Code 30∗∗ : User’s options for domestic hot water(DHW) tank heating
3011 : Application of DHW tank in user’s system
302∗ : Heat pump variables for tank temp. control and combination with booster heater
303∗ : Booster heater variables for combination with heat pump
304∗ : Periodical disinfection heating of water tank
305∗ : Off timer for power DHW mode by Forced DHW of wired remote controller
3061 : “1”Combination of external field solar panel for with heat pump for DHW heating
”2”Application of DHW Tank thermostat in user’s system
307∗ : Default direction of the DHW valve or Zone #1, #2 valve
When the 3way valve is applied to DHW Valve terminal block instead of 2way valve,
default direction is Space Heating (Room)
Field Setting Value
Main Menu
& Code
Sub Menu Function
Description
Sub
Code Default
Min
Max
Step
Unit
DHW Code
30∗∗
Domestic Hot Water
Tank
Application
∗∗11
0 (No)
0
2
1
-
Heat Pump
Max Temp
∗∗21
50
45
50
1
˚C
Stop
∗∗22
2
0
10
1
˚C
Start
∗∗23
5
5
20
1
˚C
Min. Space
heating
operation time
∗∗24
5
1
20
1
min
Max. DHW
operation time
∗∗25
30
5
95
5
min
Max. Space
heating
operation time
∗∗26
3
0.5
10
0.5
hour
Booster Heater
Application
∗∗31
1 (On)
0(Off)
1
-
-
Delay Time
∗∗32
20
20
95
5
min
Overshoot
∗∗33
0
0
4
1
˚C
Disinfection
Application
∗∗41
1 (On)
0(Off)
1
-
-
Interval
∗∗42
Fri (5) Sun(0) All (7)
1
day
Start Time
∗∗43
23
0
23
1
o'clock
Target Temp
∗∗44
70
40
70
5
˚C
Duration
∗∗45
10
5
60
5
min
Max time
∗∗46
8
1
24
1
hour
Forced DHW operation
Timer OFF
Function
∗∗51
0 (No)
0
1 (Yes)
-
-
Timer Duration
∗∗52
6
3
30
1
(x10)
min
Solar Panel/DHW
Thermostat
H/P Combination
∗∗61
0 (No)
0
2
1
-
Direction of DHW valve
DHW Tank
∗∗71
0
(Room)
0
1
(Tank)
-
-