19
ENGLISH
Classification
Y-joint connection
Y-joint / EEV kit connection
Maximum
allowable
length of
pipe
Outdoor unit
~ Indoor
units
Actual Length
The distance between the outdoor unit and the farthest indoor unit ≤ 150m
Ex) 8 indoor units
a+b+c+d+e+f+g+p≤ 150m
Ex) 6 indoor units
a+b+c+d+j ≤ 150m
Equivalent
length
The distance between an outdoor unit and the farthest indoor unit ≤ 175m
Main pipe
length
The main pipe(a) from the outdoor unit to the first Y-joint should be less than
110m.
Total length
The sum of the total length of pipes should be less then 300m.
Maximum
allowable
height
Outdoor unit
~ Indoor
units
Height
H1: The difference of height between an outdoor unit and indoor unit < 50m
Height
H2: The difference of height between indoor units ≤ 15m
Maximum allowable length
after Y-joint
Actual Length
The distance between the first Y-joint
and the farthest indoor unit ≤ 40m
Ex) 8 indoor units
b+c+d+e+f+g+p≤ 40m
Allowable length between EEV kit
and an indoor unit ≤ 20m
Ex) h, l, j ≤ 20m
EEV Kit
Model name
Remarks
EEV Kit ~
Indoor units
Actual pipe lengh
2m or less
MEV-E24SA
1 indoor
Apply to products
without EEV (Wall
mounted & ceiling)
MEV-E32SA
20m or less
MXD-E24K132A
2 indoor
MXD-E24K200A
MXD-E32K200A
MXD-E24K232A
3 indoor
MXD-E24K300A
MXD-E32K224A
MXD-E32K300A
❋
When the equivalent length between an outdoor unit and the farthest indoor unit exceeds 90m, upgrade the low
pressure pipe of the main pipe one step.