34
Refrigerant pipe installation
Basic type - additional refrigerant
H/P
H/R
1/2" (5m/16.4')
1/2" (5m/16.4')
1/2" (5m/16.4')
1/4" (5m/16.4')
1/4" (10m/32.8')
1/4" (15m/49.2')
3/8" (10m/32.8')
3/8" (10m/32.8')
3/8" (10m/32.8')
3/8" (10m/32.8')
1/4" (5m/16.4')
3/8" (10m/32.8')
144MBH (12Ton)
12MBH
24MBH
24MBH
18MBH
18MBH
18MBH
18MBH
12MBH
3/8" (1m/3.3')
1/2" (5m/16.4')
5/8" (10m/32.8')
1/2" (10m/32.8')
3/8" (15m/49.2')
3/8" (10m/32.8')
1/2" (10m/32.8')
3/8" (18m/59.1')
3/8" (18m/59.1')
3/8"
(25m/82.0')
3/8"
(15m/49.2')
3/8"
(10m/32.8')
MCU
MCU
1/4" (2m/6.6')
12MBH
24MBH
36MBH
36MBH
36MBH
24MBH
24MBH
24MBH
1/4" (15m/49.2')
216MBH (18Ton)
( 72MBH)
Branch joint
f
Basic amount of refrigerant within the outdoor unit
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Classification
AM072F
✴
AM096F
✴
AM120F
✴
AM144F
✴
AM168H
✴
AM192H
✴
Basic type [kg (lb)]
5.5 (12.1)
7.4 (16.3)
7.4 (16.3)
8.7 (19.2)
11.0 (24.3)
11.0 (24.3)
Classification
AM072K
✴
AM096K
✴
AM216KXVGJ
✴
Basic type [kg (lb)]
8.4 (18.5)
8.4 (18.5)
12.5 (27.6)
f
Amount of additional refrigerant depending on the pipe size (
ⓐ
)
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Size of liquid pipe
[mm (inch)]
Ø6.35
(Ø1/4)
Ø9.52
(Ø3/8)
Ø12.70
(Ø1/2)
Ø15.88
(Ø5/8)
Ø19.05
(Ø3/4)
Ø22.23
(Ø7/8)
Ø25.40
(Ø1)
Additional amount
[kg/m (Ib/ft)]
0.02
(0.013)
0.06
(0.040)
0.125
(0.084)
0.18
(0.121)
0.27
(0.181)
0.35
(0.235)
0.53
(0.356)
- For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.0067lb per feet regardless of
the pipe size.