Samsung AQV09K Series User & Installation Manual Download Page 36

36

Installing and connecting the drain hose of the outdoor unit

While heating, ice may accumulate. During the process of defrosting, check if condensation draining is adequate.  For adequate 

draining, do the following.

The outdoor unit is loaded with sufficient R410A refrigerant.  Do not vent R410A into atmosphere: it is a fluorinated 

greenhouse gas,  covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 1975. 
You should purge the air in the indoor unit and in the pipe. If air remains in the refrigerant pipes, it affects the compressor.  

It may cause reduction of cooling capacity and malfunction. Refrigerant for air purging is not charged in the outdoor unit. 

Use Vacuum Pump as seen in the picture. 

1.  Insert the drain plug into the drain hole on the underside of the outdoor unit.

1.  Connect each assembly pipe to the appropriate valve on the outdoor unit and 

tighten the flare nut.

2.  Tighten the flare nut first with your hands, and then with a torque wrench, 

applying the following torque.

2.  Connect a drain hose to the drain plug.

3.  Ensure that condensation draining is adequate.

Frame

Ground

Estimated 

snow fall

Snow-proof hood

Bottom surface of outdoor unit

Drain hose

Drain hole

Drain plug

Drain hole

Drain plug

•   To avoid drain plug from contacting the ground, secure gap between the 

ground and the bottom surface of the outdoor unit.

•   In areas with heavy snow fall, piled snow could block the air intake. 

 

To avoid this incident, install a frame that is higher than estimated snow 

fall. In addition, install a snow-proof hood to avoid snow from piling on the 

outdoor unit.

•   When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first 

before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works 

with the service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle 

abnormally high. It may cause explosion and injury.

Purging the connected pipes

Outdoor unit

Indoor unit

Gas pipe side

Liquid pipe side

Outer Diameter Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

•  Excessive torque can be cause of gas leakage.

•   Make the electrical connection and leave the system into “stand by 

mode”. Do not turn on the system!

 

This is necessary for better vacuum operation (full OPEN position of 

Electronic Expansion Valve - EEV -).

If using a multi system, refer to the manual supplied with the outdoor unit.

AQV09K&Y@@_Jungfrau_IBIM_E_32448A.indd   36

2011-3-19   15:45:54

Summary of Contents for AQV09K Series

Page 1: ...AQV09K Y _Jungfrau_IBIM_E_32448A indd 1 2011 3 19 15 44 33 ...

Page 2: ...Purging the indoor unit 33 Cutting or extending the pipe 33 Installing and connecting the drain hose of the indoor unit 34 Changing direction of the drain hose 35 Installing and connecting the drain hose of the outdoor unit 36 Purging the connected pipes 36 Performing the gas leak tests 39 Fixing the indoor unit in place 40 Fixing the outdoor unit in place 40 Final check and trial operation 41 Pum...

Page 3: ...he electric part of the outdoor unit is not exposed Failing to do so may result in electric shock or fire Do not install this appliance near a heater inflammable material Do not install this appliance in a humid oily or dusty location in a location exposed to direct sunlight and water rain drops Do not install this appliance in a location where gas may leak This may result in electric shock or fir...

Page 4: ...f a gas leak such as propane gas LP gas etc ventilate immediately without touching the power plug Do not touch the appliance or power cord Do not use a ventilating fan A spark may result in an explosion or fire To reinstall the air conditioner please contact your nearest service center Failing to do so may result in problems with the product water leakage electric shock or fire A delivery service ...

Page 5: ... shock fire or problems with the product Do not drink the water from the air conditioner The water may be harmful to humans Do not apply a strong impact to the remote controller and do not disassemble the remote controller Do not touch the pipes connected with the product This may result in burns or injury Do not use this air conditioner to preserve precision equipment food animals plants or cosme...

Page 6: ...ery when the air conditioner operates in Cool mode Protect compressor The air conditioner does not start operating immediately to protect the compressor of the outdoor unit after it has been started If the heat pump is operating in Heat mode De ice cycle is actuated to remove frost from an outdoor unit that may have deposited at low temperatures The internal fan is switched off automatically and r...

Page 7: ...rom illustration shown above depending on your model Checking the name of the parts Air flow blade up and down Air flow blade left and right SPi indicator Full HD filter under the panel Air intake Full HD filter under the panel Humidity sensor Air intake Room temperature sensor indicator AQV09K Y _Jungfrau_IBIM_E_32448A indd 7 2011 3 19 15 44 44 ...

Page 8: ... flows through the air conditioner with the 4 different fan speeds such as Auto Low Medium High Set the mode on Set Cancel Cancel the timer mode 2nd F Switch the function of the button on the remote controller Air swing Activate Deactivate air flow blade movement automatically up and down Mode Set one of the 5 operating modes see pages 10 11 for instructions Quiet Reduce noise generated from an in...

Page 9: ...sposal of batteries in this product Applicable in the European Union and other European countries with separate battery return systems This marking on the battery manual or packaging indicates that the batteries in this product should not be disposed of with other household waste at the end of their working life Where marked the chemical symbols Hg Cd or Pb indicate that the battery contains mercu...

Page 10: ...rature and the fan speed to feel cooler in hot season If current outside temperatures are much higher than the selected indoor temperature it may take time to bring the inner temperature to the desired coolness Quiet mode makes the noise quieter during the operation of the indoor unit in the Cool mode Heat The air conditioner heats as well as cools Warm your room with this versatile appliance in t...

Page 11: ... the button to adjust the temperature Auto You can adjust the desired temperature by 1 C within the range of 16 C 30 C Cool You can adjust the desired temperature by 1 C within the range of 16 C 30 C Dry Temperature adjustment is not possible Fan Temperature adjustment is not possible Heat You can adjust the desired temperature by 1 C within the range of 16 C 30 C Press the Temp Humi button on the...

Page 12: ...s move left and right continuously to circulate the air Press the Airswing button on the remote controller again to keep the air flow direction in a constant position Press the Turbo button on the remote controller during Cool mode Turbo indicator appears on the remote controller display and the air conditioner operates inTurbo function for 30 minutes Using theTurbo function Turbo function is only...

Page 13: ...timer in mode over 5 hours You fell disturbed sleep if the is set too short or long because the default is set to 8 hour operation If the mode is set less than 4 hours the operation will stop at the same time If the mode is set over 5 hours it will run asWake up stage from the last one hour before it stops Recommended set temperature is between 25 C 27 C for cooling and 21 C 23 C for heating Tempe...

Page 14: ...nits from 1minute 59minutes Setting On timer Setting the Current time Before using the functions of the air conditioner set the current time 1 Press 2nd F button 2nd F indicator appears on the remote controller display 2 Press TimeSet button to set the current time AM or PM indicator will blink and you can set the time by pressing Temphr or button for hour and Fanmin button for minute 3 Press Time...

Page 15: ...the time the air conditioner will return to previous status Check On timer or Off timer indicator and indicator on the indoor unit Follow the same process for setting on timer and off timer AdditionaloptionsavailableinOntimermode Displays the last mode set before turning the unit off Adjusting fan speed is not available You can adjust the temperature in Auto Cool Heat mode Only the latest setting ...

Page 16: ... is lower than 24 C it will automatically raise to 24 C Press the button on the remote controller indicator will appears on the remote controller display and the air conditioner generates MPI Press the Press the Smart Saver function is only available in Cool mode When Smart Saver function is activated temperature range will be limited to 24 C 30 C If the desired temperature is lower than 24 C turn...

Page 17: ... When the air conditioner is turned on the Auto clean function runs after stopping the air conditioner operation d light Cool function is only available in Cool mode When d light Cool function is activated temperature sets automatically and will appear on the remote controller display If you press the Mode button while the d light Cool function is on it will cancel the function If using a multi sy...

Page 18: ...ner is operating in Cool Heat mode Quiet indicator appears on the remote controller display The indoor unit will operate more quietly Press the If using a multi system this function will work only when the Quiet function is set on all operated indoor units Press the Quiet button once again Cancel AQV09K Y _Jungfrau_IBIM_E_32448A indd 18 2011 3 19 15 45 09 ...

Page 19: ...ic solvents such as thinner kerosene and acetone etc to clean the surface of the product or put any stickers on it They may damage the surface of the air conditioner Be careful with the sharp edges on the outdoor unit heat exchanger If it is difficult to clean the outdoor unit heat exchanger on your own contact service center Contact the service center when you clean the indoor unit heat exchanger...

Page 20: ...l HD filter with a vacuum cleaner or soft brush If dust is too heavy rinse it with running water Clean the Full HD filter every 2 weeks Cleaning term may differ depending on the usage and environmental conditions In dusty area clean it once a week If the Full HD filter dries in a confined or humid area odors may generate If it occurs re clean and dry it in a well ventilated area Removing the Full ...

Page 21: ...filter 1 Clean the condensate drain pan 2 Thoroughly clean the heat exchanger 2 Clean the condensate drain pipe 2 Replace the remote controller batteries 1 Outdoor unit Clean the heat exchanger on the outside of the unit 2 Clean the heat exchanger on the inside of the unit 2 Clean the electric components with jets of air 2 Verify that all the electric components are firmly tightened 2 Clean the fa...

Page 22: ...e bad cooling heating performance Close the doors and windows Check if the air conditioner has just been turned on after stopping cooling or heating operation In this case just a fan will run to protect the outdoor unit compressor Check if the pipe length is too long When the pipe length exceeds maximum allowable pipe length cooling heating performance may decrease Air flow adjustment is not worki...

Page 23: ...can be heard when refrigerant flow movement changes It is normal Smoke is generated from the outdoor unit If may not be a fire but it can be a steam generated by the defrost operation from outdoor heat exchanger during Heat mode in winter Water is dropping from the outdoor unit piping connection Water may be generated because of the temperature difference It is normal AQV09K Y _Jungfrau_IBIM_E_324...

Page 24: ...e used only for the applications for which it has been designed the indoor unit is not suitable to be installed in areas used for laundry Do not use the units if damaged If problems occur switch the unit off and disconnect it from the power supply In order to prevent electric shocks fires or injuries always stop the unit disable the protection switch and contact SAMSUNG s technical support if the ...

Page 25: ...as required by current regulations in force with slings trucks scaffolding or any other means of elevation won t be considered in warranty and charged to end user Power supply line fuse or circuit breaker Always make sure that the power supply is compliant with current safety standards Always install the air conditioner in compliance with current local safety standards Always verify that a suitabl...

Page 26: ... Avoid the following places to prevent malfunction of the unit Where there is machine oil Salty environment such as seaside areas Where sulfide gas exists Other special atmosphere areas 125mm or more 300mm or more 125mm or more 600mm minimum 300mm minimum 300mm minimum 600mm minimum L meters maximum total pipe length Wrap the refrigerant pipes and the drain hose with the absorbent pad and vinyl ta...

Page 27: ...00 or more The upper part of the outdoor unit and the air outlet is opposite the wall When the walls are blocking front and the rear side of the outdoor unit 300 or more 1500 or more Top view Side view Air outlet Air intake Air intake Air outlet Figure Description Air flow direction Unit mm Unit mm 1500 or more When the air outlet is towards the wall When 3 sides of the outdoor unit are blocked by...

Page 28: ...supplied with the air conditioner The number of each accessory is indicated in parentheses Accessories in the indoor unit case Accessories in the outdoor unit case Installation Plate 1 Remote controller Batteriesfor Remotecontroller 2 User s Installation Manual 1 4 wire Assembly Cable 1 Drain Plug 1 Rubber Leg 4 The flare nuts are attached to the end of each pipe of an evaporator or a service port...

Page 29: ...d Finder TorqueWrench Pipe Cutter Reamer Pipe Bender Spirit Level Screw Driver Spanner Drill LWrench MeasuringTape Tools for test operations Thermometer Resistance Meter Electroscope You can select the direction of the drain hose depending on where you want to install the indoor unit Therefore before fixing the installation plate to a wall or a window frame you must determine the position of the 6...

Page 30: ...e injury Connecting the assembly cable When you install the unit make first refrigerant connections and then electrical connections Connect the air conditioner to grounding system before performing the electrical connection If unit is uninstalled first disconnect electrical cables then refrigerant connections If the outdoor unit is more than 5 meters away from the indoor unit you must extend the c...

Page 31: ...it Indoor unit Outdoor unit 09 12 18 485 Communication type Indoor unit Outdoor unit Ground wire Green Yellow Ground wire Green Yellow End of the wire must be circular After connecting the cables make sure terminal numbers on the indoor outdoor unit matches Screws on terminal block must not be unscrewed with the torque less than 12kgf cm 10 Connect the grounding conductor to the grounding terminal...

Page 32: ...sures of at least 4200 kPa and for burst pressure of at least 20700 kPa Under no circumstances must sanitary type copper pipe be used There are 2 refrigerant pipes of different diameters The smaller one is for the liquid refrigerant The larger one is for the gas refrigerant A short pipe is already fitted to the air conditioner You may need to extend the pipe using the assembly pipe optional The co...

Page 33: ... length of the pipe can be Extended up to see table page 26 Shorten up to see page 26 If you need a pipe longer than 5 meters You must extend the assembly cable You must add refrigerant to the pipes otherwise the indoor unit may freeze Unscrew the caps Pipes Oblique Rough Burr Pipe cutter Pipe The remaining air in the Refrigeration cycle which contains moisture may cause malfunction on the compres...

Page 34: ... nuts first with your hands and then with a torque wrench applying the following torque 7 For further details on how to connect to the outdoor unit and purge the air refer to page 36 38 Correct Uneven Thickness Cracked Damaged Surface Inclined Excessive torque can be cause of gas leakage In case brazing the pipe the nitrogen gas must be blown into the pipe 50 Pa The joint must be accessible and se...

Page 35: ...t and turning to the left 3 Insert the drain hose by fixing it with the screw into the groove of the drain hose and the outlet of the drain pan 4 Attach the rubber cap with a screwdriver by turning it to the right until it fixes to the end of the groove 5 Check for leakage on both side of the drain outlet 1 If necessary connect the 2 meter extension drain hose to the drain hose 2 If you use the ex...

Page 36: ...ole Drain plug Drain hole Drain plug To avoid drain plug from contacting the ground secure gap between the ground and the bottom surface of the outdoor unit In areas with heavy snow fall piled snow could block the air intake To avoid this incident install a frame that is higher than estimated snow fall In addition install a snow proof hood to avoid snow from piling on the outdoor unit When install...

Page 37: ...e port cap to the valve and tighten them at the torque of 183kgf cm with a torque wrench 8 Check for a gas leak paying particular attention to the 3 way valve s stem nuts and to the service port cap Refer to page 39 Vacuum Pump Manifold gauge Valve Gas service port Low pressure Liquid service port High pressure Backward flowing prevention The remaining air in the Refrigeration cycle which contains...

Page 38: ...echarge the refrigerant Important information regulation regarding the refrigerant used Charging the refrigerant under conditions of liquid by using a liquid pipe a Factory refrigerant charge of the product see unit name plate b Additional refrigerant amount charged in the field Refer to the above information for the quantity of refrigerant replenishment c Total refrigerant charge d Refrigerant cy...

Page 39: ...en from the system and create vacuum according to page 36 38 After opening valves check leaks using a leak detector for refrigerant Pump down before disconnecting the refrigerant connections for unit repair removal or disposal Pump down is an operation intended to collect all the system refrigerant in the outdoor unit This operation must be carried out before disconnecting the refrigerant tubing i...

Page 40: ... unit as indicated on the top of the unit to let the discharged air out properly 2 Fix the outdoor unit in level to an appropriate support using anchor bolts 3 If the outdoor unit is exposed to strong winds install shield plates around the outdoor unit so that the fan can operate correctly 5 Wrap the rest of the pipe with vinyl tape 6 Attach the pipe to the wall using clamps optional Installation ...

Page 41: ...f the air conditioner 6 Disconnect the pipes 3 Press the Airswing button and check the following The airflow blades work properly 4 Press the Power button to stop the operation 2 Press the Mode button to select Cool or Heat mode In Cool mode use Temphr or button and set the temperature at 16 C In Heat mode use Temphr or button and set the temperature at 30 C Cooling mode indoor unit check Inlet ai...

Page 42: ...he insulation tape twice and position your contraction tube in the middle of the insulation tape 5 Apply heat to the contraction tube to contract it 6 After tube contraction work is completed wrap it with the insulation tape to finish Tools Crimping plier Connectionsleeve mm Insulation tape Contractiontube mm Spec MH 14 20xØ7 0 HxOD Width 18mm 50xØ8 0 LxOD Shape 40mm Insulation tape Contraction tu...

Page 43: ...ide of the Panel frame 4 Find the PCB wire and connect the wire to the Sub PCB as seen in the picture 5 Connect the wire remote controller central remote controller etc to the Sub PCB 6 Reassemble the Cover PCB and the front panel The Sub PCB is attached to be controlled by the wired remote controller and central controller Only for multi system Sub PCB Cover PCB AQV09K Y _Jungfrau_IBIM_E_32448A i...

Page 44: ... samsung com KOSOVO 381 0113216899 LUXEMBURG 261 03 710 www samsung com MACEDONIA 023 207 777 MONTENEGRO 020 405 888 NETHERLANDS 0900 SAMSUNG 0900 7267864 0 10 Min www samsung com NORWAY 815 56 480 www samsung com POLAND 0 801 1SAMSUNG 172678 022 607 93 33 www samsung com PORTUGAL 80820 SAMSUNG 726 7864 www samsung com RUMANIA 08010 SAMSUNG 08010 726 7864 only from landline local network Romteleco...

Page 45: ...itioner user installation manual imagine the possibilities Thank you for purchasing this Samsung product To receive more complete service please register your product at www samsung com register DB98 32448A 1 I F S E P G D Bu Ro Cr Se AQV09K Y _Jungfrau_IBIM_E_32448A indd 45 2011 3 19 15 46 15 ...

Reviews: