ENGLISH-29
02
INST
ALLA
TION
f
Because your air conditioner contains R-32 refrigerant, make sure that it is installed, operated, and stored it in a room
whose floor area is larger than the minimum required floor area specified in the following table:
Minimum required room area (A,m²)
m (kg)
Ceiling-mounted
Wall-mounted
Floor-standing
≤ 1.842
No requirement
1.843
3.64
4.45
28.9
1.9
3.75
4.58
30.7
2.0
3.95
4.83
34.0
2.2
4.34
5.31
41.2
2.4
4.74
5.79
49.0
2.6
5.13
6.39
57.5
2.8
5.53
7.41
66.7
3.0
5.92
8.51
76.6
3.2
6.48
9.68
87.2
3.4
7.32
10.9
98.4
3.6
8.20
12.3
110
3.8
9.14
13.7
123
4.0
10.1
15.1
136
4.2
11.2
16.7
150
4.4
12.3
18.3
165
4.6
13.4
20.0
180
4.8
14.6
21.8
196
5.0
15.8
23.6
213
- m : Total refrigerant charge in the system
- A : Minimum required floor area
f
IMPORTANT: it’s mandatory to consider either the table above or taking into consideration the local law regarding the
minimum living space of the premises.
f
Minimum installation height of indoor unit is 0.6 m for floor mounted, 1.8 m for wall, 2.2 m for ceiling.