8
Samsung Electronics
2-2 Product Specifications
2-2-1 Outdoor Unit
Item
AEX160EDGHA
AEX140EDGHA
AEX125EDGHA
3phase 16kW
3phase 14kW
3phase 12.5kW
Image
Outdoor unit
Capacity (95%
↑
)
Heating 1
W
16,000
14,000
12,500
Heating 2
W
15,000
13,000
11,500
Cooling 1
W
17,400
16,200
15,000
Cooling 2
W
13,300
12,300
11,300
POWER CONSUMPTION
(110%
↓
)
Heating 1
W
3,720
3,110
2,660
Heating 2
W
4,410
3,710
3,195
Cooling 1
W
6,000
5,150
4,350
Cooling 2
W
5,420
4,730
4,110
Running Current
(110%
↓
)
Heating 1
A
5.8
4.9
4.2
Heating 2
A
6.9
5.8
5.0
Cooling 1
A
9.4
8.1
6.8
Cooling 2
A
8.5
7.4
6.4
Power Supply
Ø,V,Hz
3 / 380-415 / 50
3 / 380-415 / 50
3 / 380-415 / 50
COP/EER (95%
↑
)
Heating 1
W/W
4.30
4.50
4.70
Heating 2
W/W
3.40
3.50
3.60
Cooling 1
W/W
2.90
3.15
3.45
Cooling 2
W/W
2.45
2.60
2.75
Refrigerant Charge
g, type
2,800 R410A
2,800 R410A
2,800 R410A
Set Dimensions
(W*H*D)
Net
mm
940X1,420X330
940X1,420X330
940X1,420X330
Gross
mm
995X1,548X426
995X1,548X426
995X1,548X426
Weight (Net/Gross)
kg
98 / 108
98 / 108
98 / 108
Noise
Cooling
Cond.1/2
dB(A)
61 60 59
Heating
Cond.1/2
dB(A)
60 59 59
Operation
range
Cooling
℃
10~46
10~46
10~46
Heating
℃
-20~35
-20~35
-20~35
RC160MHXGA_SM_E_34513A(1)_1~3.indd 8