39
ENGLISH
05 series installation option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
5
Use of Auto Change Over
for HR only in Auto mode /
Use of Cooling only indoor
unit of HR
(When setting SEG3)
Standard heating temp.
Offset
(When setting SEG3)
Standard cooling temp.
Offset
(When setting SEG3)
Standard for mode change
Heating
Cooling
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
(When setting SEG3)
Standard for mode change
Cooling
Heating
(When setting SEG3)
Time required for mode
change
Compensation option
for Long pipe or height
difference between
indoor units
MTFC (*3)
-
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
-
-
-
-
Control variables when using
hot water / external heater (*4)
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
-
-
-
Forced FAN Operation for
Heating and Cooling
-
05 series installation option(Detailed)
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
Use of Auto Change
Over or Cooling only
for HR only
(When setting SEG3)
Standard heating temp. Offset
(When setting SEG3)
Standard cooling
temp. Offset
(When setting SEG3)
Standard for mode
change Heating
Cooling
Indication
and Details
Indication Details Indication
Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
0
5
0
Follow
product
option
0
0 °C
0
0 °C
0
0 °C
1
0.5 °C
1
0.5 °C
1
0.5 °C
1
Use Auto
Change
Over for
HR only
2
1 °C
2
1 °C
2
1 °C
3
1.5 °C
3
1.5 °C
3
1.5 °C
4
2 °C
4
2 °C
4
2 °C
2
Use
Cooling
only
indoor
unit for
HR
5
2.5 °C
5
2.5 °C
5
2.5 °C
6
3 °C
6
3 °C
6
3 °C
7
3.5 °C
7
3.5 °C
7
3.5 °C
Option SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
(When setting SEG3)
Standard for mode
change Cooling
Heating
(When setting SEG3)
Time required for
mode change
Compensation option for Long
pipe or height difference between
indoor units
MTFC (*3)
Indication
and Details
Indication Details Indication
Details
Indication
Details
Indication
Details
Indication
Details
1
0
1 °C
0
5min
0
Default
0
Default
1
1.5 °C
1
7min
1
(*1) Height difference
is more than 30m or
(*2) Distance is longer
than 110m
2
2 °C
2
9min
3
2.5 °C
3
11min
4
3 °C
4
13min
2
(*1) Height difference is
15~30m or
(*2) Distance is
50~110m
2
Use
5
3.5 °C
5
15min
6
4 °C
6
20min
7
4.5 °C
7
30min