Samsung AM AN4PKH Series Installation Manual Download Page 7

7

English

Installation Pr

oc

edur

e

Spacing requirements

2500 mm or more

Obstruction

1500 mm or more

17 mm

20 mm

A

(Unit: mm)

Model

AM028AN4PKH 

AM036AN4PKH 

AM045AN4PKH 

AM056AN4PKH 

AM071AN4PKH

AM090AN4PKH 

AM112AN4PKH

AM128AN4PKH 

AM140AN4PKH

A

251

293

335

C

C

C

C

(Unit: mm)

C: 1500 mm or more

  CAUTION

•  The indoor unit must be installed according to the 

specified distances in order to permit accessibility 
from each side, to guarantee correct operationfssss, 
maintenance, and repair of the unit. The components 
of the indoor unit must be reachable and removable 
under safe conditions for people and the unit.

•  Do not hold the discharge while carrying the indoor 

unit to avoid the possibility of breakage.

•  You must hold the hanger plate on the corner and 

carry the indoor unit.

Step 3  Optional: Insulating the body 

of the indoor unit

If you install a cassette type indoor unit on the ceiling when 
temperature is over 27°C and humidity is over 80%, you 
must apply an extra 10 mm thick polyethylene insulation or a 
similar type of insulation to the body of the indoor unit.
Cut away the part where pipes are pulled out for the 
insulating work.

D

A

E

B

C

Insulate the end of the pipe and some curved area by 
using separate insulator.

  NOTE

•  A: Reference for the outer circumference of the unit 

(When insulating the body of the indoor unit, use A as 
the reference for its outer circumference.)

(Unit: mm)

Indoor unit

A

B

C

D

E

4 way Cassette <S> 

(840x204x840)

AM028AN4PKH

910X151 940X151 610X151 650X151 870X870

AM036AN4PKH
AM045AN4PKH
AM056AN4PKH

AM071AN4PKH

4 way Cassette <M> 

(840x246x840)

AM090AN4PKH

910X193 940X193 610X193 650X193 870X870

AM112AN4PKH

4 way Cassette <L> 

(840x288x840)

AM128AN4PKH

910X235 940X235 610X235 650X235 870X870

AM140AN4PKH

ki]_TW``]^hTWW†pt†k}tGolG~•‹Gm™ŒŒG[žˆ †l|†luU•‹‹GGG^

YWYXTWXTY`GGG㝘䟸GZaZ`a\_

Summary of Contents for AM AN4PKH Series

Page 1: ...Airconditioner Installation manual AM AN4PKH Thank you for purchasing this Samsung air conditioner Before operating this unit please read this manual carefully and retain it for future reference...

Page 2: ...t gas from the indoor unit 9 Step 6 Cutting and flaring the pipes 9 Step 7 Connecting the assembly pipes to the refrigerant pipes 10 Step 8 Performing the gas leak test 11 Step 9 Insulating the refrig...

Page 3: ...designed the indoorunit is not suitable to be installed in areas used forlaundry Do not use the units if damaged If problems occur switch the unit off and disconnect it from the powersupply In ordert...

Page 4: ...lectric lines Always verifythat the cut off and protection switches are suitably dimensioned Verifythat the airconditioneris connected to the power supply in accordance with the instructions provided...

Page 5: ...ust be installed such that it is beyond public access and is not touchable by users Rigid wall without vibration Where it is not exposed to direct sunshine Where the airfilter can be removed and clean...

Page 6: ...6AN4PKH AM045AN4PKH AM056AN4PKH AM071AN4PKH AM090AN4PKH AM112AN4PKH AM128AN4PKH AM140AN4PKH Chassis Small Medium Large A mm 215 238 238 B mm 105 127 127 C mm 196 222 222 Net dimension W D H mm 840X840...

Page 7: ...the indoor unit Step 3 Optional Insulating the body of the indoorunit Ifyou install a cassette type indoorunit on the ceilingwhen temperature is over27 C and humidityis over80 you must applyan extra10...

Page 8: ...Make sure that the ceiling is strong enough to support the weight of the indoor unit Before hanging the unit test the strength of each attached suspension bolt If the length of the suspension bolt is...

Page 9: ...OTE To prevent dirt orforeign objects from getting into the pipes during installation do not remove the pinch pipe completely until you are ready to connect the piping Step 6 Cutting and flaring the p...

Page 10: ...nough to coverthe refrigerant tube to protect the condensate water on the outside of the pipe falling onto the floor and to improve the efficiency of the unit 3 Cut off any excess foam insulation 4 Ma...

Page 11: ...requiring the use of sheaths insulation without using CFC and HCFC gases forhealth and the environment 2 Wind insulating tape around the pipes and drain hose avoiding compressing the insulation too mu...

Page 12: ...ilding construction condition Ceilings frequently exposed to moisture and cooling are not covered For example pipes installed at a corridor of a dormitory and studio or near an exit that opens and clo...

Page 13: ...0 mm orless 300 to 550 mm Do not give the hose an upward gradient beyond the connection port This will cause waterto flow backwards when the unit is stopped resulting in waterleaks Undergradient Ceili...

Page 14: ...rubber cap on the connection part of a flexible hose of the indoor unit and firmly tighten it with a band to prevent leakage c Check the leak test at the part where the adhesive forthe flexible hose a...

Page 15: ...under10 The auxiliary circuit breaker ELCB MCCB ELB should be considered more capacity if many indoor units are connected from one breaker Connect F3 F4 for communication to the communication cable o...

Page 16: ...e connection part of the power cable and crimping terminal lug to insulate it B 2 R d 2 B F L E Silversolder d1 D t Norminal dimensions forcable mm Norminal dimensions forscrew mm B D d1 E F L d2 t St...

Page 17: ...a 2 1 Decide the capacity of ELB and MCCB by below formula k 9 AA9 NOTE X The capacity of ELB MCCB Rated currents Model Rating current A AM028AN4PKH 0 25 AM036AN4PKH 0 27 AM045AN4PKH 0 30 AM056AN4PKH...

Page 18: ...If the poweris unbalanced greatly it may shorten the life of the condenser If the unbalanced poweris exceeded over10 of supply rating the indoorunit is protected stopped and the errormode indicates C...

Page 19: ...contact area becomes reduced or corrosion develops on the outer surfaces of the wires copperwires over a long time This may cause an increase of resistance reduction of passing current and consequentl...

Page 20: ...the optionvalues Entering the mode forsetting the options NOTE The remote control display and buttons mayvary depending on the model 1 Enterthe mode for setting the options a Remove the batteries from...

Page 21: ...e SEG4 value by pressing the Low Fan button repeatedly until the value you want to set appears on the remote control display SEG4 b Set the SEG5 value by pressing the High Fan button repeatedly until...

Page 22: ...ontrol display When you press the Low Fan or High Fan button values appear in the following order SEG10 8 Press the Mode button Heat and On appear on the remote control display 9 Set the SEG11 and SEG...

Page 23: ...the Low Fan button repeatedly until the value you want to set appears on the remote control display SEG16 b Set the SEG17 value by pressing the High Fan button repeatedly until the value you want to...

Page 24: ...you want to set appears on the remote control display When you press the Low Fan or High Fan button values appear in the following order SEG22 18 Press the Mode button Heat and Off appear on the remot...

Page 25: ...tton on the remote control twice Make sure that this command is received by the indoor unit When it is successfully received you can hear a short sound from the indoor unit If the command is not recei...

Page 26: ...ET Pro 2 Help From SEG13 to SEG18 is for setting MCU address A A k MCU S4NEK3N MCU S1NEK1N Setting the installation options in a batch Option No foran indoorunit address 0AXXXX 1XXXXX 2XXXXX 3XXXXX Op...

Page 27: ...EG11 orSEG12 You cannot set the SEG11 orSEG12 to Fvalue at the same time If the indoorunit is connected to the MCU you can set the SEG15 18 Ex Ifyouwant to set the indoorunit to A port of MCU 1 0A0000...

Page 28: ...step of stopped unit during oil return defrost mode Motion detect sensor Even if you set the Use of drain pump SEG8 option to 0 it is automatically set to 2 the drain pump is used with 3 minute delay...

Page 29: ...ing 2 4 Disuse Use Cooling 2 1 RPM compensation 5 Use Use Cooling 2 4 Use 10min 1 6 Disuse Use Heating Cooling 2 1 Use 7 Use Use Heating Cooling 2 8 Disuse Use CoolingUltra LowFan 2 2 Highceiling KIT...

Page 30: ...toppedunit duringoilreturn defrostmode SettingtheMDSKitinstallationoption Indication andDetails Indication Details Indication Details Indication Details Indication Details Indication Details HeatingSe...

Page 31: ...at of the indoor unit heat exchanger Since the watervapor might be condensed on the indoor unit which may fall into a living space use this function to get rid of the water vapor out of the indoor uni...

Page 32: ...1 UseAuto Change Overfor HRonly 2 1 C 2 1 C 2 2 C 3 1 5 C 3 1 5 C 3 2 5 C 4 2 C 4 2 C 4 3 C 2 Use Cooling onlyindoor unitforHR 5 2 5 C 5 2 5 C 5 3 5 C 6 3 C 6 3 C 6 4 C 7 3 5 C 7 3 5 C 7 4 5 C Option...

Page 33: ...es C 6 0 C Nodelay D 6 0 C 10minutes E 6 0 C 20minutes Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 Explanation PAGE ForcingFANOperation forHeatingandCooling Indication andDetails Indication Details Ind...

Page 34: ...Setting 02 series SEG9 1 Setting 05 series SEG18 0 The hot water heater is turned on at the same time as the heating thermostat is on and turned off when the heating thermostat is off k k k compensat...

Page 35: ...0 D Option type 0toF Tens position value 0to9 Units position value 0to9 New value 0toF Example Changing the Buzzer control SEG17 option of the installation options to1 disuse Option SEG1 SEG2 SEG3 SEG...

Page 36: ...Earth conductor connection Correct operation follow the steps below Afterfinishing the installation of the airconditioner you should explain the following to the user Referto appropriate pages in the...

Page 37: ...to unmatching number of installed units E201 5 Error due to repeated communication address E108 6 Communication address not confirmed E109 Other outdoor unit communication errorthat is not on the abov...

Page 38: ...ection E181 Other outdoorunit self diagnosis errorthat is not on the above list Floating Switch 2nd detection E153 X X EEPROM error E162 EEPROM option error E163 Error due to incompatible indoor unit...

Page 39: ...39 English Appendix Memo...

Page 40: ...DB68 09967A 00...

Reviews: