Installation Procedure
Installation Procedure
Step 1 Checking and preparing
accessories
The following accessories are supplied with the product.
Pattern sheet (1)
Drain hose (1)
Insulation pipe
(Liquid side1, gas side1)
Insulation drain hose (1)
Manual (2)
Air vent hose (1)
Cable-tie (6)
Clamp (1)
Step 2 Choosing the installation
location
Installation location requirements
• Air must be distributed optimally.
• The passage of air must not be disturbed.
• Condensation water must be drained easily.
• The support structure must be strong enough
to support the weight of the fan coil unit. (If the
structure is not strong, the fan coil unit may fall off,
leading to personal injury.)
• The ceiling must not be significantly sloped.
• There must be a sufficient space for maintenance and
service.
• The power and communication cables of the fan
coil unit must be at least 1 m away from electronic
appliances such as televisions. (Occasionally, more
distance may be required.)
Reinforcing the ceiling
Make sure that the ceiling is sufficient to support the
weight of the fan coil unit. If dangerous, reinforce the
ceiling with foundation bolts before installing the fan
coil unit.
Spacing requirements
1500 or
more
1500 or m
ore
1500
or m
ore
1500
or m
ore
(Unit: mm)