Samsung Electronics
4-5
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2. The panel(display ) should be connected to an indoor unit to receive option.
3. Set the installation option according to the installation condition of an air conditioner.
- The default setting of an indoor unit installation option is “02000-100000-200000-300000”.
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is
more than one indoor unit.
- No need to assign SEG3, 6, 9, 10, 11, 16, 21, 22, 23, 24 which are non applicable. Even though those segments are set,
they will be ignored.
- If you set the applicable segments with numbers other than the indiciated, the initial setting will be maintained.
4. Set the indoor unit option by wireless remote controller.
4-1-4 Setting an indoor unit installation option (suitable for the condition of each installation location)
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
RESERVED
Use of external
temperature sensor
Use of central
control
RPM setting
compensation
Indication
and
Details
Indication Details Indication Details
Indication Details Indication Details
0. Not used
1. High ceiling mode
2. High ceiling kit
3. Low noise operation mode
0
2
0
Disuse
0
Disuse
1
Use
1
Use
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
Use of drain pump
RESERVED
RESERVED
RESERVED
Master / Slave
Indication
and
Details
Indication Details Indication Details
Indication Details
1
0
Disuse
0
slave
1
Use
1
master
2
Use +
3minute
delay
Option
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
Explanation
PAGE
Use of external
control
Setting the output
of external control
S-Plasma ion
Buzzer control
Number of hours
using filter
Indication
and
Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
2
0
Disuse
0
Thermo
on
0
Disuse
0
Use of buzzer
2
1000 Hour
1
ON/OFF
Control
1
Operation
on
1
Use
1
Non use
of buzzer
6
2000
Hour
2
OFF
Control
Summary of Contents for AC026FBRDEH
Page 19: ...3 10 Samsung Electronics No Parts Procedure Remark 6 Loosen fixing screws of the Cabinet Front...
Page 58: ...Samsung Electronics 5 1 5 PCB Diagram and Parts List 5 1 PCB Diagram 5 1 1 Indoor Unit...
Page 63: ...Samsung Electronics 6 1 6 Wiring Diagram 6 1 Indoor Unit...