
17
English
Installation
Step 2.8 Installing and connecting
the assembly pipes to the refrigerant
pipes (assembly pipe)
Connect indoor and outdoor units with field-supplied
copper pipes by means of flare connections. Use
insulated seamless refrigeration grade pipe only,
(Cu DHP type according to ISO1337), degreased and
deoxidized, suitable for operating pressures of at
least 4200 kPa and for burst pressure of at least
20700 kPa. Under no circumstances must sanitary
type copper pipe be used.
There are 2 refrigerant pipes of different diameters:
•
The smaller one is for the liquid refrigerant
•
The larger one is for the gas refrigerant
A short liquid refrigerant pipe and a short gas
refrigerant pipe are already fitted to the air
conditioner. The connection procedure for the
refrigerant pipes varies according to the exit position
of each pipe when facing the wall:
1 <Front view>
3 <Side view>
Left(A)
Underside(C)
Right(B)
Guide right
or left
2 <Assembling the
hanger screw>
Screw
1
Cut out the appropriate knock-out piece (A, B, C)
on the rear of the indoor unit unless you connect
the pipe directly from the rear.
2
Smooth the cut edges.
3
Remove the protection caps of the pipes and
connect the assembly pipe to each pipe. Tighten
the nuts first with your hands, and then with a
torque wrench, applying the following torque:
Outer diameter (mm)
Torque (N•m) Torque (kgf•cm)
ø 6.35
14 to 18
140 to 180
ø 9.52
34 to 42
350 to 430
ø 12.70
49 to 61
500 to 620
ø 15.88
68 to 82
690 to 830
NOTE
•
If you want to shorten or extend the pipes,
see Step 2.9 Shortening or extending the
refrigerant pipes (assembly pipe) on page 18.
•
Tighten the nuts to the specified torques. If
overtightened, the nuts could be broken so
refrigerant may leak.
4
Cut off the remaining foam insulation.
5
If necessary, bend the pipe to fit along the bottom
of the indoor unit. Then pull it out through the
appropriate hole.
•
The pipe should not project from the rear of the
indoor unit.
•
The bending radius should be 100 mm or more.
6
Pass the pipe through the hole in the wall.
7
Fix the indoor unit on the wall.Pass the cables,
pipes and hose through the knock-out hole which
would be connected to the outdoor unit .
8
Use 2 screws to fix the indoor unit as shown in the
picture 2.
9
Assemble the Guide into the position of A or B as
shown in the picture 3.
NOTE
•
The pipe will be insulated and fixed permanently
into position after finishing the installation and
the gas leak test. For further details. see Step 4.1
Performing the gas leak tests on page 25.
CAUTION
•
Tighten the flare nut with a torque wrench
according to specified method. If the flare nut is
over-tightened, the flare may break and cause
refrigerant gas leakage.
•
Do not box in or cover the pipe connection.
All refrigerant pipe connection must be easily
accessible and serviceable.
Summary of Contents for AR**MXWS Series
Page 30: ...DB68 06730A 03...