Operating Instructions and Installation
3-11
Samsung Electronics
3-2-2(h) Refrigerant Refill
• Refill an air-conditioner with refrigerant when refrigerant has been leaked at installing or using
1. Purge air(for new installation only).
3. Connect the tank to refill with Refrigerant
4. Set the unit to cool operation mode.
7. Stop operation of the air conditioner.
9. Close the cap of each valve.
2. Turn the 3-way valve clockwise to close,
connect the pressure gauge(low
pressure side) to the service valve, and
open the 3-way valve again.
5. Check the pressure indicated by the
pressure gauge(low pressure side).
* Standard pressure is should be
4.5~5.5kg/cm
2
in a reqular, high operation
mode.
6. Open the refrigerant tank and fill with refrig-
erant until the rated pressure is reached.
* It is recommended not to pour the
refrigerant in too quickly, but gradually
while operating a pressure valve.
8. Close the 3-way valve, disconnect the
pressure gauge, and open the 3-way
valve again.
Suspension hook
High
pressure
gauge
Hand
wheel
Finger tight
fittings
Connected to
high pressure
side
Charging
line
For mounting
other and of
hose when
not in use
Compound
gauge
Summary of Contents for ASH070VE/D
Page 2: ...Samsung Electronics Co Ltd FEB 1997 Printed in Korea Code No DB81 10122A 1...
Page 4: ...1 2 Samsung Electronics MEMO...
Page 27: ...Samsung Electronics 3 14 MEMO...
Page 42: ...Samsung Electronics 6 1 6 Exploded Views and Parts List 6 1 Indoor Unit...
Page 44: ...Samsung Electronics 6 3 6 2 Outdoor Unit 24 1 24 25 25 2 25 1 25 3 25 4 25 5 18 18 1 19...
Page 48: ...6 7 Samsung Electronics MEMO...
Page 50: ...Samsung Electronics 8 1 8 PCB Diagrams 8 1 a Main PCB 7000Btu DB93 10483A...
Page 52: ...Samsung Electronics 8 3 8 1 b Main PCB 9000 12000Btu 12000BUT DB93 10471A 9000BUT DB93 10485A...
Page 55: ...Samsung Electronics 9 1 9 Wiring Diagrams 9 1 Indoor Unit...
Page 57: ...Samsung Electronics MEMO...
Page 58: ...Samsung Electronics MEMO...
Page 59: ...10 1 10 Schematic Diagrams 10 1 Indoor Unit Samsung Electronics...