
29
English
Installation Pr
oc
edur
e
Installation options for the 02 series
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
2
Evaporator Drying
Use of external
room temperature
ϑʪ͝ϑͱθࢩđ͔̈̈̈͝ї͝˝
fan operation when
thermostat is off
Use of central control
FAN RPM
compensation
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
Use of drain pump
Use of hot water
heater
-
EEV Step when
heating stops
Dew removal
operation in wind
free mode
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
Use of external
control
Setting the output
ͱ˙ʪуϩʪθ͝ɇ̷ʀͱ͝ϩθͱ̷ࢩ
External heater signal
ࢩAͱͱ̷̈͝˝ͱΧʪθɇϩ̈ͱ͝
ϑ̈˝͝ɇ̷ࢩθʪʪAͱͱ̷̈͝˝
control signal
S-Plasma ion
Buzzer control
Hours of filter usage
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
Individual control of a
remote controller
Heating setting
compensation
ࢩŵʪ͔ͱӬ͝˝
condensate water in
heating mode
Adjusted EEV step of
stopped unit during
ͱ̷̈θʪϩЇθ͝ࢩʒʪ˙θͱϑϩ
mode.
Motion detect sensor
-
࡛
Even if you set the Use of drain pump (SEG8) option to 0, it is automatically set to 2 (the drain pump is used with 3
minute delay).
࡛
If you set the Maximum filter usage time (SEG18) option to a value other than 2 and 6, it is automatically set to 2
(1000 hours).
࡛
If you set an option to a value that is out of range specified above, the option is automatically set to 0 by default.
࡛
The SEG5 option (Use of central control) is set to 1 (Use) by default. Therefore, you don't need to set the SEG5 option
additionally. Note that even if the central control system is not connected, no errors occur. If you want a specific
indoor unit not to be controlled by the central control system, set the SEG option of that indoor unit to 0 (Disuse).
࡛
The external output of SEG15 is generated via MIM-B14 connection. (Refer to the manual of MIM-B14.)
࡛
If you set the Individual control with remote control (SEG20) option to a value other than 0 to 4, it is automatically set
to 0 (Indoor 1).
࡛
The output of hot water heater in SEG9 is generated from the hot coil part of the terminal board in duct models.
Outdoor
Communication
(+)
(-)
COM2
DC 12 V Wire Remote
Controller
AC
POWER
HOT
COIL
L
N
COM1
७Ɵ˵ʪͱЇϩΧЇϩͱ˙˵ͱϩʀͱ̷̈ϩʪθ͔̈͝ɇ̷̈ϑAߤߤߢǤࢩߤߥߢǤ
(The same as Indoor Unit’s input Power)
Summary of Contents for AM NN1DEH Series
Page 44: ...DB68 07552A 01 ...