Installation Method
3-8
Samsung Electronics
3-2-3 Installation Method
3-2-3(a) Installation Procedures
1 . Open the inlet grille, and remove the flare nut.
2. Bend the connection pipe to an appropriate length using the spring bender depending
upon the installation place.
- Allowable pipe length : Maximum 25m
- Allowable pipe drop distance : Maximum 15m
- Make no more than ten bending points on the pipe
• When the pipe length is in excess of the standard pipe length of 5m, add the refrigerant
(R-22) of 50g for each additional 1m.
3. Install the high pre s s u re pipe to the heat exchanger liquid pipe, and the low pre s s u re pipe to the
heat exchanger gas pipe respectively using the flare nut, taking care not to cause any leakage of
re f r i g e r a n t .
4. Be sure to insulate the pipe with appropriate insulation material.
5. Insert the drain hose into the drain pipe, and connect them by tying them to the cable tie to pre-
vent any water leakage.
6. After completion of the installation, check the connecting area for any gas leakage.
7. Wind a finish tape when the wiring of the refrigerant pipe, the unit, and the drain piping are com-
p l e t e d .
Outdoor
unit
Outdoor
unit
Indoor
unit
Indoor
unit
Outdoor unit
checking area
Indoor unit
checking area
CAUTION
• If the pipe is lengthened, the performance of the unit is degraded, and the service life is shortened.
Therefore, the pipe length should be as short as possible (less then 15m).
Summary of Contents for AP500PF
Page 4: ...2 2 Samsung Electronics Unit mm 400 590 930 385 2 2 Dimensions ...
Page 28: ...Samsung Electronics 6 1 6 Exploded Views and Parts List 6 1 Indoor Unit ...
Page 30: ...Samsung Electronics 6 3 6 2 Outdoor Unit 6 2 1 Outdoor Unit ...
Page 36: ...Samsung Electronics 8 1 8 PCB Diagrams 8 1 Ass y Main PCB Code No DB93 10468A ...
Page 38: ...Samsung Electronics 8 3 8 2 Ass y Panel PCB Code No DB93 10469A ...
Page 43: ...Samsung Electronics 10 1 10 Schematic Diagrams 10 1 Indoor Unit ...
Page 44: ...Samsung Electronics 10 2 10 2 Remote Control ...