37
ENGLISH
1.
Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2.
The panel(display) should be connected to an indoor unit to receive option.
3.
Set the installation option according to the installation condition of an air conditioner.
- The default setting of an indoor unit installation option is “020010-100000- 200000-300000”.
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit
individually when there is more than one indoor unit.
4.
Set the indoor unit option by wireless remote controller.
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
2
--
External room
temperature sensor
/ Minimizing fan
operation when
thermostat is off
Central control
FAN RPM
compensation
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
Drain pump
Hot water heater
--
EEV Step when
heating stops
--
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
External control
External control
output / External
heater On or Off
signal
-
Buzzer
Number of hours
using filter
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
Individual control of
a remote controller
Heating setting
compensation
/ Removing
condensated water
in heating mode
EEV Step of stopped
unit during oil
return/defrost mode
-
--
X
1 WAY/2WAY/4WAY,DUCT MODEL : Number of hours using filter(SEG18) will be set to ‘1000hour’ even
if the SEG18 is set to exept for 2 or 6.
X
When setting the option other than above SEG values, the option will be set as “0”.
X
SEG5 central control option is basically set as 1 (Use), so you don’t need to set the central control
option additionally.
However, if the central control is not connected but it doesn’t indicate an error message, you need to
set the central control option as 0 (Disuse) to exclude the indoor unit from the central control.
Q
02 series installation option
Setting an indoor unit installation option
(suitable for the condition of each installation location)