Samsung AJ NB1DEH Series Installation Manual Download Page 10

10

Installation Procedure

English

Installation Pr

oc

edur

e

Step 7  Connecting the assembly pipes 

to the refrigerant pipes

There are two refrigerant pipes of different diameters :

•  A smaller one for the liquid refrigerant.
•  A larger one for the gas refrigerant. The inside of 

copper pipe must be clean and has no dust.

Remove the pinch pipe on the pipes and connect the 
assembly pipes to each pipe, tightening the nuts, first 
manually and then with a torque wrench, a spanner 
applying the following torque.

Torque 

wrench

Flare nut

Spanner

Union

1

2

3

3

Outer Diameter (mm)

ƟͱθαЇʪ࣑Ęࡻ͔࣒

Ø6.35

14 to 18

Ø9.52

34 to 42

Ø12.70

49 to 61

Ø15.88

68 to 82

(1 N

m = 10 kgf

cm)

  NOTE

•  If the pipes must be shortened, see 

Step 6  Cutting 

and flaring the pipes

 on page 

9

.

Be sure to use an insulator thick enough to cover the 
refrigerant tube to protect the condensate water on 
the outside of the pipe falling onto the floor and to 
improve the efficiency of the unit.

Cut off any excess foam insulation.

Make sure that there are no cracks or waves on the 
bent area.

It would be necessary to double the insulation 
thickness (10 mm or more) to prevent condensation 
even on the insulator when if the installed area is 
warm and humid.

Do not use joints or extensions for the pipes 
connecting the indoor and outdoor units. The only 
permitted connections are those for which the units 
are designed.

  CAUTION

•  Connect the indoor and outdoor units using pipes 

with flared connections (not supplied). For the lines, 
use insulated, unwelded, degreased and deoxidized 
copper pipe (Cu DHP type to ISO 1337 or UNI EN 12735-
1), suitable for operating pressures of at least 4.2 MPa 
and for a burst pressure of at least 20.7 MPa. Copper 
pipe for hydro-sanitary applications is completely 
unsuitable.

•  For sizing and limits (height difference, line length, 

max. bends, refrigerant charge, etc.) see the outdoor 
unit installation manual.

•  All refrigerant connection must be accessible, in order 

to permit either unit maintenance or removing it 
completely.

•  If the pipes require brazing, make sure that oxygen 

free nitrogen (OFN) is flowing through the system.

•  Nitrogen blowing pressure range is 0.02 to 0.05 MPa.

Summary of Contents for AJ NB1DEH Series

Page 1: ...Airconditioner Installation manual AJ NB1DEH Thank you for purchasing this Samsung air conditioner Before operating this unit please read this manual carefully and retain it for future reference...

Page 2: ...Cutting and flaring the pipes Step 7 Connecting the assembly pipes to the refrigerant pipes Step 8 Performing the gas leak test Step 9 Insulating the refrigerant pipes Step10 Installing the drain hos...

Page 3: ...sedforlaundry Donotusetheunitsifdamaged Ifproblemsoccur switch theunitoffanddisconnectitfromthepowersupply In orderto prevent electric shocks fires or injuries always stop the unit disable the protect...

Page 4: ...ays verify that all connections complywith the standards applicable to the installation of air conditioners Devices disconnected from the power supply should be completely disconnected in the conditio...

Page 5: ...a ceiling that can support its weight Maintain sufficient clearance around the indoor unit Before installing the indoor unit be sure to check whetherthe chosen location is well drained The indoor uni...

Page 6: ...ling 1150 Ceiling opening dimension 249 Space of suspension bolts 440 Ceiling opening dimension 1036 Space of suspension bolts Model AJ026NB1DEH AJ035NB1DEH Chassis Medium Net dimension W D H mm 970 X...

Page 7: ...ty is over 80 you must apply an extra10 mm thick polyethylene insulation or a similartype of insulation to the body of the indoor unit Cut away the part where pipes are pulled out forthe insulating wo...

Page 8: ...t space in the false ceiling to allow access for maintenance or repairs to the drainage pipe connection the refrigerant pipe connection orto remove the unit if necessary 5 Hang the indoor unit to the...

Page 9: ...l and pipe holder 2 If you wish to shorten the pipes cut them with a pipe cutter ensuring that the cut edge remains at a 90 angle to the side of the pipe Referto the illustrations below for examples o...

Page 10: ...4 Make sure that there are no cracks orwaves on the bent area 5 It would be necessary to double the insulation thickness 10 mm or more to prevent condensation even on the insulatorwhen if the install...

Page 11: ...rain hose avoiding compressing the insulation too much 3 Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit 4 The pipes and electrical cables connecting the indoo...

Page 12: ...s below use the same insulation that is used for high humidity conditions Geological condition High humidity locations such as shorelines hot springs lake or riversides and ridges when part of the bui...

Page 13: ...300 mm from the drain hose port If it is raised higherthan 550 mm there may be water leaks Band joint 300 mm or less 20 mm or more Ceiling 1 100 or more 300 to 550 mm Drain hose Do not give the hose...

Page 14: ...nstall airvent if the horizontal drain pipe is in proper slope Step11 Performing the drainage test 1 Do a leak test at the connection part of the flexible hose and the drain pipe a Connect a general h...

Page 15: ...is completed and the condensed water remains on the drain pan remove the water Step12 Connecting the powerand communication cables CAUTION Always rememberto connect the refrigerant pipes before perfor...

Page 16: ...inum polyester braid copper of FROHH2R type Connect the power cable to the auxiliary circuit breaker An all pole disconnection from the power supply must be incorporated in the fixed wiring Step13 Opt...

Page 17: ...n The compression dimension should be 8 0 Compression dimension After compressing it pull both sides of the wire to make sure it is firmly pressed Compress it 4 times 5 mm Compress it 4 times 5 mm Met...

Page 18: ...ies from the remote control and then insert them again b While holding down the High Temp and Low Temp buttons simultaneously insert the batteries into the remote control c Make sure that you are ente...

Page 19: ...y 3 Set the SEG4 and SEG5 values a Set the SEG4 value by pressing the Low Fan button repeatedly until the value you want to set appears on the remote control display SEG4 b Set the SEG5 value by press...

Page 20: ...h Fan button repeatedly until the value you want to set appears on the remote control display When you press the Low Fan or High Fan button values appear in the following order SEG10 8 Press the Mode...

Page 21: ...r SEG15 12 Press the Mode button Cool and Off appear on the remote control display 13 Set the SEG16 and SEG17 values a Set the SEG16 value by pressing the Low Fan button repeatedly until the value you...

Page 22: ...e remote control display SEG21 b Set the SEG22 value by pressing the High Fan button repeatedly until the value you want to set appears on the remote control display When you press the Low Fan or High...

Page 23: ...Power button again 5 Check whetherthe air conditioner operates in accordance with the option values you have set a Reset the indoor unit by disconnecting and then reconnecting the power cable of the i...

Page 24: ...No Main address 0 9 100 digit 0 9 10 digit 0 9 A single digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE Reserved Setting RMC address Reserved Group channel 1...

Page 25: ...output of external control S Plasma ion Buzzer Control Hours of filter usage SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 3 Individual control with remote control Heating setting compensation offset Dew remov...

Page 26: ...n SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation Page Use of drain pump Reserved Reserved Reserved Remote control Indication and details Indication Details Indication Details Indication Details 1 0 Disu...

Page 27: ...Default 1 0 Default Maintain blade status in wind free mode 0 Disuse 2 channel 2 1 1 Standard Turn out in 30 min without motion 2 Turn out in 60 min without motion 3 channel 3 3 Turn out in 120 min wi...

Page 28: ...tails 0 D Option type 0 to F Tens position value 0 to 9 Units position value 0 to 9 New value 0 to F Example Changing the Buzzer control SEG17 option of the installation options to1 disuse Option SEG1...

Page 29: ...Short or Open E122 X X X Error on Eva out sensor Short or Open E123 Indoorfan error E154 X X X X Error on outdoortemperature sensor Short or Open E221 X X X Error on cond sensor E237 Error on discharg...

Page 30: ...oor sump down_1 prevetion control E413 Compressor down due to low pressure sensor prevention control_1 E410 Simultaneous opening of cooling heating MCU SOLvalve 1st detection E180 Simultaneous opening...

Page 31: ...31 English Appendix Memo...

Page 32: ......

Reviews: