ENGLISH-23
02
INST
ALL
ATION
No.
Note
No.
Note
No.
Note
①
FR Control
CNS2(Green)
⑥
Room Sensor
CNS044(White)
⑪
TB-C (Black)
F1-F2:COMM1 (IN-OUT
COMM)
INPUT/OUTPUT, DC, 10 mA
②
Flow Switch
CNS041(Blue)
⑦
Smart Grid
CNS046(Red)
⑫
CNS1(White)
1:Signal
3:Gnd
③
Water Tank
CNS042(Yellow)
⑧
CNS043(White)
1-2:Heater Out
3-4:Eva Out
5-6:Eva in
7-8:Water Out
9-10:Water In
⑬
Boost Heater TB-A1 (Black)
L-N, OUTPUT AC
④
Heater Out(Mono)
CNS047(Black)
⑨
EEV
CNS062(Blue)
⑭
Main Power TB-A(Black)
L-N, INPUT, AC
⑤
Mixing Sensor
CNS045(Blue)
⑩
TB-C (Black)
F3-F4:COMM2 (Wired Remocon)
INPUT/OUTPUT, DC, 210 mA(per each
controller)
⑮
Terminal No .
Function
Input /output
Max . Current
Description
Remark
B1/B6
Water Pump
AC 230V output
0 .5 A
Water INV . pump operation (maximum
input power of pump 100W) . (B6 : Lived) Mandatory
B2/B3/B5
Mixing valve
AC 230V output
22 mA
Mixing Valve operation(B2: CW, B3: CCW)
Option
B4/B5
Backup Boiler AC 230V output
10 mA
Signal output for Backup Boiler(B5:
Neutral)
Option
B7/B8
Water Pump
AC 230V output
0 .5 A
Additional Water pump operation
(maximum input power of pump 100W)
(B8 : Lived)
Option
B9/B10/B11/
B12
2Way valve #1 AC 230V output
22 mA
2 Way Valve operation for Zone#1 (UFH)
(B9 : NO, B10 : NC, B11: Neutral, B12: Lived)
Option
B13/B14/
B11/B12
2Way valve #2 AC 230V output
22 mA
2 Way Valve operation for Zone#2 (FCU)
(B13 : NO, B14 : NC, B15: Neutral, B16:
Lived)
Option
B15/B16/
B17/B18
3Way valve
AC 230V output
22 mA
3 Way Valve operation for DHW
(B17 : NO, B18 : NC, B15: Neutral, B16:
Lived)
Option
B19/B20
Thermostats
AC 230V output
22 mA
Power to external thermostat(s)
(B20: Lived)
Option
B21/B22
Thermostat 1
AC 230V input
22mA
Thermostat for zone#1 (UFH)
Cooling(B21)/Heating(B22) Signal
Option
B23/B24
Thermostat 2
AC 230V input
22mA
Thermostat for zone#2 (FCU)
Cooling(B23)/Heating(B24) Signal
Option
B25/B26
Solar Pump
AC 230V input
10 mA
Signal input from Solar Pump / DHW
Thermostat (B26 :Lived)
Option
⑯
CNS304(RED)
F3-F4:COMM2 (Wired Remote controller)
⑰
CNS3(Black)
1:Signal
2:Gnd