Setting an indoor unit installation option (suitable for the condition of each installation location)
1. Check whether power is supplied or not.
f
When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2. The panel(display) should be connected to an indoor unit to receive option.
3. Set the installation option according to the installation condition of an air conditioner.
f
The default setting of an indoor unit installation option is “020010-100000- 200000-300000”.
f
Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is
more than one indoor unit.
4. Set the indoor unit option by wireless remote controller.
02 series installation option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
2
-
-
Central control
-
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
Drain pump
-
-
EEV Step when
heating stops
Master / Slave
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
External control
External control
output
-
-
Number of hours
using filter
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
-
Heating setting
compensation
EEV Step of
stopped unit during
oil return/defrost
mode
-
-
f
1 WAY / 2WAY / 4WAY, DUCT MODEL : Number of hours using filter(SEG18) will be set to ‘1000 hour’ even if the SEG18 is
set to exept for 2 or 6.
f
When setting the option other than above SEG values, the option will be set as “0”.
f
SEG5 central control option is basically set as 1 (Use), so you don’t need to set the central control option additionally.
However, if the central control is not connected but it doesn’t indicate an error message, you need to set the central
control option as 0 (Disuse) to exclude the indoor unit from the central control.
04
INST
ALLA
TION
English-31