31
English
Installation Pr
oc
edur
e
Option
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
Explanation
PAGE
Use of external
control
Setting the output of external
control / External heater signal
/ Cooling operation signal /
Free Cooling control signal
S-Plasma ion
Buzzer control
Hours of filter usage
Indication
and Details
Indication Details Indication Details Indication
Details
Indication
Details
Indication Details Indication
Details
2
0
Disuse
0
External control
(Thermo On)
0
Disuse
0
Use
buzzer
2
1000 Hour
1
ON/OFF
control
1
External control
(Operation On)
2
External heater
signal (*4)
2
OFF
control
3
External heater
signal (*4)
4
Cooling operation
signal (*5)
1
Use
1
Disuse
buzzer
6
2000 Hour
3
Window
ON/OFF
control
5
Free Cooling
control (Cooling
Thermo On) (*6)
6
Free Cooling
control (Cooling/
Dry Thermo On)
(*6)
Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Explanation
PAGE
Individual control of
a remote controller
Heating setting compensation / Removing
condensate water in heating mode
Adjusted EEV step
of stopped unit
during oil return /
defrost mode.
Motion detect sensor
-
Indication
and Details
Indication Details Indication Details Indication
Details
Indication Details Indication
Details
-
Heating Setting
Compensation
Removing Condensate
Water in Heating Mode
3
0 or 1
channel
1
0
Default
Disuse
0
Default
0
Disuse
1
2 °C
Disuse
1
Turn out in 30min.
without motion
2
channel
2
2
5 °C
Disuse
2
Turn out in 60min.
without motion
3
Default
Use (*7)
3
Turn out in 120min.
without motion
3
channel
3
4
Turn out in 180min.
without motion
4
2 °C
Use (*7)
1
Adjusted
EEV
positon
5
Turn out in 30min.
without motion or
*advanced function
4
channel
4
6
Turn out in 60min.
without motion &
*advanced function
5
5 °C
Use (*7)
7
Turn out in 120min.
without motion &
*advanced function
8
Turn out in 180min.
without motion &
*advanced function
* Advanced function: Controlling cooling/heating current or power saving with motion detect.
(*1)
When Cooling or dry mode is off. The indoor fan operate in setting minutes.
(*2)
Minimizing fan operation when thermostat is off
- Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
- Fan stops or operates Ultra low in Cooling when thermostat is off.
(*3)
1: Fan is turned on continually when the hot water heater is turned on,
3: Fan is turned off when the hot water heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch(MCM-C200) on the outdoor unit and fix it as cool mode.
If the "Cooling Priority" option is set in the Heat Pump outdoor unit, the indoor unit can operate in the Heat mode
owing to the water heater even if the outdoor unit is running in the Cool mode.