Step 4 Installing the drain hose and
drain pipe
1
ťЇϑ˵ϩ˵ʪϑЇΧΧ̷̈ʪʒʒθɇ̈͝˵ͱϑʪɇϑ˙ɇθɇϑΧͱϑϑ̈ɵ̷ʪͱЭʪθ
the drain socket.
2
Tighten the metal clamp as shown in the picture.
3
ǮθɇΧϩ˵ʪϑЇΧΧ̷̈ʪʒ̷ɇθ˝ʪϑʪɇ̷̈͝˝ΧɇʒͱЭʪθϩ˵ʪ͔ʪϩɇ̷
clamp and drain hose to insulate and fix it with clamps.
4
Insulate the complete drain piping inside the building
(field supply).
If the drain hose cannot be sufficiently set on a slope,
fit the hose with drain raising piping (field supply).
5
Push the drain hose up to insulation when connecting
the drain hose to drain socket.
Metal clamp
Drain socket
Drain hose
Large seailng pad
Be sure to bond the drain
hose and the main pipe.
Drain pipe
Drain hose
PVC Tube Joint
+ VP25 (OD: 32 mm, ID: 25 mm)
Drain pipe
CAUTION
A˵ʪʀ̧ϩ˵ɇϩϩ˵ʪ̈͝ʒͱͱθЇ̈͝ϩ̈ϑ̷ʪЭʪ̷ӥϩ˵ϩ˵ʪʀʪ̷̈̈͝˝ɵц
Їϑ̈͝˝ϩ˵ʪ̷ʪЭʪ̷̷ʪθࢋ
•
Ã͝ϑϩɇ̷̷ɇ̈θЭʪ͝ϩ̷̈ɇϩ̈ͱ͝ϩͱʒθɇ̈͝ʀͱ͝ʒʪ͝ϑɇϩ̈ͱ͝ϑ͔ͱͱϩ˵̷цࢋ
Air ventilation
Ceiling
• If it is necessary to increase the height of the drain
pipe, install the drain pipe straight within 300 mm
from the drain hose port. If it is raised higher than 550
mm, there may be water leaks.
Band joint
300 mm or
less
300 to
550 mm
20 mm or more
1/100 or more
Drain hose
Ceiling
•
Uͱ͝ͱϩ˝̈Эʪϩ˵ʪ˵ͱϑʪɇ͝ЇΧиɇθʒ˝θɇʒ̈ʪ͝ϩɵʪцͱ͝ʒϩ˵ʪ
connection port. This will cause water to flow backwards
when the unit is stopped, resulting in water leaks.
Under gradient
Ceiling
• Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as
close to the unit as possible.
Support pieces
1 to 1.5 m
1/100 or more
Ceiling