IAdditional information on SEG 3, 4, 5, 6, 8, 9
When SEG 3 is set to 1 and the HR-specific auto changeover function is run, the indoor unit operates as shown in the
following figure:
C
Temperature
b
d
c
A
D
B
a
Ts
Set temperature
for Auto mode
Reference
temperature for
cooling
Reference temperature for heating
Reference temperature for change from
heating to cooling
Reference temperature for
cooling
Cool
ing th
ermo
off
Cool
ing th
ermo
on
Heating th
ermo
off
Heating th
ermo
on
A: Set with SEG4 (˚C)
B: Set with SEG5 (˚C)
C: Set with SEG6 (˚C)
D: Set with SEG8 (˚C)
The mode change between the Cool and Heat modes is made only when the thermo off state is maintained for the
period of time set with SEG9.