Samsung AJ100MCJ5EH Installation Manual Download Page 10

10

Installation Procedure

English

Installation Pr

oc

edur

e

 

• Connect the cables to the terminal board using the compressed ring terminal.

 

• Use rated cables only.

 

• Connect the cables with driver and wrench that can apply the rated torque to the screws.

 

• Make sure that appropriate tightening torque is applied for cable connection. If the terminal is loose, arc heat may 

occur and cause fire and if the terminal is connected too firmly, terminal may get damaged.

Transmitter installation(option)

 

• AJ100MCJ5EH

Accessories (Transmitter:   MIM-B13B)

1. Turn the power off and take off the cover of the outdoor units.

2. Fix the case with bolts to the side of the control box referring to the figure 

on the right side.

In case of FJM outdoor unit, there is not enough space to fix all parts of 

transmitter. So you may use transmitter main PCB.

3. Attach the transmitter main PCB to the case, then connect F1/F2 lines, 

R1/R2 lines which are upper controller communication cables and DC 12V 

power cables to the interface module referring to the figure on page 11. 

(Upper controller power should be off.)

4. You must check the position of dip switch on the transmitter's main PCB 

ɇ͝ʒϩ˵ʪ͔ɇ̈͝ťA9ͱ˙đ²७७ࢩĘâ७७̈͝ʒͱͱθЇ̈͝ϩϑ࢏˜ͱθůǤ७७ࢩâĘ७७ࢩ

ŵ७७̈͝ʒͱͱθЇ̈͝ϩϑࡥθʪ˙ʪθϩͱΧɇ˝ʪߤߨ࢏

5. Assemble a cover of the outdoor unit and turn the power on.

6. Check the communication status.

7.

If you install a transmitter to the outdoor unit, every indoor unit which is 

connected to the outdoor unit can be controlled simultaneously.

8. Each outdoor unit connected to the same centralized controller has its 

own transmitter.

Transmitter 

MAIN

Transmitter 

SUB

485  

Communication 

Cable

DC Power 

Cable (12V)

DC Power 

Cable (5V)

Communication 

Cable

Cable Tie

Case

R1 R2

R2 R1 R2 R1

Fix the case with hinges 

(Control Box in the outdoor unit)

Tightening power terminal

Summary of Contents for AJ100MCJ5EH

Page 1: ...Airconditioner Installation manual AJ100MCJ5EH Thank you for purchasing this Samsung air conditioner Before operating this unit please read this manual carefully and retain it for future reference ...

Page 2: ...ace 7 Step 4 Connecting the power cables communication cable and controllers 8 Step 5 Optional Extending the power cable 13 Step 6 Connecting the refrigerant pipe 15 Step 7 Optional Cutting and flaring the pipes 15 Step 8 Connecting up and removing air in the circuit 16 Step 9 Performing the gas leak test 17 Step10 Adding refrigent R 410A 18 Step11 Connecting the drain hose to the outdoor unit 19 ...

Page 3: ...ner should be used only forthe applications forwhich it has been designed the indoor unit is not suitable to be installed in areas used for laundry Do not use the units if damaged If problems occur switch the unit off and disconnect it from the power supply In orderto prevent electric shocks fires or injuries always stop the unit disable the protection switch and contact SAMSUNG s technical suppor...

Page 4: ...he installation manual are not complied with the cost required to access and repairthe units in SAFETY CONDITIONS as set out in prevailing regulations with harnesses ladders scaffolding or any other elevation system will NOT be considered part of the warranty and will be charged to the end customer Powersupplyline fuse orcircuit breaker WARNING Always make sure that the power supply is compliant w...

Page 5: ...se can be firmly fixed in place Make sure that the water dripping from the drain hose runs away correctly and safely CAUTION You have just purchased a system airconditionerand it has been installed byyourinstallation specialist This device must be installed according to the national electrical rules If your outdoor unit exceeds a net weight of 60 kg do not install it on a suspended wall but stand ...

Page 6: ...re 300 or more 2000 or more 1500 or more 600 or more 300 or more 1500 or more 300 or more When installing more than1 outdoorunit Unit mm 1500 or more 600 or more 3000 or more 3000 or more 300 or more 600 or more 600 or more 1500 or more 300 or more 1500 or more 600 or more 600 or more 300 or more 600 or more 600 or more 600 or more 300 or more 300 or more 300 or more 500 or more 500 or more CAUTIO...

Page 7: ...the outdoor unit on a rigid and stable base to prevent disturbance from any noise caused byvibration When installing the unit at a height or in a location exposed to strong winds fix the unit securely to a support i e a wall or a ground 1 Position the outdoor unit so that the airflow is directed towards the outside as indicated by the arrows on the top of the unit 2 Attach the outdoor unit to the ...

Page 8: ...es communication cable and controllers You must connect the following three electrical cables to the outdoor unit The main power cable between the auxiliary circuit breaker and the outdoor unit The outdoor to indoor power cable between the outdoor unit and the indoor unit The communication cable between the outdoor unit and the indoor unit CAUTION During installation make first the refrigerant con...

Page 9: ...um input current 5 MFA represents capacitywhich may accept MCA Abbreviations MCA Min Circuit Amps A MFA Max Fuse Amps A Screw Tighten Torque kgf cm Position M4 12 0 18 0 1 L 2 L L N F1 F2 Model OutdoorUnits Maximun Input Current A PowerSupply Rated Outdoor Indoor Max Total MCA MFA OutdoorUnit IndoorUnit Hz Volts AJ100MCJ5EH 5 Room 50 1phase 220 240 23 0 3 2 26 2 26 2 28 8 A B C 1 L 2 N 1 L 2 N 1 L...

Page 10: ...y use transmitter main PCB 3 Attach the transmitter main PCB to the case then connect F1 F2 lines R1 R2 lines which are upper controller communication cables and DC 12V power cables to the interface module referring to the figure on page 11 Upper controller power should be off 4 You must check the position of dip switch on the transmitter s main PCB ɇ ʒ ϩ ʪ ɇ ťA9 ͱ đ ७७ࢩĘâ७७ ʒͱͱθ Ї ϩϑ ͱθ ůǤ७७ࢩ âĘ७...

Page 11: ...oor units PCB K2 ON to OFF ForAJN७७ AR७७ indoor units referto page 26 Check the dip switch postion on transmitter main PCB as the picture above turn ON 1 ON DIP 2 3 4 R1 R2 DC12V Blue Transmitter MAIN PCB Outdoorunit HUB PCB Terminal Block in the outdoorunit DC12V supply F1 F2 F1 F2 ...

Page 12: ...ng a driverwhich is able to apply the rated torque to the screws If the terminal is loose fire may occur caused by arc If the terminal is connected too firmly the terminal may be damaged Tightening torque kgf cm M4 12 0 to18 0 M5 20 0 to 30 0 1N m 10 kgf cm CAUTION When connecting cables you can connect the cables to the electrical part or connect them through the holes below depending on the spot...

Page 13: ...epare the following tools Tools Spec Shape Crimping pliers MH 14 Connection sleeve mm 20xØ6 5 HxOD Insulation tape Width19 mm Contraction tube mm 70xØ8 0 LxOD 2 As shown in the figure peel off the shields from the rubber and wire of the power cable Peel off 20 mm of cable shields from the pre installed tube CAUTION For information about the power cable specifications for indoor and outdoor units r...

Page 14: ... work is completed wrap it with the insulation tape to finish CAUTION Make sure that the connection parts are not exposed to outside Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials that have the same level of withstand voltage with the power cable Complywith the local regulations on extensions WARNING In case of extending the electric wire ple...

Page 15: ...wing conditions Model Cool Heat Outdoor temperature 10 C to 46 C 15 C to 24 C It could take maximum 60 minutes to operate forthe protection of the compressor if the outdoortemperature is below 5 C ƊϩʪΧ ߩ ĮΧϩ ͱ ɇ ࡤ AЇϩϩ ɇ ʒ Ѥɇθ the pipes 1 Make sure that you have the required tools available pipe cutter reamer flaring tool and pipe holder 2 If you wish to shorten the pipes cut it with a pipe cutter...

Page 16: ...e of the refrigerant cycle abnormally high It may cause explosion and injury The outdoor unit is loaded with sufficient R 410A refrigerant Do not vent R 410A into atmosphere it is a fluorinated greenhouse gas covered by Kyoto Protocol with a Global Warming Potential GWP 2088 You should purge the air in the indoor unit and in the pipe If air remains in the refrigerant pipes it affects the compresso...

Page 17: ...unit to the installation plate you must check that there are no gas leaks To check for gas leaks on the Then using a leak detector check the Outdoorunit Valves on sections A and B Indoorunit Flare nuts at the end of sections C and D C D The designs and shape are subject to change according to the model øk ç ƟkƊƟ ǮÃƟ ĘÃƟŵĮ kĘ ɵʪ ͱθʪ ͱΧʪ Эɇ Эʪϑ In orderto detect basic refrigerant leaks before recrea...

Page 18: ...Unit Outdoor Unit 1 Unit kg tCO2 e a b c Refrigerant type GWPvalue R 410A 2088 GWP Global Warming Potential Calculating tCO2e kg x GWP 1000 NOTE a Factory refrigerant charge of the product see unit name plate b Additional refrigerant amount charged in the field Referto the above information forthe quantity of refrigerant replenishment c Total refrigerant charge d Refrigerant cylinder and manifold ...

Page 19: ...cifications given in the illustration 2 Connect the flexible hose to the flexible hose port In damp hard soil ratherthan loose sandy or gravel soil that has a higher earthing resistance Away from underground structures orfacilities such as gas pipes water pipes telephone lines and underground cables At least two metres away from a lightening conductor earthing electrode and its cable NOTE The eart...

Page 20: ...ications change as shown in the following table and the automatic address setting starts A B RED GRN RED GRN YEL 3 When communication between the outdoor unit and the indoor units starts normally the LED indications change as shown in the following table Afterthis the outdoor unit starts the automatic pipe inspection A B RED GRN RED GRN YEL 4 Check whetherthe automatic pipe inspection is finished ...

Page 21: ...RED GRN RED GRN YEL 3 After a while the LED indications change as shown in the following table A B RED GRN RED GRN YEL 4 Press the K1 button to start a reinstallation Referto 3 and 4 in Setting the indoor unit address and inspecting the pipes automatically A B RED GRN RED GRN YEL Setting the indoorunit addresses manually 1 Turn off the switch1 of the DIP switch and then turn on the outdoor unit 2 ...

Page 22: ...tton High Temp button Mode button Low Fan button High Fan button Option setting mode Entering mode forsetting option Setting Option 1 Remove batteries from the remote controller 2 Insert batteries and enterthe option setting mode while pressing High Temp button and Low Temp button TYPE PICTURE MODEL TO SETADDRESSING MANUALLY BY ROTARY SWITCH SW02 SLIM1 WAY đ ߢߤߨ Ɗ७७ đ ߢߥߧ Ɗ७७ sw02 SLIM DUCT MSP DU...

Page 23: ...19 as OFF status ࣞ Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the same time The procedure of setting option Operation Indication Step1 1 Remove the batteries from the remote controller 2 Insert batteries while pressing High Temp Button and Low Temp Button Step 2 1 Press Low Fan button to enter SEG2 value 2 Press High Fan b...

Page 24: ... 8 Press Mode button to be changed to Cool mode in the OFF status 1 Press Low Fan button to enter SEG16 value 2 Press High Fan button to enter SEG17 value Step 9 Press Mode button to be changed to DRY mode in the OFF status 1 Press Low Fan button to enter SEG18 value 2 Press High Fan button to enter SEG20 value Step10 Press Mode button to be changed to FAN mode in OFF status 1 Press Low Fan button...

Page 25: ...icationand details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 9 100 digit 0 9 10 digit 0 9 A single digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE Setting RMC address Group channel 16 Group address Indication and Details Indication Details Indication Details In...

Page 26: ...l Indication and Details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 0 2 0 0 0 No use 0 1 Use Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE Master Slave Indication and Details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 1 0 0 0 0 0 Slave 1 Master Op...

Page 27: ...ode set the set temperature of the indoor unit to the highest one Check if each indoor unit operates normally and then also check if all indoor units operate normally together ࣞ Check both of the Cool and Heat modes About 20 minutes afterthe air conditioner is started check the temperature difference between the air inlet and outlet of the indoor unit If the temperature difference is largerthan th...

Page 28: ...ately start provided 3 minutes have elapsed since the last stop 2 Release the valve caps on High and Low pressure side 3 Use L wrench to close the valve on the high pressure side 4 After approximately 2 minute close the valve on the low pressure side 5 Stop operation of the air conditioner by pressing the Power button on the indoor unit or remote control 6 Disconnect the pipes A Gas B Liquid Reloc...

Page 29: ...15 88 30 to 35 1 N m 10 kgf cm NOTE Do not apply excessive force to the stop valve and always use special instruments Otherwise the stopping box can be damaged and the back sheet can leaks If the watertight sheet leaks turn the axis back by half tighten the stopping box then check the leakage again If there is no leakage any more tighten the axis entirely Closing the stop valve 1 Remove the cap 2 ...

Page 30: ... LED RED GRN RED GRN YEL K3 K1 A B Display B part Error Code Explanation Remark Red Green Yellow E201 The number of indoor unit mismatched E202 Communication errer between the outdoor and indoor unit E203 Outdoor communication error between main micom and inverter micom E206 Outdoor communication error beween main micom and hub micom E221 Outside temperature sensor error Short Open E237 Condensert...

Page 31: ... Inverter compressor starting failure 5 times E462 Compressortrip by input current control mode PFC over current E463 Compressortrip by OLP temperature control mode E464 DC Peak system error Over current E465 CompressorVlimit Error E466 Inverter DC link Voltage error under150V over 410V E483 ࢩǮ Uʪϩʪʀϩ UA ø ͱЭʪθ Эͱ ϩɇ ʪ kθθͱθऌ E467 Abnormal compressor running Compressor Rotation Error E468 Current ...

Page 32: ...G ELECTRONICS CO LTD 107 Hanamsandan 6beon ro Gwangsan gu Gwangju si Korea 62218 Samsung Electronics Service Department PO Box12987 Blackrock Co Dublin Ireland or Blackbushe Business Park Yateley GU46 6GG UK ...

Reviews: