41
English
Installation Pr
oc
edur
e
Sub indoor unit (BackUp Unit)
1
(Required) Enable the external contact control (with the installation option 02 series SEG14 - Reverse Control).
2
Connect the S-net pro2 to F1 and F2.
3
Enable the entrance control and set the mode, set temperature, and fan speed in the S-net pro2.
࡛
Setting the sub indoor unit in the S-net pro2
a
b
c
a
Select Control for Entering Room.
b
Select the sub indoor unit.
c
Set the operation mode, fan speed, and set
temperature.
࡛
Operation when the external contact settings and the ETO settings overlap
Main indoor unit
Enable of ETO
Enable of external contact
Error port output
X
X
Ęࢩ
X
O
Output due to an error
O
X
Output by ETO entrance conditions
࣑ϩʪ͔ΧʪθɇϩЇθʪࢩϩ͔̈ʪࢩʪθθͱθͱʀʀЇθθʪ͝ʀʪ࣒
O
O
Output by ETO entrance conditions
࣑ϩʪ͔ΧʪθɇϩЇθʪࢩϩ͔̈ʪࢩʪθθͱθͱʀʀЇθθʪ͝ʀʪ࣒
࢜ŵʪɇʒцϩͱʀͱ͝ϩθͱ̷ϩ˵ʪ͔ɇ̈͝ʀͱ͝ϩɇʀϩ̈͝ΧЇϩ
Sub indoor unit
Enable of entrance control
Enable of external contact
Operation when outputting Main
X
X
Ęࢩ
X
O
On with the previous operation conditions
O
O
On with the entrance control enabled
Summary of Contents for AM NN1PEH Series
Page 44: ...DB68 07552A 01...