Installation Pr
oc
edur
e
Option
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
Function
Page
-
Setting MCU PORT
address
10-digit of MCU
address
1-digit of MCU
MCU PORT address
Indication
and details
Indication Details
-
Indication Details Indication
Details
Indication Details Indication Details
2
0
No MCU
PORT
0~1
10-digit
0~9
1-digit
A~F
PORT
Location
1
MCU
PORT
address
setting
mode
CAUTION
• If you enter A to F to the SEG5 or SEG6, the indoor unit
main address is not changed.
• If you enter 0 to the SEG 3, the indoor unit maintains
the previous main address although you enter the
option value for the SEG5 or SEG 6.
• If you enter 0 to the SEG 9, the indoor unit maintains
previous RMC address although you enter the option
value for the SEG11 or SEG12.
• You cannot set the SEG11 or SEG12 to F value at the
same time.
• If the indoor unit is connected to the MCU, you can set
the SEG 15~18.
Ex.) If you want to set the indoor unit to ‘A’ port of MCU #1.
(0A0000 – 100000 – 20101A -30000)
Setting the indoor unit installation option
(suitable for the condition of each installation
location)
1
Make sure that the power is supplied to the indoor
unit.
• If the indoor unit is not plugged in, it must include a
power supply.
2
Make sure that the panel or display is connected to the
indoor unit so that it can receive options
1(L)
2(N)
F1
F2
3
Set an address for each indoor unit using the remote
control, according to your air conditioning system plan.
• The indoor unit addresses are set to 020010-
100000-200000-300000 by default.
• The SEG20 option, Individual control with remote
control, allows you to control multiple indoor units
individually by using the remote control.