8
Base construction and installation of the DVM Hydro
unit
Anchor specification
b
c
a
m
Size
Diameter of
drill bit (a)
Anchor length (b) Sleeve length (c)
Insert depth
Fastening
torque
M10
14 mm
75 mm
40 mm
50 mm
30 N·m
Dimension of the DVM Hydro unit
340
33
3
16
59
9
36
5
62
6
27
45
45
20
5
60
10
0
Communication cable
Liquid pipe
Gas pipe
External contact
Water outlet pipe
Water inlet pipe
Power cable
518
73.5 65
90
Unit: mm
Model name of DVM Hydro unit
ADN160BDEH
✴
ADN320BDEH
✴
ADN500BDEH
✴
Refrigerant
side
Liquid side
connection part
3/8” (ø9.52)
3/8” (ø9.52)
1/2” (ø12.7)
Gas side connection
part
5/8” (ø15.88)
7/8” (ø22.23)
1-1/8” (ø28.58)
Water side connection part
PT 1 (25A)
PT 1 (25A)
PT 1-1/4 (32A)
DVM HYDRO UNIT_IM_E_03469A(1).indd 8
2012-11-21 오후 2:32:19