background image

Air to Water Heat Pump

Installation manual

Tank Integrated Hydro Unit AE***RNWS** / AE***RNWM**

 

• Thank you for purchasing this Samsung Product.

 

• Before operating this unit, please read this installation manual carefully and retain it for future 

reference.

DB68-08367A-07

Summary of Contents for AE040RXED Series

Page 1: ...allation manual Tank Integrated Hydro Unit AE RNWS AE RNWM Thank you forpurchasing this Samsung Product Before operating this unit please read this installation manual carefully and retain it forfuture reference DB68 08367A 07 ...

Page 2: ...et USB cable should not be disposed of with other household waste at the end of their working life To prevent possible harm to the environment or human health from uncontrolled waste disposal please separate these items from other types of waste and recycle them responsibly to promote the sustainable reuse of material resources Household users should contact either the retailer where they purchase...

Page 3: ...ts set forth in the Operating limits table included in the manual shall immediately invalidate the warranty f f Do not use the units if damaged If problems occur switch the unit off and disconnect it from the power supply f f In order to prevent electric shocks fires or injuries always stop the unit disable the protection switch and contact SAMSUNG s technical support if the unit produces smoke if...

Page 4: ... refrigerant other than R 32 water etc enter the pipings f f When mechanical ventilation is required ventilation openings shall be kept clear of obstruction f f For disposal of the product follow the local laws and regulations f f Do not work in a confined place f f The work area shall be blocked f f The refrigerant pipings shall be installed in the position where there are no substances that may ...

Page 5: ...ear the charging area Ignition sources free f f Make sure to store the units in a place without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater f f The service engineers shall not use any ignition sources with the risk of fire or explosion f f Potential ignition sources shall be kept away from the work area where the flamma...

Page 6: ...ng it is recommended to remove the entire refrigerant f f When transferring refrigerant into cylinders make sure that only the refrigerant recovery cylinders are used f f All cylinders used for the recovered refrigerant shall be labelled f f Cylinders shall be equipped with pressure relief valves and shut off valves in a proper order f f The recovery system shall operate normally according to the ...

Page 7: ...oblem POWER SUPPLY LINE FUSE OR CIRCUIT BREAKER f f Always make sure that the power supply is compliant with current safety standards Always install the air to water heat pump in compliance with current local safety standards f f Always verify that a suitable grounding connection is available f f Verify that the voltage and frequency of the power supply comply with the specifications and that the ...

Page 8: ... Name Split AE040RXED AE060RXED AE090RXED Mono AE050RXYD AE080RXYD AE120RXYD AE160RXYD Indoor units Tank Integrated Hydro Units Model Name Split AE200RNWSEG AE260RNWSEG AE200RNWSEG AE260RNWSEG AE260RNWSGG Mono AE200RNWMEG AE200RNWMEG AE260RNWMEG AE260RNWMGG AE200RNWMEG AE260RNWMEG AE260RNWMGG ...

Page 9: ...clip of zone sensor and mixing valve 3 Cable tie for zone sensor and mixing valve 6 Aluminum tape for zone sensor and mixing valve 3 Rubber tape for zone sensor and mixing valve 3 Insulator for zone sensor and mixing valve 3 Connector wire PV Control Peak power control 1x2 m RED 1 Tube secondary 1 only for 260 LTank model Gasket 1 only for 260 LTank model Drain plug out 1 Cap drain 2 ...

Page 10: ...et mm 28 28 28 28 28 28 Connection Pipe Domestic Hotwater Inlet mm 22 22 22 22 22 22 Outlet mm 22 22 22 22 22 22 Connection Pipe Monobloc Outdoor Inlet mm 28 28 28 Outlet mm 28 28 28 WaterPump ModelName UPMM25 9 5 UPMM25 9 5 UPMM25 9 5 UPMM25 9 5 UPMM25 9 5 UPMM25 9 5 Maker Grundfos Grundfos Grundfos Grundfos Grundfos Grundfos Max Vol Flow m3 h 5 5 5 5 5 5 5 5 5 5 5 5 ElectricHeater InputPower W 2...

Page 11: ...installer s responsibility SAMSUNG shall not be held liable for any damage resulting from not observing this rule SAMSUNG do not provide specific water system components such as Pressure relief valve Air vent valve buffer tank and etc Installers and end users shall consider how to install the above designated components in overall water system depending on the installation conditions If the compon...

Page 12: ...eader Under Floor Heating Coils Radiators or Convectors 45 C 35 C Water pump 2 Water pump 1 Outdoor Indoor Mechanical Room Tw2_z1 Tw2_z2 ColdWater HotWater We control only the on off signal of backup boiler according to outdoor temperature Backup boiler should be installed with own device according to the field condition Samsung has not responsible for performance and stability of backup boiler Wa...

Page 13: ...nut Refrigerant pipe ø6 35 1 4 Flare nut Hot water outlet ø22 Straight pipe Secondary return ø22 Straight pipe 260L option Cold water inlet ø22 Straight pipe Space heating outlet ø28 Straight pipe Space heating inlet ø28 Straight pipe T P valve 7bar 90 C Pressure relief valve 3bar BSPP 1 2 3way valve ...

Page 14: ...t thermistor Eva out thermistor Water in thermistor Tank thermistor Heater thermistor Water pump Water tank 200L 260L Manometer 0 4bar S D converter Control box Booster heater 3kW Booster heater thermostat Flow sensor Expasion vessel 8L Pre charge gas 0 1MPa N2 BSPP 3 8 Strainer Tank drain valve Drain port Primary circuit Main components ...

Page 15: ... pipe Flow from heat pump ø28 Straight pipe Hot water outlet ø22 Straight pipe Secondary return ø22 Straight pipe 260L option Cold water inlet ø22 Straight pipe Space heating outlet ø28 Straight pipe Space heating inlet ø28 Straight pipe T P valve 7bar 90 C Pressure relief valve 3bar BSPP 1 2 3way valve ...

Page 16: ...8 Tank thermistor Heater thermistor Water pump Water tank 200L 260L Manometer 0 4bar S D converter Control box Booster heater 3kW Booster heater thermostat Flow sensor Expasion vessel 8L Pre charge gas 0 1MPa N2 BSPP 3 8 Strainer Tank drain valve Drain port Primary circuit Main components ...

Page 17: ... Manometer Water in Water out Temperature pressure relief valve Drain Tundish T_tank T_w3 T_w2 T_w1 Heating T_eva out T_eva in Booster heater 3kW MONO 3 G3 KIT 3 Way V V Backup heater 2kW PWM Pump Expansion Vessel 8L Flow sensor Pressure Relief v v Air Vent Manometer Water in Water out Temperature pressure relief valve Drain Tundish T_tank T_w3 Booster heater 3kW ...

Page 18: ...old water inlet Ø22 T1 0 Straight pipe Space heating outlet Ø28 T1 2 Straight pipe Space heating inlet Ø28 T1 2 Straight pipe No Mono Size type Mono outdoor outlet Ø28 T1 2 Straight pipe Mono outdoor inlet Ø28 T1 2 Straight pipe Hot water outlet Ø22 T1 0 Straight pipe Secondary return 260L option Ø22 T1 0 Straight pipe Cold water inlet Ø22 T1 0 Straight pipe Space heating outlet Ø28 T1 2 Straight ...

Page 19: ...e there is no risk of leakage of flammable gases f f There is a provision for condensate drain and pressure relief valve blow off f f The wall for installation is a flat vertical and non combustible wall capable of supporting the operation weight of the unit Installation space f f Ensure to leave the appropriate space as indicated in the drawing f f Installation site should be secured with adequat...

Page 20: ... the fork does not damage the indoor unit f f When moving the Indoor unit be care the damage of indoor unit by impact Do not remove the packaging until Indoor unit reach the final installation location f f When adjusting the exact location of the Indoor unit use the handles A minimum of two people should lift the unit by the handles Do not grasp the pipe Fork lift Handle Handle Bracket f f Remove ...

Page 21: ...nk hydro unit installation is completed install an anti vibration pad t 20 mm or more or an anti vibration frame vibration transmissibility 5 and below to prevent vibration of the outdoor unit from transferring to the base ground Fixed Bracket Level Controller DrainWork f f In the cooling operation defrost water may be produced from the pipes or tank f f Produced defrost water must be drained thro...

Page 22: ... pipe O D Liquid pipe O D Indoor unit 15 88 mm 5 8 inch 6 35 mm 1 4 inch Outdoor unit 15 88 mm 5 8 inch 6 35 mm 1 4 inch Outer diameter mm inch Torque N m ø6 35 1 4 14 18 ø9 52 3 8 34 42 ø12 70 1 2 49 61 ø15 88 5 8 68 82 ø19 05 3 4 100 120 When connecting the refrigerant pipes always use 2 wrenches spanners for tightening or loosening nuts If not piping connections can be damaged CAUTION Liquid pi...

Page 23: ...hydro unit Please check that air vent valve is not overtightened so the air vent valve can release any air out of the system during system operation Split Hydro unit No Name Size Conncetions Hot water outlet ø22 T1 0 Copper Crimp pipe fitting or welding Sencondary return ø22 T1 0 Copper Cold water inlet ø22 T1 0 Copper Space heating outlet ø28 T1 2 Copper Space heating inlet ø28 T1 2 Copper Mono H...

Page 24: ...tem After installations Commissioning should be performed by qualified representatives Unless flushing and air purging works are performed adequately It might result in malfunctions Flushing unit or purging cart 3 G3 KIT 3 Way V V Backup heater 2kW PWM Pump HX_PHE Expansion Vessel 8L Flow sensor Pressure Relief v v Air Vent Manometer Water in Water out Temperature pressure relief valve Service por...

Page 25: ... 30 40 50 60 70 80 90 100 10 15 20 25 30 35 40 45 50 Flow l min ESP kPa AE RNWM 0 10 20 30 40 50 60 70 80 90 100 10 15 20 25 30 35 40 45 50 Flow l min ESP kPa The values shown in the dotted graph reflect pressure drops in the mono outdoor unit heat exchanger When ESP is not enough additional pump should be installed In this case install the PWM control external type pump Heating type additionally ...

Page 26: ...eatingType Case 2 AC pump The maximum number of additional pump installation is one AC pumps Input power 100W 1 Power supply AC Pump B8 Live additional pump B7 Neutral additional pump L N M C PCB Terminal block Neutral additional pump Live additional pump B7 B8 Pump Power The maximum allowable current that this terminal block can supply for the additional water pump is 0 1 A CAUTION ...

Page 27: ...lation height differencea Water volume 220 Litres 220 Litres 7 m No pre pressure adjustment required Actions required Pre pressure must be decreased calculate according to Calculating the pre pressure of the expansion vessel Check if the water volume is lower than maximum allowed water volume 7 m Actions required Pre pressure must be increased calculate the appropriate value following by Calculati...

Page 28: ...t while charging water The back up heater vessel shall be full of water before heater is turned on Confirm if the vessel is empty by opening the pressure relief valve of hydro unit OK if water is flowing out It is recommended to install the make up water assembly to feed small quantities of water to the system automatically replacing the minor water losses and maintaining the system pressure This ...

Page 29: ...censed electrician Use a dedicated power supply All power connections must be protected from dew condensation by thermal insulation The system shall be earthed Do not earth the unit to a utility pipe surge absorber or telephone earth Incomplete earth may cause electrical problems CAUTION Layout of PCB 1 3 6 5 4 11 14 12 13 2 32 23 17 16 24 19 21 22 15 18 10 9 31 7 8 20 Micom 2 WIRE COMM SMPS circu...

Page 30: ...Pump output FSV 4061 1 AC OUTPUT 11 N AC OUTPUT 12 L AC OUTPUT 13 2WAYVALVE2_NO L AC OUTPUT 14 2WAYVALVE2_NC L Zone2Water Pump output FSV 4061 1 AC OUTPUT 15 N AC OUTPUT 16 L AC OUTPUT 17 3WAYVALVE_NO L AC OUTPUT 18 3WAYVALVE_NC L AC OUTPUT 19 N AC OUTPUT 20 L AC OUTPUT 21 THERMOSTAT1_C L AC INPUT 22 THERMOSTAT1_H L AC INPUT 23 THERMOSTAT2_C L AC INPUT 24 THERMOSTAT2_H L AC INPUT CNP501 3WAYVALVE ...

Page 31: ...FR CONTROL PWM SIGNAL DIGITAL OUTPUT 2 GND DIGITAL GROUND TB C COMMUNICATION DC 12V 1 COM1 F1 RS485 COMM 2 COM1 F2 3 V1 DC 12V DC OUTPUT 4 V2 GND DIGITAL GROUND 5 COM2 F3 WIRED REMOTE CONTROLLER 6 COM2 F4 CNS900 EEPROM 1 GND DIGITAL GROUND 2 NO CONNECT 3 DC 5V DC OUTPUT 4 EEPROM_SELECT DC SIGNAL 5 EEPROM_SO DC SIGNAL 6 EEPROM_SI DC SIGNAL 7 EEPROM_CLK DC SIGNAL CNS047 HEATER SENSOR 1 HEATERTEMP 10...

Page 32: ...GITAL INPUT 4 GND DIGITAL GROUND 3 EVA INTEMP 10kΩ 25 C DIGITAL INPUT 6 GND DIGITAL GROUND 7 WATER OUTTEMP 10kΩ 25 C DIGITAL INPUT 8 GND DIGITAL GROUND 9 WATER INTEMP 10kΩ 25 C DIGITAL INPUT 10 GND DIGITAL GROUND CNS057 FLOW SENSOR 1 DC 5V DC OUTPUT 2 FLOW SENSOR SIGNAL DIGITAL INPUT 3 GND DIGITAL GROUND 4 NO CONNECT CNS062 CNS063 EEV SPLIT MONO Not use 1 4 EEV CONTROL PWM SIGNAL DC OUTPUT 5 DC 12...

Page 33: ...1 GND DIGITAL GROUND 12 GND DIGITAL GROUND 13 DRY CONTACT2 SIGNAL DC INPUT 14 ZONE2 FLOWTEMP 10kΩ 25 C DIGITAL INPUT 15 GND DIGITAL GROUND 16 GND DIGITAL GROUND 17 DRY CONTACT3 SIGNAL DC INPUT 18 NO CONNECT 19 GND DIGITAL GROUND 20 NO CONNECT 21 DRY CONTACT4 SIGNAL DC INPUT 22 NO CONNECT 23 GND DIGITAL GROUND 24 NO CONNECT CNS062 CNS063 EEV 1 4 EEV CONTROL PWM SIGNAL DC OUTPUT 5 DC 12V DC OUTPUT 6...

Page 34: ...r Zone 2 FCU B9 NO B10 NC B11 Neutral B12 Lived Zone1Water Pump output FSV 4061 1 B10 NC B11 Neutral Option B13 B14 B11 B12 2Way valve 2 Water pump Zone2 AC 230Voutput 10 mA 50 mA 2WayValve operation for Zone 2 FCU B13 NO B14 NC B11 Neutral B12 Lived Zone2Water Pump output FSV 4061 1 B14 NC B15 Neutral Option B15 B16 B17 B18 3Way valve AC 230V output 10 mA 50 mA 3WayValve operation for DHW B17 NO ...

Page 35: ...ENGLISH 35 02 INSTALLATION Wiring diagram AE RNW EG 1 Phase Wiring diagram AE RNW GG 3 Phase It does not support external input CNS083 output CNS081 signal function ...

Page 36: ...m Standard dimension mm Allowance mm Standard dimension mm Allowance mm Min Min Max Standard dimension mm Allowance mm Min 4 6 4 9 5 0 2 5 6 0 3 0 2 3 4 0 2 6 5 20 4 3 0 2 0 0 9 8 15 9 28 5 8 4 10 8 15 0 2 7 1 0 3 0 2 4 5 0 2 7 9 9 30 8 4 0 4 0 1 15 16 8 16 0 2 9 0 3 0 2 5 8 0 2 9 5 13 33 8 4 0 4 0 1 45 25 8 12 0 3 11 5 0 5 0 2 7 7 0 2 11 15 34 8 4 0 4 0 1 7 8 16 5 13 8 4 35 8 16 0 3 13 3 0 5 0 2 ...

Page 37: ... PV Peak power control SIGNAL Dry contact input R 32 ALARM Dry contact output WATER PUMP PWM signal output M3 5 0 8 1 2 Control Kit PBA 6PTerminal Block F1 F2 V1 V2 F3 F4 DC 5V 12V output Control Kit PBA 26PTerminal Block B1 B26 AC 220V 240V power input output M4 1 2 1 8 Control Kit PBA 2PTerminal Block TB A L l1 N N1 AC 220V 240V power input TB A1 HEATER OUT AC 220V 240V power output ...

Page 38: ... 9 Magnetic contactor 2P Single phase AC 220V 240V power input output Magnetic contactor 3P 3phase AC 380V 415V power input output ELCB 2P Single phase AC 220V 240V power input output ELCB 4P 3 phase AC 380V 415V power input output Terminal block 2P Single phase L N AC 220V 240V power input output Terminal block 8P 3 phase N L AC 220V 240V power input output L1 R L2 S L3 T N AC 380V 415V power inp...

Page 39: ...f their length does not exceed 2 m Grounding work f f Grounding must be done by a qualified installer for your safety Grounding the power cable f f The standard of grounding may vary according to the rated voltage and installation place of a heating pump f f Ground the power cable according to the following Installation place Power condition High humidity Average humidity Low humidity Electrical p...

Page 40: ...n yellow coloured grounding wire f f If the grounding wire is too short connect an extension lead in a mechanical way and wrapping it with insulating tape do not bury the connection f f Secure the grounding wire in position with staples If the grounding electrode is installed in an area of heavy traffic its wire must be connected securely NOTE 5 Carefully check the installation by measuring the gr...

Page 41: ...cabinet right When you fix the wire by cable tie Use the left hole of mount tie 2 wires for communication cable TB A TB C TB A1 1 2 1 2 F4 F3 V2 V1 F2 F1 CONTROL KIT PBA Earth Communication cable between indoor and outdoor units Communication cable Hydro unit Circuitbreaker Communication cable connection TB A TB C TB A1 1 2 1 2 F4 F3 V2 V1 F2 F1 CONTROL KIT PBA ...

Page 42: ...WER or or If the supply cable is damaged it must be replaced by a special cable or assembly available from the manufacturer or installer Circuit Breaker ELCB ELB MCCB etc for outdoor and indoor units shall be installed by installers because they are not sub parts in the units But you don t need to install for hydro unit Built in ELCB Itcausedamagetochassis PCBpartsifthemainpowerisnotconnectedcorre...

Page 43: ... unit TighteningTorque kgf cm M3 5 7 5 M5 20 30 Separate the solderless terminal up and down to prevent it being get loosen Place the thin cable upward and the thick cable downward Secure the power cable with the cable tie Cable tie Thin cable Thick cable Solderless terminal Connection of the backup heater power supply Do not use a power supply shared by other appliances Each components for outdoo...

Page 44: ...NG C1 B20 Live L B19 Neutral N 1 Before the installation hydro unit should be turned off 2 Using the appropriate equipment to correct position of terminal block as shown on the diagram 3 Make sure what type is you use Contact signal must be L When you install two thermostats thermostat2 is prior to thermostat1 Product will not operate when signal for cooling and heating mode is inputted at the sam...

Page 45: ...de UFH loops will be closed f f 220 240V f f 2 wires Normal Open or Normal Close 1 Before the installation hydro unit should be turned off 2 Using the appropriate equipment to correct position of terminal block as shown on the diagram 3 Make sure what type is you use Normal OPEN or Normal CLOSED There are 2 types of 2 way valve normal open type and normal closed type Make sure to connect terminals...

Page 46: ... The maximum allowable current that this terminal block can supply for the additional water pump is 50mA CAUTION B15 Neutral AC power output for Zone2 water pump control signal B14 Live AC power output for Zone2 water pump control signal L N M C PCB Terminal block Neutral additional pump Live additional pump B15 B14 Pump Power The maximum allowable current that this terminal block can supply for t...

Page 47: ...de floor heating loops will be closed f f 220 240V 1 Before the installation hydro unit should be turned off 2 Using the appropriate equipment to correct position of terminal block as shown on the diagram 3 Make sure what type of 3 wayV V you use A Initial OFF ON B ON OFF Field SettingValve 3071 0 Floor heating as default Field SettingValve 3071 1 DHW tank as default FLOOR HEATING A DHW TANK 3WAYV...

Page 48: ... equipment to correct position of terminal block as shown on the diagram 3 Make sure EXT CTRL signal of back up boiler must be 230Vac Do not connect supply power of back up boiler directly Heat pump does not work when the Back up boiler operates Connecting for external contact functions Screw size Tightening torque N m Part Terminal code M3 0 5 0 75 20PTerminal block 1 20 Connecting external senso...

Page 49: ... READY Signal 2 SG READY Signal 1 SG READY Signal 1 SG READY Signal 2 Product operation Short Open Forced thermo off operation Open Open Normal operation Open Short Heating DHW setting temperature 1step up operation Short Short Heating DHW setting temperature 2step up operation These parts are optional and not included with the product Maker sure to connect to non power on off contacts CAUTION ...

Page 50: ...Mode consists of Self Test Display that shows operation value satus and menus that can turn each component on or off Self Test Mode Self Test Mode Display Water Pump Booster Heater DHW Valve 3 Way valve Zone 1 Valve Back Up Heater1 Water Pump Back Up Heater2 Water Pump Back Up Boiler Zone 2 Valve Mixing Valve OFF OFF OFF OFF OFF OFF OFF OFF OFF Self Tset Mode Display Water Inlet Temp 00 0 to 000 0...

Page 51: ...ostat is used Short or open circuit error of the room temperature sensor of the Zone 1 indoor unit detected only when the room thermostat is used Wired remote controller thermistor SHORT or OPEN Zone1Water OutletThemistor SHORT or OPEN Zone2Water OutletThemistor SHORT or OPEN Water Inlet thermistor SHORT or OPEN PHE Outlet thermistor SHORT or OPEN Water Outlet thermistor SHORT or OPEN WaterTANK th...

Page 52: ...oller and the Hydro unit Tracking error between remote controller and the Hydro unit Memory EEPROM Read Write Error Wired remote controller data error E601 E604 E654 MEMORY EEPROM Read Write Error Wired controller data error Micro SD card EEPROM Downloadconnector ThermistorConnector F3 F4TerminalBlock ...

Page 53: ...w rate error in case of normal flow rate in 10min during water pump signal is OFF E911 f f Water pump ON Low flow rate NOT enough water flow Water flow 12LPM Outdoor unit capacity 9kW Water flow 7LPM Outdoor unit capacity 9kW E912 f f Water pump OFF Normal flow rate Water flow 12LPM Outdoor unit capacity 9kW Water flow 7LPM Outdoor unit capacity 9kW Water flow range Water flow rates LPM Min Max Ou...

Page 54: ...pe must be left open to the atmosphere The pressure relief device is to be operated regularly to remove lime deposits and to verify that it is not blocked How the water heater can be drained A discharge pipe connected to the pressure relief device is to be installed in a continuously downward direction and in a frost free environment CAUTION 7 10 6 8 11 5 2 3 1 4 4 3 Sanitary warm waterTank Diagra...

Page 55: ... The table above contains the different components of the functional diagrams System configuration f f For the reliable performance and durability all parts as listed below including a relief valve an expansion vessel a drain valve and pressure reducing valve should be installed according to each national or regional standards They are not supplied by SAMSUNG Pressure relief valve Expansion vessel...

Page 56: ...L When you set the hot water supply temperature to 55 C or less do not use the booster heater The heatpump and the booster heater operate until the initial set temperature is reached After that only the booster heater may operate depending on the settings NOTE ...

Page 57: ...otection cable field supply to terminalTB A1 and earth on the terminal block 5 Connector the loose ends of theTB A1 on the terminal block and the connector CNS042 on the PCB 6 Plug the thermistor cable connector in the socket X9A on the PCB 7 Connect the booster heater power supply and thermal protection cable field supply to terminal 7 8 21 22 and earth on the terminal block 8 Connect the booster...

Page 58: ...m the SV is severe it might need to be replaced Some dripping is normal Alternatively an expansion vessel can be fitted Leak warning outlet is dripping The heating element may not be properly tightened Check the heating element o ring seal and all connections There may be a leak Other problems or if none of the above solves the problem Contact the installer supplier regarding any other failure Inc...

Page 59: ...ow Maker BELIMO SIEMENS HONEYWELL Model code 3WayValve R3020 6P3 S2 VXP45 20 4 kvs 4 V5011E1213 Actuator LR230A S SSB31 ML6420A3015 Running time 90 sec 150 sec 60 sec FSV 4046 setting 9 15 6 The table above is for your reference It can be changed without advanced notice 4 Set the FSV value by referring to the table below depending on installation environment Function Details Code Unit Default Min ...

Page 60: ... valve can be used for Zone 1 and Zone 2 When both FSV 2091 and 2092 are set as 1 2 When using Zone control FSV 4061 1 ignoreThermostat signal CAUTION 2 zone control usingThermostat Under Floor Zone Controller 1 Radiators Zone Controller 2 UFHs Radiator TW4 Balancing Vessel Mixing tank Mixing Senser Default 15 m CNS045 BLU B5 Neutral N B3 CCW L2 B2 CW L1 Description No of wires Max current Thickne...

Page 61: ...want to have the lower set temperature 1 Install the mixing valve See Installation of mixing valve 2 Install the water out temperature sensors Tw2_z1 Tw2_z2 for all zones 3 Unlike the zone control with a thermostat connect the water pump signal lines to the product f f Zone1 water pump connection B10 L1 B11 N f f Zone2 water pump connection B14 L1 B15 N 4 FSV 4061 1 Enable the 2 zone control using...

Page 62: ...he pipe and then insulate it When the pipe is a copper pipe When the pipe is not a copper pipe Pipe Sensor holder Pipe Sensor Sensor clip Sensor Aluminum tape Sensor Rubber tape Sensor Cable tie insulator insulator When the holder sensor cannot be welded on the pipe fix the senor with aluminum tape and insulate it NOTE ...

Page 63: ... the EHS converter Mode Selection switch Micro SD card Left position Field SettingValue FSV mode Right position Operating Data Backup mode Left position Right position f f Micro SD card is a separate purchase using 8 32GB It s possible ...

Page 64: ...elect FSV Upload or Download Upload Uploads the FSV data of the Hydro unit to the SD card Download Downloads the FSV data of the SD card to the Hydro unit The upper level controllers excludingWi Fi kit 2 0 and MWR WW10 wired remote controller cannot use the 2 zone control and energy monitoring When connecting between the MWR WW10 wired remote controller and an upper level controller the settings f...

Page 65: ...the order of IMAGE and MICOM f f When the update fails theWired Remote Controller is reset automatically and the update proceeds again 5 When the download is finished tracking starts automatically When tracking is completed remove the microSD Card Be sure to use the microSD Card after formatting in FAT16 or FAT32 The microSD Card supports the SD or SDHC with the capacity of 1 GB to 32 GB The updat...

Page 66: ...fter finishing the reset When you reset theWired Remote Controller while the microSD Card is removed the above message appears on the screen in standby mode When you reset theWired Remote Controller while the microSD Card is removed and then inserted the following actions are performed If the reinserted microSD Card contains all the files for update update proceeds regardless of the version of the...

Page 67: ...operation will continue 2 Temperature of discharge water is controlled as time goes on like below 1 20 25 30 35 40 45 50 55 60 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Day Temp Classification Initial Heating Step raise Heating Step down Total Hour Time 96 72 24 24 24 24 24 144 24 24 24 24 24 552 Temperature 30 55 30 35 40 45 50 55 50 45 40 35 30 3 Remaining days are displayed on t...

Page 68: ... 26 27 31 32 25 Load Control 1 ON 2 3 4 DIP switch When outdoor unit only power supply change by local condition it is an option to auto restart system Classification When the outdoor unit is power off When the outdoor unit is power on Hydro Unit operation according to the DIP S W 4 setting ON default Hydro Unit E101 error occurs Hydro Unit E101 error disappears Hydro Unit operation turns off OFF ...

Page 69: ...ng HighTemp Button High Fan Button Mode change LowTemp Button Low Fan Button Entering mode for option setting Option setting mode Entering mode to set option 1 Remove batteries from the remote controller 2 Insert batteries and enter the option setting mode while pressing HighTemp button and LowTemp button 3 Check if you have entered the option setting status ...

Page 70: ...an control kit address setting option set the SEG3 as A When changing a digit of control kit installation option set the SEG3 as 2 Ex When setting the central controller into disuse status Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation PAGE MODE The option mode you want to change The tens digit of an option SEG you will change The unit digit of an option SEG you will change The changed value Ind...

Page 71: ...without using connecting sleeves their contact area becomes reduced or corrosion develops on the outer surfaces of the wires copper wires over a long time This may cause an increase of resistance reduction of passing current and consequently may result in a fire CAUTION 20 20 20 60 120 180 Powercable 20 20 20 60 120 180 Pre installed tubeforthe powercable Unit mm 3 Insert both sides of core wire o...

Page 72: ...m Insulation tape Method 2 7 After tube contraction work is completed wrap it with the insulation tape to finish Three or more layers of insulation are required Insulation tape Method 1 Insulation tape Method 2 Make sure that the connection parts are not exposed to outside Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials that have the same leve...

Page 73: ...AE200RNWMEG EU AE160RXYDEG EU space heating only MIM E03CN AE120RXYDEG EU AE260RNWMEG EU 011 1W0447 AE120RXYDGG EU AE260RNWMGG EU AE120RXYDGG EU space heating only MIM E03CN AE160RXYDEG EU AE260RNWMEG EU AE160RXYDGG EU AE260RNWMGG EU AE160RXYDGG EU space heating only MIM E03CN Model code Outdoor Model code Indoor Registration number AE040RXEDEG EU AE200RNWSEG EU 011 1W0451 AE060RXEDEG EU AE200RNWS...

Page 74: ...This appliance is filledwith R 32 ...

Reviews: