10
English
Installation Pr
oc
edur
e
Installation Procedure
Step 5 Purging inert gas from the
indoor unit
The indoor unit comes with nitrogen gas (inert gas)
charged at the factory. Therefore, all inert gas must be
purged before connecting the assembly piping.
Unscrew the pinch pipe at the end of each refrigerant
pipe.
NOTE
• To prevent dirt or foreign objects from getting into the
pipes during installation, do not remove the pinch pipe
completely until you are ready to connect the piping.
Step 6 Cutting and flaring the pipes
1
Make sure that you have the re
α
uired tools available:
pipe cutter, reamer, flaring tool, and pipe holder.
2
If you wish to shorten the pipes, cut them with a pipe
cutter, ensuring that the cut edge remains at a 90°
angle to the side of the pipe. Refer to the illustrations
below for examples of edges cut correctly and
incorrectly.
90°
990
3
To prevent any gas from leaking out, remove all burrs
at the cut edge of the pipe, using a reamer.
4
Slide a flare nut on to the pipe and flare the pipe.
D
A
90
° ±2°
D
L
45°
±
2°
Outer Diameter (D)
Depth (A)
Flare dimension (L)
Ø1/4 (6.35)
0.051 (1.3)
0.34~0.36 (8.7~9.1)
Ø3/8 (9.52)
0.071 (1.8)
0.50~0.52 (12.8~13.2)
Ø1/2 (12.70)
0.079 (2.0)
0.64~0.65 (16.2~16.6)
Ø5/8 (15.88)
0.087 (2.2)
0.76~0.78 (19.3~19.7)
Unit:inch(mm)
5
Check that the flaring is correct, referring to the
illustrations below for examples of incorrect flaring.
Insulator
Li
α
uid side
Gas side
Pipe cutter
Pipe
Obli
α
ue
Rough
Burr
Pipe
Flare
R 0.016 to 0.032 inch
(R 0.4 to 0.8 mm)
Correct
Inclined
Damaged
Surface
Cracked
Uneven
Thickness