Troubleshooting
The following error indications appear on the fan coil unit display when a problem occurs.
Error detection and restart
• If an error occurs during operation, the display blinks to indicate an error and all operations except for the display
operation stop.
• When you restart the product using the remote control and the switch, a normal operation starts, and then the
detected error mode is determined.
Display indications at error detection
Condition of the fan coil unit
Error code
Fan coil unit display indications
Slim 1 way cassette
Blue Yellow green
Short- or open-circuit error of the room temperature sensor
E121
X
◑
◑
X
X
1. Short- or open-circuit error of the EVA IN sensor
E122
◑
X
◑
X
X
2. Short- or open-circuit error of the EVA OUT sensor
E123
Error of the fan
E154
X
◑
X
1. Error that there is no communication between FCU relays for
2 minutes
E101
X
X
◑
◑
X
2. Communication error received from the relay
E102
3. Error that relay tracking continued for 3 minutes
E202
4. Communication error that the actual number of installed
FCUs differs from the number detected by tracking
E201
5. Error due to duplicated communication addresses
E108
6. Error that communication addresses are not yet determined
E109
Communication errors other than the errors listed above
Errors detected by the self-diagnosis
X
X
◑
◑
◑
ߢࢋkθθͱθͱ˙иɇϩʪθϩʪ͔ΧʪθɇϩЇθʪθ̈ϑʪΧθʪЭʪ͝ϩ̈ͱ࢘͝Ɵ˵ʪΧθͱʒЇʀϩ
ϑϩͱΧϑɇϩ˵̈˝˵иɇϩʪθϩʪ͔ΧʪθɇϩЇθʪɇɵͱЭʪߧߦঐࢋ
E128
2. Thermal fuse open error
E198
Second detection of the float switch error
E153
X
X
X
◑
◑
EEPROM error
E162
◑
◑
◑
◑
◑
EEPROM option error
E163
◑
◑
◑
◑
◑
◑
: Blinking
X
: Off
NOTE
• If you stop the operation while an error is being indicated. all the indicators are turned off.
• In case of re-operation, a normal operation starts, and then the product reevaluate the detected error and displays it
again if required.
• If the E108 error occurs, set the FCU address again, and then reset the system.
Example) If the fan coil units 1 and 2 are set to the address 5, the fan coil unit 1 is changed from 1 to 5, and E108 and
A002 are displayed on the fan coil unit 2.