7-2
EB 5724 EN
Start-up and configuration
7.3 Quick check
To test the electric actuator's ability to func-
tion, the following quick checks can be per-
formed:
Î
Apply the maximum and minimum con-
trol signals (e.g. over the manual level in
TROVIS-VIEW).
Î
Check the end positions of the valve.
Î
Check the travel indicator.
TROVIS 5725-3
Î
Disconnect the power supply and check
whether the valve moves to the fail-safe
position.