Once you have checked that there are no leaks in the system, you can insulate
the piping, hose and cables and place the indoor unit on the installation plate.
1
To avoid condensation problems, place heat-resistant polyethylene foam
separately around each refrigerant pipe in the lower part of the indoor unit.
2
Wrap the refrigerant pipes and the drain hose located at the rear of the
indoor unit up in the absorbent pad.
➢
Triply wind the pipes and hose to the end of the indoor unit with
the absorbent pad (make intervals of 20mm / inch).
3
Wind insulating tape around the pipes, assembly cable and drain hose.
4
Place the resulting bundle carefully in the lower part of the indoor unit,
making sure that it does not jut out from the rear of the indoor unit.
5
Hook the indoor unit on to the installation plate and move the unit to the
right and left until you are sure that it is securely in place.
6
Finish wrapping vinyl tape around the rest of the piping leading to the
outdoor unit.
7
Using clamps (optionally supplied), attach the piping to the wall wherever
possible.
Installation plate
Placing the Indoor Unit in Position
C
OMPLETING THE
I
NSTALLATION