ENGLISH-48
Field setting mode
Others : Code 50
✴✴
Field Setting Value
Main Menu &
Code
Sub Menu Function
Description
Sub Code Default
Min
Max
Step Unit
Others Code
50
✴✴
Outing
Water Out Temp for Cooling
✴✴
11
25
5
25
1
˚C
Room Temp for Cooling
✴✴
12
30
18
30
1
˚C
Water Out Temp for Heating
✴✴
13
15
15
55
1
˚C
Room Temp for Heating
✴✴
14
16
16
30
1
˚C
Auto Cooling WL1 Temp
✴✴
15
25
5
25
1
˚C
Auto Cooling WL2 Temp
✴✴
16
25
5
25
1
˚C
Auto Heating WL1 Temp
✴✴
17
15
15
55
1
˚C
Auto Heating WL2 Temp
✴✴
18
15
15
55
1
˚C
Target Tank Temp
✴✴
19
30
30
70
1
˚C
DHW Saving Mode
Temp Difference
✴✴
21
5
0
40
1
˚C
Power Peak Control
Application
✴✴
41
0(No)
0
1(Yes)
-
-
Select forced off parts
✴✴
42
0(All)
0
2
1
-
Using input voltage
✴✴
43
1(High) 0(Low)
1
-
-
Frequency Ratio Control
✴✴
51
0(No)
0
1(Yes)
-
-
Outing Mode (Hot Key of Wired Remote Controller)
•
All the target temperatures – space heating and cooling, water law, DHW, Room temperature – are set to the values
defined in the above table under the holiday mode (outing hot key)
•
With the lowered target temperatures (FSV #5011 ~ #5019), the system operates normally.
NOTE
Economic DHW Heating
•
DHW heating only by the heat pump to save energy. Target DHW temperature is lower than the temperature set by user.
The temperature difference is defined by FSV #5021. (default: 5°C)
- If user sets the temperature 45°C, the system sets the target temperature 40°C with the default setting.
Peak Power Control
•
If users make contracts with local electric power company for limiting the amount of power consumption when a surge in
power usage, users can set FSV of “Forced off”.
•
According to FSV (#5041), Default is Non-usage. And According to FSV (#5042), If input is “0(default)”, all the thermal
applications are unavailable while external contacts is high.
If input is “ 1”, Only the booster heater is available.
If input is “ 2”, Only the back up heater is available.
•
Applying the control when power voltage of input contact is high is default. According to FSV (#5043), it is available to
adopt this logic in low condition exceptionally.
•
When applying to this logic, SAMSUNG controller come to get “Thermo off” condition for all operation.
•
If not used for a long time, anti-freeze fluid shall be used for preventing damage to the unit in cold condition.