit s operational mode Check the operational mode of outdoor unit or other indoor unit then re enter or stop the operational mode of the relevant unit If it is necessary to apply a different operational mode to an indoor unit from others please stop other indoor units then operate the indoor unit ...

Page 192: ...of problem Communication failure between EEPROM and MICOM Outdoor unit display Yes Are there any problems such as short or dewetting between EEPROM PIN If you restart after reentering model options and power reset does the error occur again Replace PCB Yes No Normal operation No 1 How to check Check the location of EEPORM by referring to the schematic diagram Replace PCB ...

Page 193: ...oller options Criteria Cause of problem Display number type of indoor unit E170 occurs Lamp type all lamps flash Occurs in an indoor unit with Celsius setting Outdoor unit display Check relevant remote controller options for each model then enter correct options As this happens only in a Celsius setting model it is necessary to reenter option codes for error free models in a region where Celsius i...

Page 194: ...rom the outdoor unit to indoor units and if there is no problem find an indoor unit that hampers communication by making a connection to each unit and replace the indoor unit PCB after checking out lines At that time is the power between the 2 lines a square wave with DC 0 7 Is the number of actual indoor units installed and the number of setting values of setup switch for the number of indoor uni...

Page 195: ...Remove a communication line from the outdoor unit to indoor units then measure 2 lines on the outdoor unit with SCOPE Reconnect the communication line from the outdoor unit to indoor units then remove all communication connectors on the indoor unit PCB then find an indoor unit that hampers communication by making a connection to each unit and replace indoor unit PCB after checking out lines After ...

Page 196: ...ain PCB and inverter PCB during Indoor unit display Criteria Cause of problem Outdoor unit display 1 How to check Yes Service complete No Check if there is any communication error Restart after turning off the power Yes Inspect M C No Check if the INVERTER PBA power on Change the PBA Yes Connect the connector No Check the connection between the INVERTER PBA and MAIN PBA MAIN CN39 INVERTER CN70 CN7...

Page 197: ...tor dislocated from the PCB Does the resistance value greatly deviate from the temperature table After separating the outdoor temperature sensor connector from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB As it is due to a problem with the outdoor temperature sensor replace it Yes No No Yes Yes Tempera...

Page 198: ...ature sensor connector dislocated from the PCB Does the resistance value greatly deviate from the temperature table After separating the outdoor COND OUT temperature sensor connector from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB At it is due to a problem with the outdoor COND OUT replace it Yes No ...

Page 199: ...insert the sensor Re attach the sensor holder Yes 1 How to diagnose 1 During Cooling operation there will be no detection 2 During Heating operation Each of the below conditions have to be met for at least 20 minutes No Defective sensor replace sensor No Clogged sensor path Replace a heat exchange ASS Y No Average high pressure 25kg cm2 OK Tcond out Tair out 3 C OK Tair in Teva out 2 C OK Tcond ou...

Page 200: ...e sensor connector dislocated from the PCB Does the resistance value greatly deviate from the temperature table After separating the discharge temperature sensor connector from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB As it is due to a problem with the discharge temperature sensor replace it Yes No...

Page 201: ...ely attached Is the resistance value for the sensor appropriate Refer to E231 Does the compressor operate well and is the temperature of discharge piping for compressor kept at certain temperature level Restart then check again Reinsert the sensor Re attach the sensor holder Yes No Analyze the cause of the compressor s fail ure to operate No Defective sensor Replace the sensor No ...

Page 202: ...rror in Low High pressure sensor 1 During oil retrieval omit the error detection and start detecting 5 minutes after complete operation 2 During safety start operation omit the error detection and start detecting 5 minutes after complete operation 3 During defrost operation omit the error detection and start detecting 5 minutes after complete operation 4 SHORT error detection carry out error detec...

Page 203: ...r connector dislocated from the PCB Does the resistance value greatly deviate from the temperature table After separating the liquid temperature sensor connector from the PCB measure the resistance value between both terminals Restart after replacing the PCB Restart after connecting the connector to the PCB As it is due to a problem with the liquid temperature sensor replace it No No Yes Yes Yes T...

Page 204: ... failure of the relevant sensor 1 How to check The sensor connection parts fell off the PCB Measured resistance out of the range Pull out the sensor part Measure the inter terminal resistance Replace the PCB and restart Insert the part in the PCB and restart Replace the damaged sensor Yes No Yes Yes No Part to measure resistance value Temperature C Resistance KΩ 130 120 100 80 60 25 20 10 0 8 9 11...

Page 205: ...r displays the tem perature ok Check for clogging in the suction area of the indoor machine 1 How to check Outdoor unit display Indoor unit display Operation Timer Fan Filter Defrost Criteria All the operating indoor machines do not reach 4 C for more than five minutes Cause of problem Check if the indoor FAN MOTOR operates normally Check if the indoor EEV operates normally Check the indoor heat e...

Page 206: ...hile the AC or heater is on the indoor outdoor fan operates normally 1 How to check Outdoor unit display Indoor unit display Operation Timer Fan Filter Defrost Criteria The high pressure sensor reading approaches 38KG CM2 Cause of problem AC in operation Check electrical installation of the outdoor machine Polluted outdoor machine heat exchanger Closed sub valve Add some coolant Check for clogging...

Page 207: ...peration Yes Connect S net to vacuum forceful Check the pipeline No Clogging in the pipe ex filter Outdoor unit display Indoor unit display Operation Timer Fan Filter Defrost Criteria The Cond out sensor temperature is detected below 35 C Cause of problem Insufficient coolant clogging in the motor Bad compressor Bad Cond out sensor The outdoor compressor s Discharge Check Valve leaks Exceeding the...

Page 208: ...st operation Yes Check the amount of coolant Check the pipeline No Clogging in the pipeline ex filter The sensor s resistance normal Refer to E251 Outdoor unit display Indoor unit display Operation Timer Fan Filter Defrost Criteria The compressor temperature above 110 C Cause of problem Insufficient coolant Clogging in the outdoor machine s solenoid valve Clogging in the sub valve Malfunctioning e...

Page 209: ... No Overcurrent option setting ok Outdoor unit display No heater operation with the outside temperature above 30 C No AC operation with the outside temperature below 10 C No refilling of the heater coolant with the outside temperature above 15 C Indoor unit display No signals Criteria If the outside temperature is above 30 C operation of the indoor heater with a remocon causes this error The indoo...

Page 210: ... operates normally Check the amount of coolant 1 How to check Test operation Yes Replace the OLP sensor Check the pipeline No Clogging in the pipeline ex filter v OLP sensor is resistance is normal Refer to E320 Outdoor unit display Indoor unit display Operation Timer Fan Filter Defrost Criteria OLP SENSOR temp above Trip_Dis Cause of problem See if the sub valve is open Check the amount of coolan...

Page 211: ... in the fan Inaccurate assembly of the fan connection cable Yes Assemble the cable accurately before operation Before connecting the fan terminal to PCB turn off the power 1 How to check Outdoor unit display Indoor unit display Operation Timer Fan Filter Defrost Criteria Refer to the below method Cause of problem Fan stuck Poor fan connection Damaged fan ...

Page 212: ...y 1st 1 Diagnosis 1 Check only if the AC is on The following conditions met for more than 20 minutes 2 Check if the heater is on All the conditions should be met Min two indoor machines operate when the thermostat is started The mean high pressure exceeds 18kg cm2 5 minutes of safe operation Maintained for more than 5 minutes Indoor machine evaporator inlet temperature actual temperature 3 C and e...

Page 213: ...5 1 Samsung Electronics 5 Exploded Views and Parts List 5 1 Indoor Unit 5 1 1 Slim1 way cassette type Body ...

Page 214: ...Y 1 SA 17 DB67 00833A DRAIN PUMP PBT 1 0 WHITE 1 SA 18 DB69 00137A BAND RING STS304 T1 5 PI14 1 SNA 19 DB73 00390B RUBBER BASE PUMP NBR 30 BLK 1 SNA 20 DB73 00391B RUBBER CAP PUMP NBR 30 BLK 1 SNA 21 DB63 01699A COVER PUMP ABS 2 5 78 100 GRAY 1 SNA 22 DB95 00131M ASS Y SENSOR FLOAT SLIM1WAY SmH250 02L 180mm RED BLK 1 SA 23 DB94 01367C ASS Y DRAIN PAN ASS Y 1 SA 24 DB73 00133B RUBBER CAP DRAIN SOCK...

Page 215: ...Exploded Views and Parts List 5 3 Samsung Electronics Slim 1 way cassette type cont Panel A type ...

Page 216: ...BS 2 196 437 BLK 1 SA 7 DB63 01695A FILTER AIR INLET G ABS 2 196 320 BLK 1 SA 8 DB63 01697A COVER DISPLAY PCB HIPS 2 5 117 154 BLK 1 SNA 9 DB64 00237A PANEL DISPLAY LED AKM 2800 PC 1 SA 10 DB64 01759A PANEL FRONT SLIM 1WAY ABS 40 465 1180 DA White 1 SNA 11 DB64 01760A WINDOW DISPLAY PCB PC 1 5 40 40 MILKY WHT 1 SNA 12 DB64 01762A GRILLE AIR INLET ABS 2 0 213 859 WHT 1 SA 13 DB65 00023A CLIP WIRE A...

Page 217: ...Exploded Views and Parts List 5 5 Samsung Electronics Slim 1 way cassette type cont Panel B type ...

Page 218: ... 03266A GUIDE AIR OUTLET S AGSP1181 ABS 2 5 32 760 SLIM1WAY 1 SA 15 DB61 03267A GUIDE CUSHION AIR OUT S LF AGSP1181 ABS 12 32 448 SLIM1WAY 1 SA 16 DB61 03268A GUIDE CUSHION AIR OUT S RH AGSP1181 ABS 12 32 435 SLIM1WAY 1 SA 17 DB61 03366A GUIDE FILTER L AGSP1181G ABS 2 55 438 SLIDE PANEL 1 SA 18 DB61 03367A GUIDE FILTER S AGSP1181G ABS 2 55 278 SLIDE PANEL 1 SA 19 DB63 01858A FILTER AIR INLET L AGS...

Page 219: ...5 7 Samsung Electronics 5 1 2 Mini 4 way cassette type Body 31 8 15 16 12 16 11 17 21 5 4 1 2 9 10 6 18 7 3 14 13 20 19 24 26 27 28 29 30 23 25 22 33 32 ...

Page 220: ... 4WAY CASSETTE 1 SA 16 DB73 00307A RUBBER WIRE HOLE NBR 52 1 2 SNA 17 DB90 02225A ASS Y COVER PIPE MINI 4WAY CASSETTE 1 SA 18 DB61 02527A HOLDER EVAP STS304 T0 7 4 SA 19 DB94 00846A ASS Y DRAIN HOSE MINI 4WAY CASSETTE 1 SA 20 DB90 01010A ASS Y COVER DRAIN CH040EZM NEW 4WAY CASSETTE 1 SNA 21 DB61 02490A GUIDE EVAP STS304 T0 7 1 SA 22 DB96 05354D ASS Y EVAP UNIT MINI 4WAY CASSETTE 1 SNA 23 DB31 0030...

Page 221: ...Exploded Views and Parts List 5 9 Samsung Electronics Mini 4 way cassette type cont Panel PMSMAA 30 19 2 15 3 17 27 18 31 13 1 14 9 20 22 21 32 8 29 7 6 11 25 26 16 10 12 24 23 4 5 33 28 ...

Page 222: ...074D CLAMP CABLE DA 4N 2 SA 16 DB65 00023A CLIP WIRE ASS Y L130mm 1 SA 17 DB63 01364A COVER A ABS V0 BLK 1 SA 18 DB63 01366A COVER B ABS V1 BLK 2 SA 19 DB63 01377A COVER C ABS V2 BLK 1 SA 20 DB63 01036A COVER KNOB HIPS UL94 HB WHT 2 SA 21 DB64 01145A KNOB SLIDE HIPS 94HB HG 0760 WHT 2 SA 22 DB67 00030A SPRING KNOB STS304 T0 5 2 SA 23 DB69 01269A CUSHION IN EPS 30 4 SA 24 DB69 01270A CUSHION OUT EP...

Page 223: ...Exploded Views and Parts List 5 11 Samsung Electronics 5 1 3 4 way cassette type Body AVXC4H052 072C ND052 0724H ...

Page 224: ...64 01734A CABI SIDE SGCC M 2 2 SNA 10 DB90 02692A ASS Y COVER PIPE ASS Y 1 1 SNA 11 DB90 03189A ASS Y CABI FEONT ASS Y SGCC M 1 1 SNA 12 DB90 01950B ASS Y COVER DRAIN PUMP ASS Y 1 1 SNA 13 DB94 01389A ASS Y HOSE DRAIN ASS Y 1 1 SNA 14 DB61 03093A HOLDER EVAP STS301 2 2 SNA 15 DB96 08027B ASS Y EVAP UNIT ASS Y 1 SNA DB96 08027A ASS Y EVAP UNIT ASS Y 1 SNA 16 DB90 03190A ASS Y CABI BACK ASS Y SGCC M...

Page 225: ...Exploded Views and Parts List 5 13 Samsung Electronics 4 way cassette type cont Body AVXC4H100 110 145C ND100 110 145H ...

Page 226: ... 1 SA 9 DB64 01562A CABI SIDE SGCC M 2 2 SA 10 DB90 02692A ASS Y COVER SIDE ASS Y 1 1 SA 11 DB90 02690A ASS Y CABI FRONT ASS Y SGCC M 1 1 SA 12 DB90 01950B ASS Y COVER DRAIN PUMP ASS Y 1 1 SA 13 DB90 02693A ASS Y HOSE DRAIN ASS Y 1 1 SA 14 DB61 02701A HOLDER EVAP STS301 2 2 SA 15 DB96 06677A ASS Y EVAP UNIT ASS Y 1 SA DB96 06707A ASS Y EVAP UNIT ASS Y 1 SA 16 DB90 02688A ASS Y CABI BACK ASS Y SGCC...

Page 227: ...Exploded Views and Parts List 5 15 Samsung Electronics 4 way cassette type cont Panel P4SMA 10 11 22 23 17 18 24 19 28 12 3 27 13 21 26 25 20 2 1 9 7 8 6 5 4 16 15 14 ...

Page 228: ...MOTOR A POM 1 SNA 13 DB66 01104A LINK MOTOR B POM 1 SNA 14 DB61 02711A HOLDER LINK BLADE ABS BLK 8 SNA 15 DB66 01105A LINK BLADE POM 7 SNA 16 DB66 01106A LINK UNIVERSAL JOINT POM 2 SNA 17 DB66 01107A JOINT UNIVERSAL POM 5 SNA 18 DB63 01486A COVER SIDE A HIPS BLK 1 SNA 19 DB63 01487A COVER SIDE B HIPS BLK 1 SNA 20 DB63 01488A COVER SIDE C HIPS BLK 1 SNA 21 DB63 01489A COVER SIDE D HIPS BLK 1 SNA 22...

Page 229: ...Exploded Views and Parts List 5 17 Samsung Electronics 5 1 4 Global 4 way cassette type Body ND 4HXCB 1 5 6 2 20 9 9 1 23 26 27 19 8 7 21 13 17 15 16 14 18 12 10 11 3 22 25 24 4 ...

Page 230: ...TH HIPS T0 2 448 5 499 1 1 1 1 SA 11 DB63 02702B COVER SAFETY ABS T3 0 414 379 1 1 1 1 SA 12 DB94 02667C ASS Y DRAIN PAN ASS Y 1 1 1 1 SA 13 DB61 04498A CASE PUMP HIPS T0 2 139 98 6 1 1 1 1 SNA 14 DB63 02703A COVER PUMP HIPS T0 2 81 2 57 9 1 1 1 1 SA 15 DB67 00982C DRAIN PUMP ASS Y 1 1 1 1 SA 16 DB73 00521A RUBBER CAP PUMP EPDM 1 1 1 1 SA 17 DB73 00523A RUBBER BASE PUMP NBR 1 1 1 1 SA 18 DB95 0446...

Page 231: ...2 16062A ASS Y COLLECTOR ASS Y 1 SNA DB62 16062B ASS Y COLLECTOR ASS Y 1 SNA DB96 16061A ASS Y COLLECTOR ASS Y 1 SNA DB96 14726B ASS Y COLLECTOR ASS Y 1 SNA 26 DB96 16063A ASS Y EVAP UNIT ASS Y 1 SA DB96 16063B ASS Y EVAP UNIT ASS Y 1 SA DB96 15439B ASS Y EVAP UNIT ASS Y 1 SA DB96 14909B ASS Y EVAP UNIT ASS Y 1 SA 27 DB95 04461A ASS YTHERMISTOR IN EVA IN OUT ASS Y 1 1 1 1 SA ...

Page 232: ...0 02 Samsung Electronics 5 20 ...

Page 233: ...Exploded Views and Parts List 5 21 Samsung Electronics Global 4way cassette type cont Panel ND 4HXCB 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 25 23 24 26 27 28 1 2 3 4 5 ...

Page 234: ...A COVER BACK B HIPS BLK 1 SNA 13 DB63 02736A COVER BACK C HIPS BLK 1 SNA 14 DB63 02737A COVER BACK D HIPS BLK 1 SNA 15 DB66 01544A LINK CLAMP HIPS VICTORY GRAY 2 SA 16 DB63 02740A CUSHION IN EPS 25 2 SNA 17 DB63 02741A CUSHION IN L EPS 25 1 SNA 18 DB63 02742A CUSHION IN R EPS 25 1 SNA 19 DB63 02744A COVER DISPLAY HIPS VICTORY GRAY 1 SA 20 DB64 02542A WINDOW SENSOR PC WAFFLE MILKY 1 SA 21 DB63 0273...

Page 235: ...ews and Parts List 5 23 Samsung Electronics 23 8 13 9 14 2 16 18 17 1 6 15 21 11 24 25 4 5 22 26 10 3 8 7 19 20 23 6 23 4 23 5 23 3 23 7 23 1 23 8 23 2 12 5 1 5 Duct type Slim I AVXDSH020 032 040C ND020 032 040LH ...

Page 236: ...Y PARTITION ASS Y 1 SA 16 DB61 02282A BRACKET MOTOR SGCC M T2 0 1 SA 17 DB99 00669A BAND MOTOR SINYA 4 SA 18 DB31 00312A MOTOR SINYA SSR PID 1 SA 19 DB67 00565A BLOWER ASS Y ABS TORSIONAL BUSH 2 SA 20 DB90 01947A ASS Y CASE BLOWER UPPER ASS Y 2 SA 21 DB90 01948A ASS Y CASE BLOWER BOTTOM ASS Y 2 SA 22 DB94 01007B ASS Y DRAIN PAN ASS Y 1 SNA 23 DB93 05576F ASS Y CONTROL IN ASS Y 1 SA 23 1 DB90 01941...

Page 237: ...nd Parts List 5 25 Samsung Electronics 5 1 6 Duct type Slim II AVXDSH052 070C ND052 072LH 8 10 9 35 13 11 32 16 22 21 27 28 20 23 24 19 17 3 18 26 25 5 8 4 30 30 1 30 6 30 5 30 2 33 30 4 30 3 12 29 6 7 14 31 15 2 1 34 ...

Page 238: ...6 DB94 00809A ASS Y PARTITION SGCC M T1 0 1 1 SA 17 DB61 02282A BRACKET MOTOR SGCC M T2 0 1 1 SA 18 DB97 03800A BAND MOTOR SINYA 1 1 SA 19 DB31 00314C MOTOR SINYA 60Hz 1 1 SA 20 DB66 01007A MOTOR SHAFT SINYA 1 1 SNA 21 DB94 00759A MOLD BEARING ASS Y 1 1 SA 22 DB67 00581A CAP BEARING SGCC M T0 8 1 1 SNA 23 DB73 00285A RUBBER SHAFT CR V0 1 1 SNA 24 DB96 04902A COUPLER ASS Y 1 1 SA 25 DB67 00565A BLO...

Page 239: ...t 5 27 Samsung Electronics 5 1 7 Duct type Slim III AVXDSH100 110 145C ND100 110 145LH 8 10 9 33 13 11 32 16 22 21 27 28 20 23 24 19 17 3 18 26 25 5 8 4 30 30 1 30 4 30 7 30 6 30 2 30 3 30 5 30 9 30 8 12 29 6 7 34 14 31 15 2 1 35 ...

Page 240: ...1 SA 17 DB61 02331A BRACKET MOTOR SGCC M T2 5 1 1 SA 18 DB97 03751A BAND MOTOR SINYA 1 1 SA 19 DB31 00427A MOTOR SINYA SSR 1 1 SA 20 DB81 00617A MOTOR SHAFT SINYA 1 1 SA 21 DB94 00759A MOLD BEARING ASS Y 1 1 SA 22 DB67 00581A CAP BEARING SGCC M T0 8 1 1 SA 23 DB73 00285A RUBBER SHAFT CR V0 1 1 SA 24 DB96 04902A COUPLER ASS Y 1 1 SA 25 DB67 00583A BLOWER A ASS Y 1 1 SA 26 DB67 00583B BLOWER B ASS Y...

Page 241: ...s and Parts List 5 29 Samsung Electronics 5 1 8 Duct type MSP AVXDUH100 110C ND100 110SH 12 4 10 2 7 11 15 3 16 14 1 9 6 5 13 17 8 14 8 14 7 14 6 14 1 14 5 15 3 15 1 15 2 15 9 15 6 15 8 15 7 15 4 15 5 14 3 14 4 14 2 ...

Page 242: ...LOWER ASS Y 1 SNA 14 1 DB90 02402A ASS Y CABI FRONT ASS Y SGCC M T1 5 1 SNA 14 2 DB90 02408A ASS Y BRACKET OUTLET PART ASS Y SGCC M T1 0 1 SA 14 3 DB61 02331A BRACKET MOTOR ASS Y SGCC M T2 5 1 SNA 14 4 DB72 03751A BAND MOTOR ASS Y SGCC M T1 6 4 SA 14 5 DB61 02333A CASE FAN LOW ASS Y ABS GF10 T3 0 2 SA 14 6 DB61 02332A CASE FAN UP ASS Y ABS GF10 T3 0 2 SA 14 7 DB67 00583B BLOWER ASS Y ABS GF10 OD23...

Page 243: ...Parts List 5 31 Samsung Electronics Duct type MSP cont AVXDUH145C ND145SH 1 5 6 15 16 9 8 10 4 14 13 7 18 20 2 3 17 12 11 17 8 17 4 17 10 17 6 17 3 17 9 17 7 17 1 17 2 18 1 18 8 18 4 18 7 18 2 18 5 17 5 18 6 18 9 19 18 3 ...

Page 244: ...370A ASS Y BLOWER ASS Y 1 SNA 17 1 DB90 02028A ASS Y CABI FRONT ASS Y SGCC M T1 5 1 SNA 17 2 DB90 02013A ASS Y BRACKET OUTLET PART ASS Y SGCC M T1 0 1 SA 17 3 DB61 02372A BASE MOTOR ASS Y SGCC M T2 5 1 SNA 17 4 DB61 02375A BRACKET MOTOR ASS Y SGCC M T2 5 1 SNA 17 5 DB72 00710A BAND MOTOR ASS Y SGCC M T1 6 4 SA 17 6 DB61 00540B BRACKET MOTOR GUIDE ASS Y SGCC M T1 6 1 SNA 17 7 DB61 02382A CASE FAN L...

Page 245: ...ws and Parts List 5 33 Samsung Electronics 5 1 9 Duct type BiG ND HHXCA ND HHXCE 2 11 1 1 4 3 5 6 12 9 8 10 7 11 11 2 11 3 11 4 11 5 11 6 2 1 2 2 6 9 6 1 6 6 6 8 6 5 6 3 6 7 6 2 6 4 5 1 5 2 5 3 4 2 4 1 4 4 4 3 4 5 ...

Page 246: ...H SGCC 1 1 SNA 5 2 DB63 03007A COVER PIPE SGCC 1 1 SNA 5 3 DB61 04984A BRACKET CONTROL BASE SGCC 1 1 SNA 6 DB93 11723C ASS Y CONTROL IN 1 1 SNA 6 1 DB90 06715A ASS Y CASE CONTROL SGCC 1 1 SNA 6 2 DB63 03004A COVER CONTROL SGCC 1 1 SNA 6 3 DB26 00095A TRANS POWER 1 1 SA 6 4 DB61 00250A HOLDER WIRE 2 2 SNA 6 5 DB93 12676A ASS Y BLDC DRIVER 1 1 SA 6 6 DB93 12654A ASS Y PCB MAIN IN 1 1 SA 6 7 DB93 121...

Page 247: ...ectronics 9 17 12 11 15 10 13 14 16 5 4 8 7 3 6 1 2 13 1 13 3 13 2 2 5 2 4 2 1 2 2 2 6 2 3 1 1 1 14 1 13 1 5 1 7 1 6 1 8 1 4 1 10 1 9 1 11 1 12 1 15 1 9 1 2 1 3 1 2 5 1 10 Wall mounted type Vivace AVXWVH020 032 040 052 060C ND020 032 040 052 060VH ...

Page 248: ...E 4 4 SA 1 10 DB61 03139A SPRING ETC GRILLE STS 1 1 SA 1 11 DB63 01630A COVER DISPLAY ABS FR 17 1 1 SA 1 12 DB93 04452F ASS Y DISPLAY ASS Y 1 1 SA 1 13 DB61 02910A FRAME GRILLE ASS Y 1 1 SA 1 14 DB92 01052A WINDOW MIRROR ACRYL 1 SNA DB92 01052B WINDOW MIRROR ACRYL 1 SNA 1 15 DB61 03139B SPING ETC GRILLE STS 1 1 SA 2 DB94 01237A ASS Y TRAY DRAIN ASS Y 1 SA DB94 01245A ASS Y TRAY DRAIN ASS Y 1 SA 2 ...

Page 249: ...G SENSOR STS301 2 2 SNA 10 DB94 00455A ASS Y BEARING RUBBER ASS Y 1 1 SA 11 DB94 00456A ASS Y CROSS FAN ASS Y 1 SA DB94 00456B ASS Y CROSS FAN ASS Y 1 SA 12 DB31 00219A MOTOR FAN ASS Y 1 SA DB31 00267A MOTOR FAN ASS Y 1 SA 13 DB94 01152B ASS Y BODY BACK ASS Y 1 SA DB94 01153B ASS Y BODY BACK ASS Y 1 SA 13 1 DB61 03028A BODY BACK HIPS 1 SA DB61 03029A BODY BACK HIPS 1 SA 13 2 DB93 04230A ASS Y COMP...

Page 250: ...0 02 Samsung Electronics 5 38 ...

Page 251: ...ts List 5 39 Samsung Electronics 5 1 11 Wall mounted type Neo Forte without EEV AVXWNH020 032 040C ND020 032 040NH 1 6 1 2 1 9 1 1 2 2 5 2 3 7 1 3 1 4 1 6 9 4 7 2 1 2 5 1 5 4 5 3 8 1 7 1 8 5 3 3 4 3 6 3 8 1 5 3 1 3 2 3 5 3 3 ...

Page 252: ... 03060G ASS Y EVAP ASS Y 1 SNA 3 DB94 00457J ASS Y TRAY DRAIN ASS Y 1 SA 3 1 DB63 00848A TRAIN DRAIN ABS 1 SNA 3 2 DB61 01635C BRADE H HIPS 1 SA 3 3 DB61 01636A BLADE V PP 1 SA 3 4 DB63 00849A TRAY STABILIZER ABS 1 SNA 3 5 DB69 00839A CUSHION EPS TRAY RH EPS 3 SA 3 6 DB73 00180A RUBBER CAP DRAIN GUM EPM 3 SNA 3 7 DB31 00371A ASS Y MOTOR STEPPING 220 240V 50 60Hz Class E 1 SA 3 8 DB94 00458B ASS Y ...

Page 253: ...ts List 5 41 Samsung Electronics Wall mounted type Neo Forte without EEV cont AVXWNH056 060C ND056 060NH 1 6 1 2 1 1 16 2 4 2 3 2 2 2 5 3 7 10 11 13 4 9 7 2 1 2 5 1 5 5 5 2 5 3 8 14 15 5 4 5 3 3 4 3 6 3 8 12 3 1 3 2 3 5 3 3 ...

Page 254: ... 6 DB73 00180A RUBBER CAP DRAIN GUM EPM 1 SA 3 7 DB31 00285A ASS Y MOTOR STEPPING 220 240V 50 60Hz Class E 1 SNA 3 8 DB94 00458B ASS Y DRAIN HOSE ASS Y 1 SNA 4 DB93 06038F ASS Y CONTROL IN ASS Y 1 SA 5 DB92 01235A ASS Y PANEL FRONT ASS Y 1 SNA 5 1 DB64 01184C PANEL FRONT HIPS 1 SA 5 2 DB64 02045A ASS Y GRILLE AIR INLET ASS Y 1 SA 5 3 DB64 02046A DECORATON GRILLE PC GRAY 1 SNA 5 4 DB93 02867C ASS Y...

Page 255: ...Exploded Views and Parts List 5 43 Samsung Electronics 5 1 12 Wall mounted type Neo Forte with EEV ND020 032 040QHXC ...

Page 256: ...A RUBBER BUTYL BUTYL 1 SA 2 7 DB73 00570A RUBBER BUTYL BUTYL 1 SA 3 DB94 00457J ASS Y TRAY DRAIN ASS Y 1 SA 3 1 DB63 00848A TRAIN DRAIN ABS 1 SNA 3 2 DB61 01635C BRADE H HIPS 1 SA 3 3 DB61 01636A BLADE V PP 1 SA 3 4 DB63 00849A TRAY STABILIZER ABS 1 SNA 3 5 DB69 00839A CUSHION EPS TRAY RH EPS 3 SA 3 6 DB73 00180A RUBBER CAP DRAIN GUM EPM 3 SNA 3 7 DB31 00371A ASS Y MOTOR STEPPING 220 240V 50 60Hz ...

Page 257: ...Exploded Views and Parts List 5 45 Samsung Electronics Wall mounted type Neo Forte with EEV cont ND052 060QHXC ...

Page 258: ... DB61 01975C BRADE H HIPS 1 1 SA 3 3 DB61 01976A BLADE V PP 1 1 SA 3 4 DB63 01066A TRAY STABILIZER ABS 1 1 SNA 3 5 DB69 01024A CUSHION EPS TRAY RH EPS 1 1 SA 3 6 DB73 00180A RUBBER CAP DRAIN GUM EPM 1 1 SNA 3 7 DB31 00285A ASS Y MOTOR STEPPING 220 240V 50 60Hz Class E 1 1 SA 3 8 DB94 00458B ASS Y DRAIN HOSE ASS Y 1 1 SA 4 DB93 09504A ASS Y CONTROL IN ASS Y 1 1 SA 5 DB92 01235A ASS Y PANEL FRONT AS...

Page 259: ...t 5 47 Samsung Electronics 5 1 13 Ceiling type ND052 070CHXCA 14 7 43 37 29 4 23 18 6 41 40 36 34 32 1 38 19 20 16 24 42 13 15 39 30 26 28 27 3 25 46 33 44 1112 22 21 17 8 31 35 2 5 9 10 45 45 6 45 1 45 2 45 8 45 7 45 3 45 4 45 5 ...

Page 260: ...KET OUTLET ABS 1 1 SA 18 DB31 00158A BLADE V ABS 12 12 SA 19 DB31 00159A BLADE CONNECTOR V ABS 2 2 SA 20 DB31 00164A BLADE CONNECTOR H ABS 2 2 SA 21 DB31 00157A BLADE H ABS 1 1 SA 22 DB31 10113A SWING MOTOR IN ASS Y 1 1 SA 23 DB61 01352A BRACKET DRAIN SGCC M 1 1 SA 24 DB67 00258A DRAIN SUB LF SGCC M 1 1 SA 25 DB67 00259A DRAIN SUB RH ABS 1 1 SA 26 DB96 07272B EVAPORATOR ASS Y 1 1 SA 27 DB96 07656A...

Page 261: ...TROL ABS UL94 V0 1 1 SA 45 DB93 05193B ASS Y CONTROL IN ASS Y 1 SA DB93 05193A ASS Y CONTROL IN ASS Y 1 SA 45 1 DB61 01154A BASE CONTROL SGCC M 1 1 SA 45 2 DB61 01220A CASE PCB MAIN ABS UL94 V0 1 1 SA 45 3 DB93 05982C CEILING EU PCB ASS Y PCB 1 1 SA 45 4 DB65 00105M TERMINAL BLOCK 6P DAF S6P 1 1 SA 45 5 DB95 01101B TERMINAL BLOCK 6P DAF S6P 1 1 SA 45 6 DB26 00080A TRANS POWER ASS Y 1 1 SA 45 7 230...

Page 262: ...0 02 Samsung Electronics 5 50 ...

Page 263: ...5 51 Samsung Electronics 5 2 Outdoor Unit 5 2 1 RVXVHT075 100FE RD075 100VHXFA ...

Page 264: ...Exploded Views and Parts List Samsung Electronics 5 52 RVXVHT075 100FE RD075 100VHXFA cont ...

Page 265: ...BEAM LOW ASS Y 1 1 SNA 19 DB31 00298A FAN PROPELLER AS G F20 1 1 SA 20 DB31 00330B MOTOR FAN UGBTEF 13LSAM02 1 1 SA 21 DB95 01456H ASS Y COMP EVI FIXED ZPI61KCE TF5 496 1 1 SA 22 DB95 01468F ASS Y COMP EVI DIGITAL ZPJ72KCE TF5 496 1 1 SA 23 DB96 09442B ASS Y COND OUT A ASS Y 1 1 SA 24 DB96 12960A ASS Y TUBE HOT GAS BYPASS ASS Y 1 1 SA 25 DB96 08421A ASS Y TUBE DISCHARGE A ASS Y 1 1 SA 26 DB96 1241...

Page 266: ...AIN OUT ASS Y 1 SA DB93 08701B ASS Y PCB MAIN OUT ASS Y 1 SA 48 DB90 05282A ASS Y CASE CONTROL IN ASS Y 1 1 SNA 49 DB64 01311C CONTROL BOX BODY SGCC M t0 8 1 1 SNA 50 DB93 08105A ASS Y LEAD WIRE MAIN COMP ASS Y 1 1 SA 51 DB93 08105B ASS Y LEAD WIRE MAIN COMP ASS Y 1 1 SA 52 DB95 00766G ASS Y COMP HEATER ASS Y 1 1 SA 53 DB95 00766H ASS Y COMP HEATER ASS Y 1 1 SA 54 DB95 01425B ASS Y BELT HEATER ASS...

Page 267: ...Exploded Views and Parts List 5 55 Samsung Electronics 5 2 2 RVXVHT125FE RD125VHXFA ...

Page 268: ...Exploded Views and Parts List Samsung Electronics 5 56 RVXVHT125FE RD125VHXFA cont ...

Page 269: ...0 DB95 01456G ASS Y COMP EVI FIXED ZPI83KCE TF5 496 1 SA 21 DB95 01468G ASS Y COMP EVI DIGITAL ZPJ83KCE TF5 496 1 SA 22 DB90 04739A ASS Y BEAM FRONT LOW ASS Y 1 SA 23 DB96 09444B ASS Y COND OUT C ASS Y 1 SA 24 DB96 11587C ASS Y TUBE OIL BALANCE VALVE A ASS Y 1 SA 25 DB96 08687A ASS Y OIL SEPAPATOR 16HP ASS Y 1 SNA 26 DB96 12425A ASS Y TUBE 4WAY LIQUID SVC VV ASS Y 1 SNA 27 DB96 12312A ASS Y TUBE V...

Page 270: ...ASE CONTROL IN ASS Y 1 SNA 49 DB64 01311C CONTROL BOX BODY SGCC M T0 8 1 SNA 50 DB93 08105C ASS Y LEAD WIRE MAIN COMP ASS Y 1 SA 51 DB93 08105D ASS Y LEAD WIRE MAIN COMP ASS Y 1 SA 52 DB95 00766G ASS Y COMP HEATER ASS Y 1 SA 53 DB95 00766H ASS Y COMP HEATER ASS Y 1 SA 54 DB95 01425B ASS Y BELT HEATER ASS Y SA 55 DB95 01959G ASS Y DISCHARGE SENSOR ASS Y 1 SA 56 DB95 01965J ASS Y THERMISTOR OUTDOOR ...

Page 271: ...Exploded Views and Parts List 5 59 Samsung Electronics 5 2 3 RD075 100VRXFA 2 1 3 4 20 13 21 24 14 15 18 6 7 8 9 10 19 16 17 A 12 11 5 ...

Page 272: ...Views and Parts List Samsung Electronics 5 60 RD075 100VRXFA cont 52 51 50 49 45 38 44 46 43 39 41 42 40 48 47 57 56 55 54 53 58 59 60 61 A 36 29 37 33 27 30 22 21 31 26 28 32 4 32 3 35 1 35 25 32 2 32 1 32 5 32 ...

Page 273: ...SIDE LF ASS Y 1 1 SNA 19 DB90 04740A ASS Y FRONT BEAM LOW ASS Y 1 1 SNA 20 DB31 00298A FAN PROPELLER AS G F20 1 1 SA 21 DB31 00330B MOTOR FAN UGBTEF 13LSAM02 1 1 SA 22 DB95 01456H ASS Y COMP EVI FIXED ZPI61KCE TF5 496 1 1 SA 23 DB95 01468F ASS Y COMP EVI DIGITAL ZPJ72KCE TF5 496 1 1 SA 24 DB96 09442B ASS Y COND OUT A ASS Y 1 1 SA 25 DB96 14377A ASS Y TUBE HOT GAS BYPASS ASS Y 1 1 SA 26 DB96 14332A...

Page 274: ...ASS Y 1 1 SA 46 DB65 00232D TERMINAL BLOCK 3PHASE ASS Y 1 1 SNA 47 DB35 00096A RELAY XMC0 503IBBC00F 2 2 SA 48 DB93 08707A ASS Y PCB SUB ASS Y 1 1 SA 49 DB93 06543K ASS Y BLDC DRIVER ASS Y 1 1 SA 50 DB93 10733A ASS Y PCB MAIN OUT ASS Y 1 SA DB93 10733B ASS Y PCB MAIN OUT ASS Y 1 SA 51 DB90 05282A ASS Y CASE CONTROL IN ASS Y 1 1 SNA 52 DB64 01311C CONTROL BOX BODY SGCC M t0 8 1 1 SNA 53 DB93 08105A...

Page 275: ...Exploded Views and Parts List 5 63 Samsung Electronics 5 2 4 RD125VRXFA 2 3 4 19 20 24 13 14 11 18 6 23 7 8 9 10 12 16 17 15 A 1 5 ...

Page 276: ...Views and Parts List Samsung Electronics 5 64 RD125VRXFA cont 52 51 50 49 45 38 44 46 43 39 41 42 40 48 47 57 56 55 54 53 58 59 60 61 28 A 37 36 33 32 21 22 34 25 26 27 4 27 3 27 2 29 31 32 1 27 5 27 27 1 30 35 ...

Page 277: ...DB31 00330B MOTOR FAN UGBTEF 13LSAM02 1 SA 21 DB95 01456G ASS Y COMP EVI FIXED ZPI83KCE TF5 496 1 SA 22 DB95 01468G ASS Y COMP EVI DIGITAL ZPJ83KCE TF5 496 1 SA 23 DB90 04739A ASS Y BEAM FRONT LOW ASS Y 1 SA 24 DB96 09444B ASS Y COND OUT C ASS Y 1 SA 25 DB96 14374A ASS Y TUBE OIL BALANCE VALVE ASS Y 1 SA 26 DB96 14974A ASS Y OIL SEPAPATOR ASS Y 1 SA 27 DB96 14366A ASS Y TUBE 4WAY LIQUID SVC VV ASS...

Page 278: ...CK 3PHASE ASS Y 1 SNA 47 DB35 00096A RELAY XMC0 503IBBC00F 2 SA 48 DB93 08707A ASS Y PCB SUB ASS Y 1 SA 49 DB93 06543K ASS Y BLDC DRIVER ASS Y 1 SNA 50 DB93 10733C ASS Y PCB MAIN OUT ASS Y 1 SA 51 DB90 05282A ASS Y CASE CONTROL IN ASS Y 1 SNA 52 DB64 01311C CONTROL BOX BODY SGCC M T0 8 1 SNA 53 DB93 08105C ASS Y LEAD WIRE MAIN COMP ASS Y 1 SA 54 DB93 08105D ASS Y LEAD WIRE MAIN COMP ASS Y 1 SA 55 ...

Page 279: ...Exploded Views and Parts List 5 67 Samsung Electronics 5 2 5 RD040 050MHXCA ...

Page 280: ...DB67 00861A FAN PROPELLER AS GF20 460 3FAN 2 2 SA 19 DB90 04482A ASS Y BRACKET MOTOR SGCC M T2 0 1 1 SNA 20 DB63 02260A FELT TOP COVER A FELT PVC FELT 1 1 SNA 21 DB63 02259A FELT COMP SOUND A FELT PVC FELT 1 1 SNA 22 DB63 02280A COVER TERMINAL NORYL SE1 701 BLK 1 1 23 DB63 02281A GASKET 55F TBR EPDM RUBBER T0 8 1 1 24 DB63 02282A FELT TOP COVER B FELT PVC FELT 1 1 SNA 25 DB63 02283A FELT COMP SOUN...

Page 281: ...r CHK Out 4 Comp CHK Out 1 Comm Signal F1 2 Comm Signal F2 1 Comm Signal F3 2 Comm Signal F4 1 ROOMTemp Sensor 2 GND 3 EVA INTemp sensor 4 GND 1 GND 2 Float S W 1 On off Contact point input 2 GND 1 6 DC12V 2 5 Motor Control 7 10 Not used CN74 Ventilator CN74 Drain Pump CN73 Fan Motor CN71 AC Power CN44 RPM Feedback CN32 Remocon DC12V CN10 Micom Download CN91 Display CN60 Louver CN81 External Contr...

Page 282: ...iagram Samsung Electronics 6 2 Panel DC connecting connector 1 5 Control Display LED 6 Not used 7 Receive signals from wireless remote controller 8 GND 9 VCC DC5V CN01 Connect the Main PBA of the Indoor Unit ...

Page 283: ...5 Display Control Signal 7 Remote Sihnal Receive 8 GND 9 VCC DC5V 1 DV310V 2 N C 3 GND 4 DC15V 5 Motor Control Signal 6 Motor Feedback Signal 1 L Phase 2 N Phase 1 N Phase 2 Drain Pump Control 1 N Phase 2 Ventilator Control CN83 EXTANAL CONTROL CN51 FLOAT S W CN41 ROOM EVA IN CN42 EVA OUT TEMP SENSOR 16 17 CN62 EEV CN76 EXTERNAL OPTION CN60 LOUVER CN81 EXTERNAL CHECK CN33 Comm2 Wired Remote F3 F4 ...

Page 284: ...ND 2 Heater Discharge Output 1 5V input 2 GND 3 Hall IC output 1 Comm Signal F3 2 Comm Signal F4 1 Comm Signal F1 2 Comm Signal F2 1 DC12V 2 GND 1 5 LED Control 6 AUTO_S W 7 REMOCON_SIGNAL 8 GND 9 VCC 1 DC12V 2 FAN SSR OUT CN62 Electrically Operated Valve Control CN76 SUB PCB Connection CN60 Louver CN81 External Control Out 16 17 18 19 CN75 Ventilator CN74 Drain pump CN73 Fan Motor CN71 AC power C...

Page 285: ...PCB Diagram 6 5 Samsung Electronics 6 1 4 Duct type Slim MAIN PCB ...

Page 286: ...eiving signal 10 GND 11 DC5V 1 Comm Signal F1 2 Comm Signal F2 1 Comm Signal F3 2 Comm Signal F4 1 3 Trans OUtput connect 1 AC Power L 2 AC Power N 1 AC Power L 2 AC Power N None 1 DC12V 2 Fan Control Signal None 1 N phase 2 heated water coil signal 1 N phase 2 Drain signal 1 N phase 2 Ventilator signal CN43 CCH Temp sensor CN81 External CHECK CN32 Wire Remocon Power CN83 External Control CN51 Flo...

Page 287: ... type Slim cont SUB PCB 1 AC Power L 2 AC Power N 1 ROOMTemp Sensor 2 GND 3 EVA INTemp sensor 4 GND 1 DC310V 2 not used 3 GND 4 DC15V 5 Motor Control signal 6 Motor Feedback Signal CN71 AC Input CN35 MAIN PCB Connection CN72 FAN Motor output ...

Page 288: ...0 02 Samsung Electronics 6 8 ...

Page 289: ...PCB Diagram 6 9 Samsung Electronics 6 1 5 Duct type MSP MAIN PCB ...

Page 290: ...onnnection 1 L phase 3 N phase 1 AC power L 3 AC power N 1 N phase output 3 SSR Control signal L phase 5 N phase output 1 SSR Output 3 SSR Iuput 1 12V 3 Control Signal 1 N phase 2 heated water coil signal 1 N phase 2 Drain pump signal 1 N phase 2 Ventilator signal CN51 Float Switch CN41 Temp Sensor CN42 Temp Sensor CN43 Heater Discharge CN32 Wired Remocon Power CN83 External Control CN62 EEV CN91 ...

Page 291: ...PCB Diagram 6 11 Samsung Electronics 6 1 6 Duct type BIG MAIN PCB ...

Page 292: ...3 2 Comm Signal F4 1 3 Trans Output 1 AC Power L 2 AC Power N 1 AC Power L 2 AC Power N 1 DC12V 2 Error Check Signal 3 DC12V 4 Comp Check Signal 1 DC12V 3 Fan Control Signal 1 N phase 2 Drain Pump Signal 1 N Phase 2 Ventilator Signal CN32 Wired Remocon Power CN83 External Control CN62 EEV CN91 Display CN51 Floating Switch CN41 Room Eva In Temp Sensor CN42 Eva Out Temp Sensor CN43 Discharge Temp Se...

Page 293: ...PCB Diagram 6 13 Samsung Electronics Duct type BIG cont EMI PCB Power Output N Power Input L Power Input N Earth Power Output L ...

Page 294: ... DC12V 2 GND 3 DC5V 4 FAN Signal 5 FAN RPM 8 Inrush 1 AC Power L 2 AC Power N 1 AC Power L 2 AC Power N 1 3 5 U V W Feedback 2 DC5V 4 GND 6 MotorTemperature 7 GND 1 U 2 V 3 W CN13 Motor Control CN11 Main PCB Connection CN14 AC Power 10 AC Power CN12 Motor DC Connector ...

Page 295: ...PCB Diagram 6 15 Samsung Electronics 6 1 7 Wall mounted type Neo Forte without EEV MAIN PCB ...

Page 296: ... External Control Signal 16 Comp Check Signal 17 19 12V 18 Error Check Signal 1 Display Control 3 Operating switch 4 5V 5 Remocon Receiver signal 6 GND 1 4 EEV control Signal 5 12V 1 4 Electrically Operated Valve Signal 5 12V 1 12V 2 5 Auto Grille Control CN73 Fan Motor CN71 AC Power CN82 MPI Not Used CN60 Up Down Louver CN33 Communication 2 REMOCON CN32 Wired Remocon Power CN61 Option Setup Sub B...

Page 297: ...PCB Diagram 6 17 Samsung Electronics Wall mounted type Neo Forte without EEV cont SUB SWITCH No CN COLOR FUNCTION CN61 Black Main Sub PCB Connecor CN83 White External Contact Control 15 16 ...

Page 298: ...0 02 Samsung Electronics 6 18 ...

Page 299: ...PCB Diagram 6 19 Samsung Electronics 6 1 8 Wall mounted type Neo Forte with EEV MAIN ...

Page 300: ...l 17 19 12V 18 Error Check Signal 1 DC12V 2 5 Louver Control Signal 1 L Phase 3 N Phase 1 2 14 15 DISPLAY Signal 3 Operation S W 4 DC5V 5 Wireless Remocon Signal 6 GND 1 Start Capacitor 3 Motor Control 5 N Phase 1 4 EEV Control 5 6 DC12V CN42 Temp Sensor CN41 Temp Sensor CN44 RPM Feedback CN31 Outdoor Comm CN71 AC Power CN33 Wired Remocon Comm CN32 Wired Remocon DC Power CN61 Connect to SUB CN62 E...

Page 301: ...amsung Electronics Wall mounted type Neo Forte with EEV cont SUB SWITCH 1 On Off Contact Switch Input 2 GND 16 1 3 DC12V 2 Error Check Out 4 Comp Check Out CN83 External Control CN61 Connect to Main CN42 External Control ...

Page 302: ...0 02 Samsung Electronics 6 22 ...

Page 303: ...PCB Diagram 6 23 Samsung Electronics 6 1 9 Wall mounted type Vivace MAIN PCB ...

Page 304: ...on Switch Address Signal 11 14 GND 15 External Control Signal 16 Comp Check Signal 17 19 12V 18 Error Check Signal 1 Not Used 2 12 Display Control 13 Operating Switch 14 5V 15 Remocon Receiver Signal 16 GND 1 4 EEV Control Signal 5 12V 1 12V 2 5 Auto Grille Control CN73 Fan Motor CN71 AC Power CN82 MPI CN60 Up Down Louver CN33 Wired Remocon Comm CN32 Wired Remocon Power CN61 Option Setup Sub Board...

Page 305: ...PCB Diagram 6 25 Samsung Electronics Wall mounted type Vivace cont SUB SWITCH No CN COLOR FUNCTION CN61 Black Main Sub PCB Connecor CN83 White External Contact Control 15 16 ...

Page 306: ...THEMISTOR 2 GND 1 ROOMTemp Sensor 2 GND 3 EVA INTemp sensor 4 GND 1 On off Contact point input 2 GND 1 GND 2 Float S W 1 DC12V 2 5 LOUVER control 1 DC12V 2 3 GND 1 N 2 L 1 EEV 2 DC12V CN32 Remocon DC12V CN31 Indoor Outdoor Unit Communication CN33 Wired Remocon Communication CN91 Display CN71 AC Power CN74 Drain Pump CN75 Ventilator CN73 Fan Motor CN81 External Control OUT CN42 Temp Sensor CN41 Tem...

Page 307: ... R438 YEL R439 BLU BLK BLU WHT C401 WHT C402 WHT C403 WHT C404 BLU C405 RED C212 C409 WHT C601 WHT C602 C603 R833 YEL C604 BLK C605 C411 BLU C606 C412 YEL C607 C413 BLK R450 0 1 2 3 4 5 6 7 8 9 C221 C222 C417 C418 C419 RED LED05 RED LED06 WHT WHT LED07 LED08 C420 C812 C813 C814 C815 C816 C817 C818 BLK 0 1 2 3 4 5 6 7 8 9 C819 0 1 2 3 4 5 6 7 8 9 A B C D E F C820 C821 C825 LED101 PC02 LED102 PC03 L...

Page 308: ...8 GND 1 2 3 4 Control signal 5 12V 1 2 3 4 Control signal 5 6 12V 1 2 3 4 Control signal 5 12V 1 2 3 4 Control Signal 5 6 12V 1 12V 2 5V 3 GND 4 IPM Fault Error Signal 5 BLDC Fan Motor Control Signal 6 Inrush Relay Signal 7 OverVoltage Error Signal 8 Motor Overheating Error signal 9 Fan Motor counter rotation Error Signal 10 Fan RPM Error Signal 11 12 13 Not used CN901 TRANS OUTPUT CN13 Relay Comm...

Page 309: ...OUT FAN RPM HU 5V HV GND HW GND BLDC DRIVER DVMPLUS3 M TEMP 7805 7808 AC220 240V HIGH VOLTAGE CAUTION Y GRN Y GRN RED 2 GT2 C602 C603 C606 C805 C611 C613 R605_FUSIBLE PC501 PC502 PC503 PC504 PC505 PC506 IC603 7 CN101 R702 R703 5 CN301 13 CN501 3 CN701 3 CN703 PTC1 PTC2 C312 XT801 C301 IC602 C302 C102 C303 C604 C505 C307 C309 BD701 RY701 R310 21 27 20 1 IC301 L601 D603 C701 C702 R401 R402 R403 R404...

Page 310: ...LUS2 POWER IN DB41 00482A X701 VA701 R701 L701 DS701 3 1 CN701 X702 VA702 R702 L702 CN702 X703 VA703 L N Y703 Y704 Y702 Y701 F701 WHT BLU L L phase input N N phase input Earth Connection 1 AC 220V L 3 AC 220V N CN701 Power input AC220V CN702 Earth CN701 Power output 220V 44 45 46 ...

Page 311: ...B Diagram 6 31 Samsung Electronics CT PCB CN61 Current sensor output value 1 COMP 1 CurrentValue Output 2 COMP 2 CurrentValue Output 3 COMP 3 CurrentValue Output 4 GND 4 0 6 0 53 2 2 2 2 2 2 4 4 4 2 2 47 ...

Page 312: ...PCB Diagram Samsung Electronics 6 32 CT PCB CN61 Current sensor output value 1 COMP 1 CurrentValue Output 2 COMP 2 CurrentValue Output 3 COMP 3 CurrentValue Output 4 GND 47 ...

Page 313: ...rol Signal CN85 External Test Signal K4 Operation data display 5 12V Voltage CN86 External Contact Signal 9 CN81 Main Inverter board communication 10 CN37 Programmer 11 CN75 4 Way Valve 12 CN74 Thermal Valve 1 Signal Input 2 Signal Output 3 GND 4 DC 5V 5 DC 12V 6 Inverter board DC control 7 Not used 13 CN81 Electric Expansion Valve 14 CN42 High Pressure Sensor 15 CN32 Main Communication board conn...

Page 314: ...ation 3 CN41 CN42 DC Fan 4 CN22 DC Contact Control 1 DC Voltage 310V 1 2 Main Inverter Board Communication Signal 2 Not Used 3 Feedback Signal 3 GND 4 DC 16V 4 DC 5V 5 GND 6 Revolution Control Signal 5 CN71 Main Inverter Board Communication 1 DC 12V 2 Inverter Board DC Control 3 Not Used INVERTER PCB ...

Page 315: ...PCB Diagram 6 35 Samsung Electronics ᐭ ᐮ ᐯ ᐰ ᐱ EMI PCB 1 CN01 Main Power 2 N1 N Phase Output 3 L1 L Phase Output 4 N N Phase Input 1 L Phase 2 N Phase 5 L L Phase Input ...

Page 316: ...PCB Diagram Samsung Electronics 6 36 COMMUNICATION PCB 1 CN31 Communication 2 CN13L 5V Output 1 F1 Signal 1 DC 5V 2 F2 Signal 2 GND ᐭ ᐮ ...

Page 317: ...gram 7 1 Indoor 7 1 1 Slim 1way cassette type This Document can not be used without Samsung s authorization Fan Motor Part Drain Pump Part Display Part Indoor Eva In Eva Out Sensor Part Float S W Part EEV Control Part Rouver Control Part ...

Page 318: ...tronics 7 2 7 1 2 4 way cassette type This Document can not be used without Samsung s authorization Indoor Eva In Eva Out Sensor Part Display Part Rouver Control Part Fan Motor Part Float S W Part EEV Control Part Drain Pump Part ...

Page 319: ...ectronics 7 1 3 Mini 4way cassette type This Document can not be used without Samsung s authorization Indoor Eva In Eva Out Sensor Part Display Part Rouver Control Part Fan Motor Part Float S W Part Drain Pump Part EEV Control Part ...

Page 320: ...onics 7 4 7 1 4 Duct type Slim I II AVXDSH020 032 040 052 072C ND020 032 040 052 060 072LH This Document can not be used without Samsung s authorization Indoor Eva In Eva Out Sensor Part Display Part Fan Motor Part EEV Control Part ...

Page 321: ...Samsung Electronics 7 1 5 Duct type Slim III AVXDSH100 110 145C ND100 110 145LH This Document can not be used without Samsung s authorization Indoor Eva In Eva Out Sensor Part Display Part Fan Motor Part EEV Control Part ...

Page 322: ...Wiring Diagram Samsung Electronics 7 6 7 1 6 Duct type MSP Indoor Eva In Eva Out Sensor Part Display Part Fan Motor Part EEV Control Part This Document can not be used without Samsung s authorization ...

Page 323: ...ram 7 7 Samsung Electronics 7 1 7 Duct type BIG Motor Part Main PBA EEV Control Part Sensor Part Sensor Part BLDC PBA Motor Control EMI PBA Power Input This Document can not be used without Samsung s authorization ...

Page 324: ...tronics 7 8 7 1 8 Wall Mounted type Vivace Display Part This Document can not be used without Samsung s authorization Indoor Eva In Eva Out Sensor Part Fan Motor Part Rouver Control Part Auto Grille Part MPI Part EEV Control Part ...

Page 325: ...m 7 9 Samsung Electronics 7 1 9 Wall Mounted type Neo Forte without EEV Display Part This Document can not be used without Samsung s authorization Indoor Eva In Eva Out Sensor Part Fan Motor Part Rouver Control Part ...

Page 326: ...g Electronics 7 10 7 1 10 Wall Mounted type Neo Forte with EEV Display Part This Document can not be used without Samsung s authorization Indoor Eva In Eva Out Sensor Part Fan Motor Part Rouver Control Part EEV Control Part ...

Page 327: ...Wiring Diagram 7 11 Samsung Electronics 7 1 11 Distributor kit This Document can not be used without Samsung s authorization C Room EEV Control Part B Room EEV Control Part A Room EEV Control Part ...

Page 328: ...Samsung Electronics 7 12 7 1 12 Ceiling Indoor Eva In Eva Out Sensor Part Display Part Fan Motor Part EEV Control Part This Document can not be used without Samsung s authorization Rouver Control Part ...

Page 329: ...door Unit Motor RPM Part 3Phase Input EEV Control Part Temp Sensor Part Valves Parts Valves Parts Comp Part CCH Part BLDC Motor Part This Document can not be used without Samsung s authorization RVXVHT075 100 125FE RD075 100 125VHXFA ...

Page 330: ...g Electronics 7 14 Motor RPM Part 3Phase Input EEV Control Part Temp Sensor Part Valves Parts Valves Parts Comp Part CCH Part BLDC Motor Part This Document can not be used without Samsung s authorization RD075 100 125VRXFA ...

Page 331: ...agram 7 15 Samsung Electronics Pressure Sensor Part EEV Control Part Comp Part Motor Control Part This Document can not be used without Samsung s authorization Temp Sensor Part Valve Control Part RD040 050MHXCA ...

Page 332: ...0 02 Samsung Electronics 7 16 ...

Page 333: ...EEV Circuit Part External Contact Point Control Part Louver Drive Part Slide Panel Drive Part Display Receiving Part Main Adress Setting Switch RMC Adress Setting Switch 485 Comm Part COM1 8 Schematic Diagram 8 1 Indoor Unit 8 1 1 Slim 1 way cassette type MAIN 8 1 This Document can not be used without Samsung s authorization Samsung Electronics ...

Page 334: ...ontrol Part Temperature Sensor Part 485 Communication Part EEV SUB PCB Part External Control Part Louver Control Part Display PCB Part Address Option Switch Set Part 8 1 2 4 way cassette type 8 2 This Document can not be used without Samsung s authorization Samsung Electronics ...

Page 335: ...ssette type This Document can not be used without Samsung s authorization SMPS Part Zero Crossing Part Motor Control Part Temperature Sensor Part Communication Part EEV Control Part External Control Part Louver Control Part Display Control Part Address Setting Switch Part 8 3 ...

Page 336: ...Document can not be used without Samsung s authorization Samsung Electronics SMPS Part Zero Crossing Part Motor Control Part Temperature Sensor Part Communication Part EEV Control Part External Control Part Display Control Part Address Setting Switch Part 8 4 ...

Page 337: ...1 5 Duct type BIG MAIN SMPS Part Zero Crossing Part Motor Control Part Temperature Sensor Part Communication Part EEV Control Part External Control Part Display Control Part Address Setting Switch Part This Document can not be used without Samsung s authorization ...

Page 338: ... 2 1 R107 3 9K F 0 1W 2 1 AGND AGND 15VDC IC901 FNA41560 17 25 24 23 14 18 19 15 26 22 16 20 13 4 21 9 8 10 11 12 5 6 7 1 2 3 P RTH VTH NU W V IN WL VFO CSC NV NW VS W U IN VL IN UH VCC L VB W VB U COM IN VH IN WH IN UL VS V VB V VS U VCC H 15VDC 0 2W DTA114EKA Q903 2 1 3 O I G PDC310V 0 1W F 3 9K R108 2 1 630V 10nF C101 2 1 KA7805A IC102 2 3 1 IN OUT GND IPM_TH_OUT 0 2W DTA114EKA Q904 2 1 3 O I G...

Page 339: ... Samsung Electronics This Document can not be used without Samsung s authorization SMPS Part Zero Crossing Part Motor Control Part MPI Part Temperature Sensor Part Communication Part EEV Control Part Cross wire checking Part Buzzer Part EEPROM Melody Part Louver control Part Display Control Part 8 7 ...

Page 340: ...ung s authorization 8 1 7 Wall mounted type Neo Forte with EEV Power Supply Part Zero Crossing Detect Part Buzzer Control Part Display Part EEPROM Part Address External Control MICOM Part EEV Control Part Communication Part Cross Wire Check Part Temperature Sensor Part Fan Control Part MICOM Reset Part ...

Page 341: ... type This Document can not be used without Samsung s authorization 8 9 SMPS Part Zero Crossing Part Motor Control Part Temperature Sensor Part Communication Part EEV Control Part External Control Part Louver Control Part Display Control Part Address Setting Switch Part ...

Page 342: ...IN PCB 1 Samsung Electronics Outdoor Load Part Communication Circuit Part 3Phase Check Part Reset Circuit Part Zero Crossing Part Display Circuit Part Switch Circuit Part Sensor Circuit Part Micom Download Circuit Part This Document can not be used without Samsung s authorization 8 10 ...

Page 343: ...Schematic Diagram Schematic Diagram MAIN PCB 2 Samsung Electronics Power Circuit Part Sensor Circuit Part Current Sensor Input Part This Document can not be used without Samsung s authorization 8 11 ...

Page 344: ...without Samsung s authorization BLCD PCB Samsung Electronics Power Input Part Hall Sensing Input Part Motor Over Temp Protection Part Inverter IPM Part Inverter Controller Part Inverter Controller Power Part Inverter Over Current Sensor Part Signal Transfer Part 8 12 ...

Page 345: ...Schematic Diagram 8 13 Samsung Electronics Filter PCB This Document can not be used without Samsung s authorization ...

Page 346: ...Schematic Diagram Samsung Electronics 8 14 CT PCB This Document can not be used without Samsung s authorization ...

Page 347: ...䗮ֵ䚼ߚ Џ㢃 ݭ 䚼ߚ Ӵᛳ 䚼ߚ SMPS Part Zero crossing detected Part EEPROM Part Option selection Part Mode shift control Part LED display Part Main chip Part External control display Part Main inverter communication Part Main chip program Part Sensor Part 8 15 Samsung Electronics This Document can not be used without Samsung s authorization ...

Page 348: ...matic Diagram Schematic Diagram MAIN PCB 2 䋳䕑䚼ߚ ϝⳌẔ 䚼 9 ࠊ䚼 AC load Part Three phase inspection Part EEV controller Part 8 16 Samsung Electronics This Document can not be used without Samsung s authorization ...

Page 349: ...unication Part Electric control Part Inverter chip Part Inverter program Part Power filter Part PFC control Part Inverter control Part Compressor current test Part Comparisons of compressor phase currents Part 8 17 Samsung Electronics This Document can not be used without Samsung s authorization ...

Page 350: ...Schematic Diagram Schematic Diagram EMI PCB 8 18 Samsung Electronics This Document can not be used without Samsung s authorization ...

Page 351: ...Schematic Diagram Schematic Diagram COMMUNICATION PCB 8 19 Samsung Electronics This Document can not be used without Samsung s authorization ...

Page 352: ...Export Capa x1 10kW Notation Cooilng Heating 020 2 0 2 3 040 4 0 4 5 052 5 2 6 0 072 7 2 8 1 100 10 0 11 0 110 11 1 12 8 145 14 5 16 3 Products Indoor Cassette C Duct D RAC W Mode C O C H P H H P Heater E C O Heater G C O HotWater Heater N Design Indoor Cassette 4 way 4 Mini 4 way M Duct Slim S Mid pressure U RAC Neo Forte N Vivace V RagingVoltage 208 230V 60Hz C ...

Page 353: ... U Hydro Unit HYDRO W Water tank Refrigerant R R22 Value S R22 Tender X R410A STD Y R410A DLX W R410A PRM Z R410A Flagship Mode C C O H H P RagingVoltage A 115V 60Hz B 220V 60Hz C 208 230V 60Hz D 200 220V 50Hz E 220 240V 50Hz F 208 230V 60Hz 3phasea G 380 415V 50Hz 3phasea M 127V 50Hz H 380V 60Hz 3phasea J 460V 60Hz 3phasea Version A Z Export S Solar Water Tank Z High efficiency EER mode indoor un...

Page 354: ...ification Outdoor Unit R410A RVX Type Mini DVM M DVM PLUS III DVM PLUS III HR V Mode Heat Pump H Heat recovery R Airflow direction Upward airflows T Frontward airflow F Version Export A Z Capacity x1 10HP 3 Digits Rating voltage 3Ø 380 415V 50Hz G 3Ø 208 230V 60Hz F 1Ø 220 240V 50Hz E V T RVX H 075 F E ...

Page 355: ...Non Module TOP Inverter C Module S SLIM G GHP M MINI J HOME D WDVM E GEO P ECO Heating Refrigerant R R22 X R410A Mode C C O H H P R H R T TROPICAL C O Q TROPICAL H P RagingVoltage A 115V 60Hz B 220V 60Hz C 208 230V 60Hz D 200 220V 50Hz E 220 240V 50Hz F 208 230V 60Hz 3phasea G 380 415V 50Hz 3phasea M 127V 50Hz H 380V 60Hz 3phasea J 460V 60Hz 3phasea Version A Z Export MCD Dummy Mockup madel RD H 1...

Page 356: ...e Heater 30 e Oil solenoid valve 1 31 f Oil solenoid valve 2 32 g Oil solenoid valve 3 33 h Oil balancing service valve between units 34 i Low pressure sensor No Classification Description 35 j Check valve 36 k Crank case heater of DVI compressor 37 m Crank case heater of FVI compressor 1 38 n Crank case heater of FVI compressor 2 39 o Sump Base temperature sensor 40 p Oil temperature sensor 41 q ...

Page 357: ...id Pilot solenoid valve Expansion Electronic Expansion Valve EEV Reversing Reversing valve 4 way valve Check Check valve Service Service valve Angle ball type 3 Switch Heater Pressure Switch High pressure switch Mechanical type Heater Electric heater 4 Others Compressor DVI Digital Vapor Injection Compressor FVI Fixed Vapor Injection Compressor Accumulator Accumulator Heat Exchanger Condensing or ...

Page 358: ...Reference Sheet 9 7 Samsung Electronics Cycle Operation Mode cont RVXVHT075 100 125FE RD075 100 125VHXFA cont RVXVHT075 100FE RD075 100VHXFA DVM PLUS 7 5 10HP 0 1 3 4 5 6 7 8 9 B C F E K L N V W Y Z T D ...

Page 359: ...Reference Sheet Samsung Electronics 9 8 Cycle Operation Mode cont RVXVHT075 100 125FE RD075 100 125VHXFA cont RVXVHT125FE RD125VHXFA DVM PLUS 12 5HP 0 1 3 4 5 6 7 8 9 B C F E K L N V W Y Z T D ...

Page 360: ...eference Sheet 9 9 Samsung Electronics Cycle Operation Mode cont RD075 100VRXFA RD075 100VRXFA DVM PLUS HR 7 5 10HP 9 9 9 3 6 36 9 3 0 9 9 9 7 7 7 7 7 3 3 3 7 7 7 9 3 7 9 6 7 9 9 9 9 9 9 69 69 69 69 2 6 ...

Page 361: ...Reference Sheet Samsung Electronics 9 10 Cycle Operation Mode cont RD125VRXFA RD125VRXFA DVM PLUS HR 125HP 9 69 69 9 9 69 69 3 6 36 9 3 0 9 9 9 7 7 7 7 7 3 3 3 7 7 7 9 3 7 9 7 6 9 9 9 9 9 9 2 6 ...

Page 362: ...60FUAEK G5T450FUCEX C Low Pressure 5 8 5 8 IFDL 7 7 w PNQSFTTPS 0JM 4FQBSBUPS PVCMF QJQF IFBU FYDIBOHFS 8BZ 7 7 4 1 JHI 1SFTT 4FOTPS PU HBT CZQBTT 7 7 PUPS PUPS ƫ ƫ 5BJS 5DPVU 5EJT JMUFS JMUFS JMUFS 7 ƫ 5TD 5PQ 4 7 w 7 1 0 i w ᎎ w w w w DDVNVMBUPS ᎎ i w i w 3FGSJHFSBOU nPX JO PPMJOH ƫ 9 JHI 1SFTT 4XJUDI Cycle Operation Mode cont 9 2 1 2 RD040 050MHXCA ...

Page 363: ...ronics Co Ltd Jul 2011 Printed in Korea Code No DB98 31205A 5 GSPN Global Service Partner Network Area Web Site North America http service samsungportal com Latin America http latin samsungportal com CIS http cis samsungportal com Europe http europe samsungportal com China http china samsungportal com Asia http asia samsungportal com Mideast Africa http mea samsungportal com ...

Reviews: