![Samsung AC MN KH/EU Series Technical Data Book Download Page 14](http://html1.mh-extra.com/html/samsung/ac-mn-kh-eu-series/ac-mn-kh-eu-series_technical-data-book_4088144014.webp)
Wind-Free 4Way Cassette (600x600)
1. Specification
14
Model Name
Indoor Unit
AC060NNNDKH/EU
AC071NNNDKH/EU
Outdoor Unit
AC060MXADKH/EU
AC071MXADKH/EU
System
Mode
-
HEAT PUMP
HEAT PUMP
Performance Capacity
Cooling
(Min/Std/Max)
kW
1.80 / 5.80 / 6.50
2.20 / 6.80 / 8.00
Btu/h
6,100 / 19,800 / 22,200
7,500 / 23,200 / 27,300
Heating
(Min/Std/Max)
kW
1.60 / 7.00 / 9.00
1.90 / 7.50 / 9.00
Btu/h
5,500 / 23,900 / 30,700
6,500 / 25,600 / 30,700
Power
Power Input
Cooling (Min/Std/Max)
kW
0.38 / 2.15 / 2.60
0.35 / 2.72 / 3.95
Heating (Min/Std/Max)
kW
0.35 / 2.32 / 3.60
0.35 / 2.80 / 3.95
Current Input
Cooling (Min/Std/Max)
A
1.90 / 9.30 / 11.50
2.00 / 11.80 / 17.00
Heating (Min/Std/Max)
A
1.70 / 10.00 / 17.30
2.00 / 12.30 / 17.00
Current
MCA
A
21
21
MFA
A
25
25
Efficiency
EER
Cooling
W/W
2.70
2.50
COP
Heating
W/W
3.02
2.68
SEER (Cooling Energy Grade)
W/W
6.2 (A++)
6.0 (A+)
SCOP (Heating Energy Grade)
W/W
4.0 (A+)
3.8 (A)
Pdesignh
kW
2.6
4
Piping
Connections
Liquid Pipe
Type
Flare connection
Flare connection
Φ, mm
6.35
6.35
Φ, inch
1/4
1/4
Gas Pipe
Type
Flare connection
Flare connection
Φ, mm
12.7
15.88
Φ, inch
1/2
5/8
Heat Insulation
-
Both liquid and gas pipes
Both liquid and gas pipes
Piping length
(ODU-IDU)
Standard
m
5
5
Max.
m
30
50
Elevation
m
20
30
Chargeless
m
5
5
Wiring
connections
Power Source Wire
mm
2
-
-
Transmission Cable
mm
2
Min. 0.75
Min. 0.75
Remark
-
F1, F2
F1, F2
Power supply intake
-
Both indoor and outdoor unit
Both indoor and outdoor unit
Refrigerant
Type
-
R410A
R410A
Factory Charging
kg / tCO₂e
1.3 / 2.71
1.5 / 3.13