4. Using a crimping tool, compress the two points and flip it over and compress another two points in the same location.
- The compression dimension should be 8.0.
- After compressing it, pull both sides of the wire to make sure it is firmly pressed.
Compression
dimension
f
f
Method 1
f
f
Method 2
Compress it 4 times.
5 mm
Compress it 4 times.
5 mm
5. Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape.
Three or more layers of insulation are required.
f
f
Method 1
f
f
Method 2
40 mm
Insulation tape
Insulation tape
35 mm
6. Apply heat to the contraction tube to contract it.
Contraction tube
7. After tube contraction work is completed, wrap it with the insulation tape to
finish.
Insulation tape
• Make sure that the connection parts are not exposed to outside.
• Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials
that have the same level of withstand voltage with the power cable. (Comply with the local regulations on
extensions.)
CAUTION
• In case of extending the electric wire, please DO NOT use a round-shaped pressing socket.
- Incomplete wire connections can cause electric shock or a fire.
WARNING