background image

Troubleshooting 

Samsung Electronics

4-23

4-3-16 The others

1. E465 : Compressor over load error

t*GBDPNQSFTTPSXPSLTJNQSPQFSMZDIBOHFUIFDPNQSFTTPSBOEDIFDLJGJUXPSLTQSPQFSMZ

    

¤

 If a compressor is normal, check the assembly between Heatsink-Inverter PBA. If it is fine, change Inverter PBA.

2. E468 : Current sensor error
    

t

Check EEPROM data. 

    

t

Check PCB operates properly.

3. E471 : Oudoor EEPROM error
    

t

 Upload EEPROM on Outdoor unit Main PBA.

4. E474 : IPM(IGBT Module) or PFCM Temperature sensor Error
    

t

 E500 : IPM is over heated

    

t

 Check IPM is well assembled to heatsink

    

t

 Check whether inlet port is clogged.

    

t

 Change IPM if it is defective one

5. E554 : Gas leak error
    

t

 Check refrigerant charge

    

t

 Check Indoor EVA sensor

    

t

 Check Service valve is open.

    

t

 Check the pipes and wires correctly connected.

6. E556 : Capacity miss match between indoor and outdoor

t

 Check the model name of indoor and outdoor unit and set option code on indoor unit again.

7. Outdoor overload protection control (at the stop of the compressor.) :  E404 

t

 Check whether the fan and the motor operate normally.

t

 Check the operation of EEV.

t

 Check the temperature sensor of the indoor unit heat Exchanger.

t

 Check the indoor unit inlet blocking.

Summary of Contents for AC036KNPDEC

Page 1: ...AC048KXQPCC MG AC036KNPPCC MG AC036KXQPCC MG AC140KNPDEH EU AC140KXADGH EU AC100KNPDEH EU AC100KXADEH EU AC048KNPDEC TL AC048KXADGC TL AC036KNPDEC TL AC036KXADEC TL 1 Precautions 2 Product Specifications 3 Disassembly and Reassembly 4 Troubleshooting 5 PCB Diagram 6 Wiring Diagram 7 Reference Sheet AC048KXQPCC AC036KXQPCC AC140KXADGH AC048KXADGC AC048KNPDEC SV AC048KXADGC SV AC048KNPPCC AC036KNPPC...

Page 2: ...ting 4 1 4 2 Outdoor Trouble shooting 4 2 4 3 Troubleshooting by symptoms 4 5 4 3 1 Communication error after finishing tracking E202 4 5 4 3 2 Outdoor s service valve Clog 4 6 4 3 3 No Power completely dead Initial diagnosis 4 7 4 3 4 E102 Communication error between indoor and outdoor unit E201 Unit quantity miss matching beween Indoor and Outdoor E202 Abnormal state no communication between Ind...

Page 3: ...voltage Low voltage error 4 21 4 3 15 Pipe Blocking Error Error Code E422 4 22 4 3 16 The others 4 23 4 3 17 Setting an indoor unit installation option 4 24 5 PCB Diagram 5 1 5 1 Indoor unit 5 1 5 1 1 Main PCB 5 1 5 1 2 Power PCB 5 3 5 1 3 Panel PCB 5 4 5 2 Outdoor unit 5 5 5 2 1 Main PCB Diagram 5 5 5 2 2 Inverter PCB 5 6 5 2 3 EMI PCB 5 10 6 Wiring Diagram 6 1 6 1 Indoor unit 6 1 6 2 Outdoor uni...

Page 4: ...case any wire or power plug has been damaged replace it to eliminate any possible danger O Do not bend the power cord by force and do not put any heavy object on the power cord There is a danger of electric shock or fire O Do not use multi socket There is a danger of electric shock or fire O Ground the product if necessary Be sure to ground the product if there is any danger of electric leakage du...

Page 5: ...ious style boasts high quality interior design that fits naturally into any place O Compact Remote Controller A small hand size remote control makes it even easier to use O Long Piping Length Height It can give the benefit to the installers and aries the reliability of the air conditioner O Long Ambient Operation In LowTemperature It can arise the reliability and the capacity of the air conditione...

Page 6: ...ed part Changed item and feature Basic After changed Indoor Unit Wi Fi Function added Outdoor Unit AC048KXQPCC AC036KXQPCC AC140KXADGH AC048KXADGC Inverter controller changed Outdoor Unit AC100KXADEH AC036KXADEC 2 1 2 Changes in comparison to basic model ...

Page 7: ...xD Indoor Unit mm 610 1850 400 610 1850 400 610 1850 400 610 1850 400 610 1850 400 610 1850 400 610 1850 400 Outdoor Unit mm 940 1420 330 940 1210 330 940 1210 330 940 998 330 940 1210 330 940 998 330 940 1420 330 Shipping Dimension WxHxD Indoor Unit mm 705 1963 493 705 1963 493 705 1963 493 705 1963 493 705 1963 493 705 1963 493 705 1963 493 Outdoor Unit mm 995 1597 426 995 1388 426 995 1388 426 ...

Page 8: ...rWashing Item Descriptions Code No Q ty Remark Manual AC048 036KNPPCC DB68 04872A 1 Indoor Unit Manual AC140 100KNPDEH DB68 06271A DB68 06272A 1 Manual AC048 036KNPDEC DB68 06270A 1 Wireless Remocon DB93 15883B 1 Battery DB47 90024A 2 Holder Remocon DB61 06087A 1 Rubber Cabi Hole DB73 00195A 1 InsulationTube DB62 10944A 1 Insulation AC048 036KN DB72 50300A 1 ...

Page 9: ...6 Item Descriptions Code No Q ty Remark Insulation AC140 100KN DB72 50300C 1 Indoor Unit HolderTop DB61 40042B 1 Screw L14 6002 000538 4 Screw L12 6002 000231 4 Rubber leg DB73 20134A 4 Outdoor Unit Drain Plug DB67 00806A 1 CAP Drain DB63 10355C 3 ...

Page 10: ...Samsung Electronics 3 1 Item Remark Screw driver Monkey spanner Q Necessary Tools 3 Disassembly and Reassembly ...

Page 11: ...and disconnect the main power supply 2 Ass y Inlet Part 1 Open the Ass y Inlet and remove the safety clips 3 Ass y Cover Control 1 Loosen one fixing screw of Ass y Cover Control Use Screw driver and detach the cover 2 Lift up the Ass y Cover Control and detach it by pulling the bottom outward 3 1 Indoor Unit ...

Page 12: ...the connectors connected to Panel Outlet and the Motor Connector Motor In Panel Horizontal blade Vertical blade 4 Ass y Panel outlet 1 Loosen the 7 fixing screws of Ass y Panel Outlet and detach the panel outlet by pushing upwards Use Screw driver Detaching direction Detaching direction ...

Page 13: ...rews of EVA 3 Loosen the grounding screw 4 Pull out the sensor cable 5 Pull out the Bracket Pipe upward 6 Pull the upper part of the Heat Exchanger toward you and lift up the Heat Exchanger to detach 6 Ass y Control In 1 Loosen the 1 fixing screw of Ass y Control 2 Loosen the EVA grounding fixing screw 3 Detach the Ass y Control In by pushing it to the right Detaching direction ...

Page 14: ...ure Remark 7 Ass y Blower 1 Loosen the 1 fixing screw of Guard Fan Use Screw driver 2 Push the Guard Fan in the arrow direction and detach the guard 3 Loosen the Blower nut clockwise and pull the Blower toward you and detach it Use a monkey spanner Detaching direction ...

Page 15: ...d detach the case Use Screw driver 2 Loosen the 3 fixing screws of Motor and ground fixing screw Use a monkey spanner Remove the connectors before detaching the Motor 9 CoverTop 1 Loosen the 3 fixing screws of Cover Top and detach the cover Use Screw driver Screw TH type2 M4 L10 BLK 2 Lift up the rear of Cover Top and detach it Detaching direction ...

Page 16: ...Remark 10 Ass y Panel Outlet 1 Panel Outlet 2 As you push the 2 hooks on each side of Panel outward detach the bottom part of Partition by lifting it toward you 3 Detach the wire positioned with HolderWire 4 Detach the wire positioned with HolderWire Rear side Front side ...

Page 17: ...emark 11 Ass y Panel outlet Seperate Display PBA 1 Loosen the 2 fixing screws of Case Display PBA and detach the case Use Screw driver 2 Unlink the fixing hook placed in the middle of Case Display PBA 3 Loosen the 2 fixing screws of PBA and detach the PBA Use Screw driver ...

Page 18: ...9 No Parts Procedure Remark 12 Ass y Panel outlet Motor Step 1 Loosen the 8 fixing screws of Holder Blade and detach the holder Use Screw driver 2 Loosen the 2 fixing screws of Step Motor and detach the motor Use Screw driver 3 The detached Step Motor ...

Page 19: ...o mounting screw in the Cabinet Front RH Use Screw Driver 2 Cabi Top 1 Unscrew and remove 9 screws on each side of the Cabinet Top Use Screw Driver 3 Cabi Install Front 1 Unscrew and remove 1 screw in the Cabinet Install Front Use Screw Driver 4 Guard Cond 1 Pull the sensor from Guard Cond 2 Unscrew and remove 4 screws in the Guard Cond Use Screw Driver ...

Page 20: ...nd remove 4 screws on each side of the Cabinet Back RH Use Screw Driver 6 Cabi Install Back 1 Unscrew and remove 1 screw in the Cabinet Install Back Use Screw Driver 7 Cabi Front LF 1 Unscrew and remove 10 screws in the Cabinet Front LF Use Screw Driver 8 Fan 1 Turn 2 mounting nuts as shown in the picture and remove it Use Adjustable Wrench ...

Page 21: ... Motor mounting screws Use Screw Driver 3 Disconnect the Motor wire From Ass y Control Out 10 Bracket Motor 1 Unscrew and remove 2 mounting screws in Bracket Motor Use Screw Driver 11 Control Out 1 Disconnect 4 Connecters From Ass y Control Out 2 Unscrew and remove 1 mounting screw in Control Out Use Screw Driver 3 Separate Ass y Control Out ...

Page 22: ...Valve Use Screw Driver 3 Separate the pipe from the Entrance Exit using a welder When removing the compres sor Heat Exchanger and Pipe purge the Coolant inside the Compressor completely and remove the pipe with a welding flame 13 Assy EEV Valve 1 Unscrew and remove 2 mounting screws in Service Valve Use Screw Driver 2 Separate the pipe from the Entrance Exit using a welder ...

Page 23: ... Check the connection wire Change the Fan motor Change the Main PCB BLDC Motor is used as Fan Motor therefore if you connect or disconnect the connector while the power is still on it may get damaged Make sure to turn off the power before performing any operation Operation OFF Operation OFF Operation OFF EEPROM ERROR Change PCB Operation OFF Operation OFF Operation OFF EEPROM Option Setting Error ...

Page 24: ...utdoor unit Installation number setting error repeated indoor unit address indoor unit communication cable error Check indoor quantity setting in outdoor 11 E202 Communication error between indoor and outdoor unit Communication error on all indoor unit outdoor unit communication cable error Check electrical connection and setting between indoor unit and outdoor unit 12 E205 Communication error on ...

Page 25: ...to ZCP detection circuit problem or power failure 42 E453 Error due to overheated motor of outdoor unit s Fan1 FAN1 error 43 E455 Error due to overheated IPM of Fan1 FAN1 error 44 E458 Fan speed error FAN1 ERROR 45 E461 Error due to operation failure of inverter compressor 46 E462 System stop due to full current control 47 E463 Over current trip PFC over current error Check OLP sensor 48 E464 IPM ...

Page 26: ...sink temperature sensor error of Fan1 FAN1 error 69 E500 IPM over heat error on inverter 1 Check Outdoor Inverter PBA 70 E508 Smart install is not installed 71 E554 Gas leak detected Check the refrigerant 72 E556 Error due to mismatching capacity of indoor and outdoor unit Check the indoor and Outdoor unit Capacity 73 E557 Option code miss matching among the indoor units only for DPM Check the ind...

Page 27: ... the communication cable and replace the indoor unit PCB Remove the communication cable connecting the outdoor unit to indoor unit and measure the signal on LINE 2 of the outdoor unit with a scope Reconnect the cable connecting the outdoor unit to the indoor unit and restart the unit If the communication still doesn t work e h t e c a l p e r indoor unit PCB and Check the communication cable in ea...

Page 28: ...Clog Wire remote controller display E422 Symptom Clogging of outdoor s service valve Failure Valve clog No No Yes Yes Is the outdoor service valve clogged Was lacking in refrigerant Check the normal of EVA IN TEMP SENSOR Open the outdoor s service valve Refrigerant Charge ...

Page 29: ...0V 5 Is the wired remote controller connected correctly 2 Check procedure Yes Turn off the main power switch circuit break of power outlet and turn on again after 30 seconds Check the input power No Is the outdoor unit power supply L N 220V Yes Check the connection of the terminal block No Is the outdoor unit power voltage L N 220V Yes Replace the inverter PBA No Is the voltage between the termina...

Page 30: ...Troubleshooting 4 8 Samsung Electronics Yes Outdoor unit is not powered on Initial diagnosis 1phase cont Yes Connect the reactor No Is the reactor connector connected correctly Replace the PBA Cont ...

Page 31: ...er Check connection of the outdoor unit terminal block Check the connection wires and connectors of the indoor and outdoor units Replace the PCB of the indoor unit if the PCB Transformer fuse pcd etc fails Replace the wired remote controller Turn off the main power switch circuit break of power outlet and turn on again after 30 seconds Is the outdoor unit power supply N R N S N T 220Vac Is the out...

Page 32: ...ase cont Yes Yes Reconfigure the option DIP switches Check the system depending on the error display No No Are the option DIP switches inside the wired remote controller configured correctly Is there an error message displayed on the wired remote controller display Check the target temperature Cont ...

Page 33: ...klist 1 Is the communication cable between the indoor unit and outdoor unit connected correctly 2 Isn t the power cable and communication cable wiring error 2 Troubleshooting procedure Yes Restart after power off Is the communication error occurred again Isn t the power cable and communication cable wiring error Replace the outdoor unit PCB Terminate the service Correct the wrong wiring Is the con...

Page 34: ...resistance similar to the table on the left After confirming the state is normal end the service No Yes Replace the outdoor unit PBA ױ Power is on ױ After confirming the state is normal end the service Example COND sensor outdoorunittemperaturesensormeasuringresistancevaluebytemperature E231 E221 Example OLPsensor dischargetemperaturesensormeasuringresistancevaluebytemperature E320 E251 Currenttem...

Page 35: ... FAN MOTOR operates normally The indoor EEV operates normally The indoor heat Exchanger sensor displays the temperature ok Outdoor unit display E403 Criteria t MM UIF PQFSBUJOH JOEPPS NBDIJOFT EP OPU SFBDI GPS NPSF UIBO GJWF NJOVUFT Cause of problem t IFDL JG UIF JOEPPS 0503 PQFSBUFT OPSNBMMZ t IFDL JG UIF JOEPPS 7 PQFSBUFT OPSNBMMZ t IFDL UIF JOEPPS IFBU YDIBOHFShT 065 TFOTPS t IFDL GPS DMPHHJOH ...

Page 36: ...n the pipeline ex filter Outdoor unit display E416 Criteria t5IF DPNQSFTTPS UFNQFSBUVSF BCPWF Cause of problem t OTVGGJDJFOU DPPMBOU t MPHHJOH JO UIF PVUEPPS NBDIJOFhT TPMFOPJE WBMWF t MPHHJOH JO UIF TVC WBMWF t BMGVODUJPOJOH FYIBVTU HBT UFNQ TFOTPS t MPHHJOH JO UIF QJQFMJOF BOE UIF GJMUFS t JRVJE 7 EBNBHFE 1 How to check Test operation Check the amount of coolant Connect S net to vacuum Forceful ...

Page 37: ...mocon causes this error E441 The indoor machine remocon ON signal If the outside temperature is below 10 C before the AC runs this error occurs Causeofproblem t0 1 4 403 UFNQ BCPWF 5SJQ JT 1 How to check The above malfunction codes do not indicate a malfunction of the product All you have to do is change the temperature suitably for the limits shown in the manual When the product malfunctions if t...

Page 38: ... both terminal of sensor satisfy the resistance value in accordance with temperature 4 Is the resistance value of sensor connection pull_up correct 2 Troubleshooting procedure Isn t the Fan locked Is the connector connected correctly Is the color of Fan wire matched correctly Remove the Fan lock Connect the connector Replace the Fan Replace the PCB Normal operation Exit Yes Yes Yes No No No No ...

Page 39: ...rmal 2 Troubleshooting procedure Yes Restart after power off Is the restart error occurred again Is the interphase resistance value of compressor ulv vlw wlu normal Is the connection cable for the compressor and power terminal normal Replace the PCB Terminate the service Replace the compressor Is the compressor body and interphase resistance insulated Replace the compressor Correct the cable conne...

Page 40: ...tions Outdoor unit display E462 E484 Criteria t 5IF PVUEPPS NBDIJOF JOQVU DVSSFOU BCPWF 5SJQ Causeofproblem t IFDL UIF DPNQSFTTPS JOQVU WPMUBHF FSSPS GPS MPX WPMUBHF t IFDL UIF PWFSDVSSFOU PQUJPO TFUUJOH 1 How to check Overcurrent option setting ok Compressor input voltage supplied ok Check the input power terminal Correct the overcurrent setting ...

Page 41: ... JT PQFO t IFDL UIF BNPVOU PG DPPMBOU t IFDL UIF 0 1 TFOTPS 1 How to check No No No No No Yes Yes Yes Check the amount of coolant The sensor s resistance normal Refer to E20 The outdoor indoor EEV operates normally All the sub valves open Clogging in the pipeline ex filter Test operation Replace the OLP sensor Connect S net to vacuum forceful Open the sub valve Check the EEV Check the pipeline ...

Page 42: ...s Yes Does the compressor wire connected to the compressor normally Yes Yes Replace the compressor Reinstall and remove the obstruction Is the installation of outdoor unit good Reinstall and remove the obstruction Is the installation of indoor unit good Open valve screw to the end Are the service valves full opened Correct the compressor wire connection Is insuration resistance between each compre...

Page 43: ... tance of each contact Yes No Replace M C Check and reconnecting the AC power cable wire Is the AC Power cable connection to the outdoor unit terminal block good Check and reconnecting the reactor wire at the TAB terminal Is the connection of reactor terminal good Replace the blown FUSE Are the FUSEs on EMI PCB blown Is each contact resistance normal less than 0 1ohm Does the error reappear freque...

Page 44: ...ipe is empty and open all the service valves on the gas and liquid pipes Change and connect the pipes immediately and empty the pipes and then open the service valves Check the replacement of the EEV body coil and the refrigerant leaking part After that recharge Check the temperature value through S NET etc and then if there is a fault replace and reconnect No No No No Check the opening of the out...

Page 45: ...ule orPFCMTemperaturesensorError t E500 IPMisoverheated t CheckIPMiswellassembledtoheatsink t Checkwhetherinletportisclogged t ChangeIPMifitisdefectiveone 5 E554 Gasleakerror t Checkrefrigerantcharge t CheckIndoorEVAsensor t CheckServicevalveisopen t Checkthepipesandwirescorrectlyconnected 6 E556 Capacitymissmatchbetweenindoorandoutdoor t Checkthemodelnameofindoorandoutdoorunitandsetoptioncodeonin...

Page 46: ...the installation option according to the installation condition of an air conditioner The default setting of an indoor unit installation option is 02000 100000 200000 300000 4 Set the indoor unit option by wireless remote controller Heating setting compensation SEG21 is applied to Heat pump model only SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 0 2 RESERVED RESERVED RESERVED RESERVED SEG7 SEG8 SEG9 SEG10 SEG11 ...

Page 47: ...Samsung Electronics 5 1 5 PCB Diagram 5 1 Indoor unit 5 1 1 Main PCB This Document can not be used without Samsung s authorization ...

Page 48: ... 1 DC 12V 2 ERROR_Check 3 DC 12V 4 Comp_Chec 1 GND 2 External control 1 DC 12V 2 GND 3 PANEL_TXD 4 PANEL_RXD 5 REMOCON_RXD 6 DC 5V 7 KEY_INT 1 GND 2 GND 3 SPI_Control 4 1 F1 2 F2 3 DC 12V 4 GND 5 F3 6 F4 1 DC 12V 2 UB_12B 3 UB_12A 4 UB_12B 5 UB_12A 1 DC 12V 2 UB_12B 3 UB_12A 4 UB_12B 5 UB_12A CN02 CTRL POWER FAN CN01 AC LOAD CN41 EVA IN ROOM CN81 ERROR COMP CN83 EXT_CTRL CN61 STEP UP DOWN CN903 DI...

Page 49: ... 4 BLDC_PS 5 FAN_PWM 6 RPM_FEEDBACK 7 ZEROCROSS 8 PWR_RY_12 9 INRUSH_RY_12 10 DETECT_OV LV CN71 POWER 1 L 2 NC 3 N 4 NC 5 EARTH CN501 BLDC MOTOR 1 DC310V 2 NC 3 AGND 4 DC15V 5 Vsp 6 RPM_FEEDBACK CN02 MAIN PBA 1 FAN_TURBO_4WAWY_12 2 FAN_HIGH_FAN_12 3 FAN_LOW_COMP_12 4 HEATER_CTRL_12A 5 HEATER_ZC CN72 AC LOAD 1 N 2 NC 3 COMPRESSOR 4 OUTDOORFANMOTOR 5 OUTDOOR4WAYV V ...

Page 50: ...ics 5 1 3 Panel PCB This Document can not be used without Samsung s authorization CN903 DISPLAY 1 DC12V 2 GND 3 PANEL_TXD 4 PANEL_RXD 5 REMOCON_RXD 6 DC5V 7 KEY_INT CN31 DOWNLOAD MICOM 1 20 Download CN01 DOWNLOAD Touch IC 1 DC5V 2 GND 3 4 I2C 5 I2C ...

Page 51: ...PCB Diagram and Parts List Samsung Electronics 5 5 5 2 OUTDOOR 5 2 1 MAIN PCB Diagram ...

Page 52: ...0 DOWNLOAD 1 4 EEV SIGNAL 5 6 DC 12V 1 7 EEPROM 1 COMM SIGNAL 2 COMM SIGNAL 3 GND 4 DC 5V 5 DC 12V 6 COMM SIGNAL 1 N C 2 SENSOR SIGNAL 3 GND 4 DC 5V 1 SENSOR SIGNAL 2 N C 3 GND 4 DC 5V 1 2 COMM SIGNAL 1 EARTH CN101 POWER CN702 4WAY CN403 SENSOR CN306 DOWNLOAD CN802 EEV CN806 EEPROM CN305 COMM INV CN401 LOW PRESSURE CN402 HIGH PREWSSURE CN303 COMM INDOOR CN103 EARTH ...

Page 53: ... 3 BOOT_INV 4 TDO_INV 5 TCK_INV 6 TDI_INV 7 TMS_INV 8 nTRST 9 GND 10 11 5V 14 18 19 ENC 17 GND 20 SUB 1 DC310V 2 N C 3 GND 4 DV15V 5 FAN RPM 6 FAN RPM Feedback 1 DC310V 2 N C 3 GND 4 DV15V 5 FAN RPM 6 FAN RPM Feedback 1 COMP U phase RED 2 COMP V phase BLU 3 COMP W phase YEL 1 L phase BRN 2 N phase SKY Reactor A1 B1 Reactor A2 B2 CN351 Communication CN551 Downloader CN901 FAN1 CN911 FAN2 CN401 COMP...

Page 54: ..._INV 4 TDO_INV 5 TCK_INV 6 TDI_INV 7 TMS_INV 8 nTRST 9 GND 10 11 5V 14 18 19 ENC 17 GND 20 SUB 1 DC310V 2 N C 3 GND 4 DV15V 5 FAN RPM 6 FAN RPM Feedback 1 DC310V 2 N C 3 GND 4 DV15V 5 FAN RPM 6 FAN RPM Feedback CN401 COMP U phase RED CN402 COMP V phase BLU CN403 COMP W phase YEL 1 L phase BRN 2 N phase SKY Reactor A1 B1 Reactor A2 B2 CN351 Communication CN551 Downloader CN901 FAN1 CN911 FAN2 CN401...

Page 55: ...TXD_INV 3 BOOT_INV 4 TDO_INV 5 TCK_INV 6 TDI_INV 7 TMS_INV 8 nTRST 9 GND 10 11 5V 14 18 19 ENC 17 GND 20 SUB 1 DC310V 2 N C 3 GND 4 DV15V 5 FAN RPM 6 FAN RPM Feedback 1 DC310V 2 N C 3 GND 4 DV15V 5 FAN RPM 6 FAN RPM Feedback 1 COMP U phase RED 2 COMP V phase BLU 3 COMP W phase YEL 1 2 Reactor RST AC Power 3 Phase CN152 AC Power CN351 Communication CN551 Downloader CN901 FAN1 CN911 FAN2 CN400 COMP ...

Page 56: ...CB Diagram and Parts List 5 10 Samsung Electronics Q AC048KXQPCC AC036KXQPCC AC100KXADEH AC036KXADEC L1 BRN N1 SKY BLU 1 3 AC 220 240V L1 AC POWER L phase N1 AC POWER N phase CN01 AC POWER 5 2 3 EMI PCB ...

Page 57: ...PCB Diagram and Parts List Samsung Electronics 5 11 Q AC140KXADGH AC048KXADGC R AC 380 400V WHT S AC 380 400V BRN T AC 380 400V BLK 1 3 AC 220 240V RST AC POWER 3phase CN100 AC POWER ...

Page 58: ...Wiring Diagram Samsung Electronics 6 1 6 Wiring Diagram 6 1 Indoor Unit ...

Page 59: ...Wiring Diagram 6 2 Samsung Electronics 6 2 Outdoor unit Q AC048KXQPCC AC036KXQPCC AC100KXADEH AC036KXADEC This Document can not be used without Samsung s authorization ...

Page 60: ...Wiring Diagram Samsung Electronics 6 3 Q AC140KXADGH AC048KXADGC This Document can not be used without Samsung s authorization ...

Page 61: ...n Inv Side General Temp N Non Inv Side Low Temp R Non Inv Side Tropical Temp Z Non Inv Top Tropical Temp 1 1 In out 4Way 4 MSP Duct M Ceiling C ProductType Indoor Code Type F FLAGSHIP P PREMIUM D DELUXE S STANDARD ProductType Outdoor Code Type A STANDARD GENERAL Temp MODULE B STANDARD LOW Temp MODULE C STANDARD TROPICAL MODULE D STANDARD GENERAL Temp NON MODULE S STANDARD T DELUXE TROPICAL Capacit...

Page 62: ... BLDC Sirocco C H 510 450 390 rpm Outdoor unit Heat Exchanger FMC 16mm 1R 69S 910 2EA FP1 4 Corrugate Fan Motor BLDC Propeller RPM MAX 800 rpm Indoor unit Heat Exchanger PFE 12mm 2X63X785 6 1PASS FP1 5 Louver Fan Motor BLDC Sirocco C H 430 390 370 rpm Outdoor unit Heat Exchanger PFC 16mm 1R 69S 910 2EA FP1 4 Corrugate Fan Motor BLDC Propeller RPM MAX 800 rpm ...

Page 63: ... 430 390 rpm Outdoor unit Heat Exchanger F T Φ7W 2R 66S 950 FP1 7 Louver Fan Motor BLDC Propeller RPM MAX 800 rpm Q AC100KXADEH Indoor unit Heat Exchanger PFE 8mm 2X63X785 6 1PASS FP1 5 Louver Fan Motor BLDC Sirocco C H 410 370 350 rpm Outdoor unit Heat Exchanger F T Φ7W 2R 46S 950 FP1 7 Louver Fan Motor BLDC Propeller RPM MAX 830 rpm ...

Page 64: ...440 390 rpm Outdoor unit Heat Exchanger F T Φ7W 2R 66S 950 FP1 7 Louver Fan Motor BLDC Propeller RPM MAX 800 rpm Q AC036KXADGC Indoor unit Heat Exchanger PFE 12mm 2X63X785 6 1PASS FP1 5 Louver Fan Motor BLDC Sirocco C H 410 370 350 rpm Outdoor unit Heat Exchanger F T Φ7W 2R 46S 950 FP1 7 Louver Fan Motor BLDC Propeller RPM MAX 830 rpm ...

Page 65: ...d under applicable International and or domestic law Samsung Electronics Co Ltd May 2016 Printed in Korea Code No AC 00163E_1 631 2 6 59 3 571 5 1 7 25 UHD HE 6LWH XURSH 6 0LGHDVW IULFD JVSQ VDPVXQJFVSRUWDO FRP VLD JVSQ VDPVXQJFVSRUWDO FRP 1RUWK DWLQ PHULFD JVSQ VDPVXQJFVSRUWDO FRP KLQD FKLQD VDPVXQJSRUWDO FRP ...

Reviews: